插座位置检查
灶台、煤气瓶、通风口或水槽附近的插座。
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
尝试一个工程 4
每项工作都会预填示例数值。请替换为您自己的数值。
- Check a power point beside a cooktopA socket‑outlet 100 mm from the cooktop edge.
- Place a power point near a gas bottleA socket‑outlet 1.2 m from an exchange gas cylinder outdoors.
- Check a light near a gas relief ventA light 1 m ahead of a 20 mm gas relief vent.
- Place the cooktop isolating switchThe cooktop switch 600 mm from the cooktop edge.
输入
使用默认输入值的示例计算。
- 国家
- 新西兰
- 附件
- 插座
- 靠近
- 灶台(开放式烹饪表面)
- 水平距离
- 300 mm
- 距楼面或地面的高度
- 1,100 mm
- 灶面高度
- 900 mm
- 上方的油烟机或橱柜
- 0 mm
- 这是灶台开关
- 否
此位置
允许
- 规则
- Cl 4.7.3
- 数值
- Figure 4.17
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 自烹饪台面边缘起算300mm
- 禁止在其范围内150mm
AS/NZS 3000:2018 Cl 4.7.3
- 禁止起始于900mm
AS/NZS 3000:2018 Cl 4.7.3
- 禁止延伸至2,500mm
AS/NZS 3000:2018 Cl 4.7.3
- 距地面高度1,100mm
- 此位置结果允许
AS/NZS 3000:2018 Cl 4.7.3
关于此计算器
How this is calculated
AS/NZS 3000 keeps socket‑outlets and switches out of a few places in a kitchen and around gas, and sets one rule near the floor. You pick the accessory, what it is near and the distances. The tool finds the rule, draws its zone and says whether the position is inside it.
Beside a cooktop, no socket‑outlet or switch may sit within 150 mm of the edge of an open gas or electric cooking surface. That band runs up from the cooking surface to the range hood, cupboard or ceiling above it, or to 2.5 m above the floor, whichever is lower. The cooktop's own switch must also be near it, in sight, not on the appliance and not reached across the cooking surface. The standard advises within 2 m, so the tool warns beyond that.
Around an outdoor gas cylinder, no ignition source may sit in the hazardous area. It is widest at the base and narrower at the top, 0.5 m above the cylinder, and an in-situ fill cylinder has a larger area than an exchange cylinder. The standard dimensions the base and the top. Between them the tool takes the edge as a straight line, as drawn, and says when a result rests on that reading. A gas relief vent has a zone ahead of it and a smaller one behind, scaled up for a vent over 50 mm. New Zealand adds an indoor cylinder compartment and the zone about a reticulated gas regulator.
Sinks, basins, baths and showers have zones of their own. The tool sends those to the wet area zones tool.
| Step | Table or clause | What it decides |
|---|---|---|
| Near the floor | Cl 4.4.2.2(b) | How a low socket‑outlet is fitted |
| Beside a cooktop | Cl 4.7.3 and Figure 4.17 | The prohibited band beside and above the cooking surface |
| The cooktop switch | Cl 4.7.1 | Where the cooktop's own switch goes |
| An outdoor gas cylinder | Cl 4.18.2.1 and Figure 4.18 | The hazardous area by cylinder type |
| An indoor cylinder | Cl 4.18.3 | No ignition source in the compartment, New Zealand |
| A gas relief vent | Cl 4.18.4 and Figure 4.19 | The exclusion zone by vent size |
| A gas regulator | Cl 4.18.5 and Figure 4.20 | The zone about the riser, New Zealand homes |
Worked examples
- A power point 100 mm from the cooktop edge. The position is Not allowed and fails: it is inside the 150 mm band, below 2.5 m.
- The cooktop switch 600 mm from the edge. The position is Allowed: outside the band, within 2 m and not reached across.
- A power point 1.2 m from a gas bottle, 300 mm up. The position is Not allowed and fails: at that height the hazardous area of an exchange cylinder reaches 1,333 mm. That figure is the straight-line reading between A and B.
- A light 1 m ahead of a gas relief vent. The position is Not allowed and fails: the zone of a 20 mm vent runs 1,500 mm along the discharge.
- A power point beside a kitchen sink. The position is Check in the wet area zones tool. Section 6 sets the zones about the sink.
Limits
The tool checks the rules named here. It does not check the hazardous area classification of Cl 7.7, equipment rated for a Zone 2 area, or the gas fitting standards. It does not set general mounting heights: AS/NZS 3000 sets none outside the rules above and Section 6. Measure on site where a result is close to a boundary.
See also: Power points near a cooktop, gas bottle and sink, Kitchen power points and the cooktop zone and Wet area zones.
问题
结果仅供设计参考。请依据现行标准核对。
插座距灶台须多远?
煤气或电热灶台开口边缘 150 mm 范围内,不得设置插座或开关。该区域从灶台表面向上延伸至上方的抽油烟机、橱柜或天花板,或距地面 2.5 m,以较低者为准。
插座距燃气瓶须多远?
位于 AS/NZS 3000 Figure 4.18 危险区域之外。对于交换式气瓶,其范围在底部为 1500 mm,顶部为 500 mm(自气瓶上方 0.5 m 起算)。对于现场灌装气瓶,分别为 3500 mm 和 1500 mm。
插座距水槽须多远?
AS/NZS 3000 在 Section 6 中依据水槽或洗手盆周围的分区对此作出规定。选择水槽后使用潮湿区域分区工具。本工具涵盖灶台、燃气及地面。
灶台隔离开关应装在哪里?
应靠近灶台,便于看见且易于触及,但不得设于电器上,也不得设于使用者需跨越灶台表面才能够到的位置。标准建议距离在 2 m 以内。该装置不得位于灶台旁的禁止区域内。
插座可以装在靠近地面的位置吗?
是的。距地面 75 mm 范围内安装时,应使插头能水平拔出,专为此设计的地面插座除外。潮湿房间的离地净距见 Section 6。
计算示例
背景
本工具读取的条款和表格
- AS/NZS 3000:2018 Cl 4.4.2.2(b)Socket‑outlets near a floor
- AS/NZS 3000:2018 Cl 4.7.1Switch for a cooktop
- AS/NZS 3000:2018 Cl 4.7.3Clearance from a cooktop
- AS/NZS 3000:2018 Cl 4.18.2.1Gas cylinders outdoors
- AS/NZS 3000:2018 Cl 4.18.3Gas cylinders indoors, New Zealand
- AS/NZS 3000:2018 Cl 4.18.4Gas relief vents
- AS/NZS 3000:2018 Cl 4.18.5Reticulated gas regulators, New Zealand
- AS/NZS 3000:2018 Cl 4.4.2.2, Cl 4.7 and Cl 4.18Where socket‑outlets, switches and other accessories may not go: floors, cooktops and gas