AS/NZS 3000:2018
Cl 2.5.3.1
Operating points of circuit-breakers and fuses
The MCB trip curve tool reads the 1.45 × In conventional operating current of Cl 2.5.3.1, and the 0.1 s instant trip and 0.4 s disconnection of Table 8.1.
已核验:对照印刷版标准阅读,页码 97, 427 (PDF = page + 4)。检查于 2 Oct 2026。
单位:Value × IN for a multiple, s for a time
这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。
4 行
| Kind | Value (× IN for a multiple, s for a time) | Clause | Page |
|---|---|---|---|
| multiple | 1.45 | Cl 2.5.3.1 | 97 |
| multiple | 1.6 | Cl 2.5.3.1 | 97 |
| time | 0.1 | Table 8.1 Note 3 | 427 |
| time | 0.4 | Table 8.1 | 427 |
读取它的工具 (2)
引用本内容的指南和学习页面 (12)
- Dairy shed motor current: 15 kW at 400 V
- Motor starting current for a 55 kW DOL start
- Hot water cylinder cable size for a 3 kW element
- What size cable for a 25 A circuit?
- What size breaker for 4 mm² cable
- AS/NZS 3008.1.2 Tables 4 to 21: current ratings
- AS/NZS 3008 vs BS 7671: cable sizing compared
- Motor full load current: 11 kW 400 V DOL
- Cable size for a 32 A single‑phase 25 m run
- Checking an existing circuit
- IB ≤ IN ≤ IZ: the overload rule on a 32 A circuit
- Motor circuits and starting