AS/NZS 3000:2018

Cl 2.5.3.1

Operating points of circuit-breakers and fuses

The MCB trip curve tool reads the 1.45 × In conventional operating current of Cl 2.5.3.1, and the 0.1 s instant trip and 0.4 s disconnection of Table 8.1.

已核验:对照印刷版标准阅读,页码 97, 427 (PDF = page + 4)。检查于 2 Oct 2026。

单位:Value × IN for a multiple, s for a time

这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。

返回 AS/NZS 3000:2018 页面上的对应卡片

4 行

Cl 2.5.3.1, Operating points of circuit-breakers and fuses
KindValue (× IN for a multiple, s for a time)ClausePage
multiple1.45Cl 2.5.3.197
multiple1.6Cl 2.5.3.197
time0.1Table 8.1 Note 3427
time0.4Table 8.1427