AS/NZS 3000:2018
Cl 2.5.3.1
Operating points of circuit-breakers and fuses
The MCB trip curve tool reads the 1.45 × In conventional operating current of Cl 2.5.3.1, and the 0.1 s instant trip and 0.4 s disconnection of Table 8.1.
Na-verify: binasa laban sa naka-print na standard, mga pahina 97, 427 (PDF = page + 4). Na-check noong 2 Oct 2026.
Mga unit: Value × IN for a multiple, s for a time
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
4 na row
| Kind | Value (× IN for a multiple, s for a time) | Clause | Page |
|---|---|---|---|
| multiple | 1.45 | Cl 2.5.3.1 | 97 |
| multiple | 1.6 | Cl 2.5.3.1 | 97 |
| time | 0.1 | Table 8.1 Note 3 | 427 |
| time | 0.4 | Table 8.1 | 427 |