跳至内容
AmpSize

This page is not in 简体中文 yet, so you are reading the English.

· 阅读约 3 分钟

Starting a loaded conveyor

电动机启动方式对比

Worked to AS/NZS 3000:2018.

A drawn result card from the Motor Starting Methods tool: lowest start current that starts the load variable speed drive.

A starter is chosen to cut the starting current. But every way of cutting the current also cuts the torque, and a loaded belt needs torque to move. This guide works a 22 kW conveyor through the motor starting comparison. The physics is in Motor starting methods: current and torque.

The motor and the load

ItemValue
Motor22 kW, 400 V, power factor 0.85, efficiency 0.9
Full load current41.51 A
Locked-rotor current7 times full load current, from the motor data
Locked-rotor torque220 % of full load torque
Load breakaway torque120 % of full load torque, a loaded belt
Fault level at the motor4 kA

Open the conveyor.

Step 1. Direct on line

The motor draws its full locked-rotor current, 290.57 A, and gives its full 220 % torque. That starts the belt easily. The cost is the current: about a 7.3 % dip at the motor with 4 kA of fault level.

Step 2. Star-delta

In star each winding sees the line voltage divided by the square root of 3. The line current falls to a third, 96.86 A, but so does the torque: 73.3 %. That is below the belt's 120 %, so star-delta cannot break it away. The motor sits stalled in star until the timer changes it to delta, and then it draws a direct on line start anyway.

Step 3. Soft starter and primary resistance

A soft starter at 3.5 times full load current draws 145.29 A, but its torque falls with the square of that limit over the locked-rotor current: 55 %. Primary resistance leaving 70 % of the voltage gives 107.8 %. Neither starts the belt.

Step 4. What does start it

  • A variable speed drive. At a 150 % current limit it gives about 150 % torque from standstill, at 62.27 A and about a 1.6 % dip. It is the lowest current that starts the belt.
  • An autotransformer at the 80 % tap. The torque is the tap squared times 220 %: 140.8 %. The line current is 185.96 A. Open the 80 % tap.
  • Direct on line, where the supply takes the dip.

With a drive limited to 110 %, the drive no longer starts the belt either, and the lowest start that does is direct on line at 290.57 A. Open the 110 % drive.

The result

MethodLine currentStarting torqueStarts the belt
Direct on line290.57 A220 %Yes
Star-delta96.86 A73.3 %No
Autotransformer, 65 % tap122.77 A93 %No
Soft starter, 3.5 times145.29 A55 %No
Variable speed drive, 150 %62.27 A150 %Yes

The comparison is at standstill. A method that only just breaks the load away can still stall during the run-up. Size the circuit-breaker so its magnetic trip clears the starting current of the method you choose. The motor tool gives the full load current and speed, and the fault level tool the fault current at the motor's board.

使用这些输入试用

驱动器电流限值
150 %
电动机处的短路电流水平
4 kA
轴功率
22 kW
负载脱离转矩
120 %
堵转电流
7 x
堵转转矩
220 %
使用这些输入打开计算器

下一步

其背后的概念

更多示例

AmpSize 是设计辅助工具。请对照现行标准核实结果。

这是否有用?

有问题,或数值看起来有误?联系我们。