跳至内容
AmpSize

This page is not in 简体中文 yet, so you are reading the English.

· 阅读约 4 分钟

Motor circuit for a 15 kW pump: DOL or star-delta

电动机回路计算器

+2 references

Worked to AS/NZS 3000:2018. Tables checked 1 Oct 2026.

A drawn result card from the Motor Circuit tool: cable and circuit-breaker 16 mm² on 32 A type D.

A motor circuit has more parts than a cable and a breaker. It has a starter, an overload relay and an isolating switch too. This guide sizes all of them for one pump with the motor circuit calculator. The ideas are in Motor starters, contactors and overload relays and Motor circuits and starting.

The pump

  • A 15 kW pump, 400 V three‑phase, power factor 0.85, efficiency 0.9.
  • The board is 30 m away. The cable runs in enclosed air.
  • The breaker is type D. The earth loop impedance at the board, Ze, is 0.35 Ω.
  • The pump starts direct on line.

Step 1. Find the running and starting current

The full load current is 28.3 A. The maker gives no locked-rotor figure, so the tool takes 8 times full load current. That is 226.4 A (AS/NZS 3000:2018 Cl 4.13.1.2(i)). A direct on line start draws all of it.

Open the tool with this pump.

Step 2. Pick the circuit-breaker and the cable

The smallest standard rating at or above 28.3 A is 32 A. A type D breaker does not trip on a start below about 10 times its rating. For 32 A, the tool takes that as 320 A. The 226.4 A start is below it, so the breaker rides through.

The cable size tool then sizes the cable for the 32 A breaker. The result is 16 mm² on 32 A type D. The voltage drop is 0.45 %.

Step 3. Pick the contactor and the relay

The tool gives a 32 A AC-3 contactor. The overload relay is set to 28.3 A, in the 23 to 32 A range. The isolating switch must be 28.3 A or more at AC-23. It can then break the locked-rotor current.

Step 4. Check the motor protection

At 15 kW the motor needs overload protection (Cl 4.13.2). It needs overtemperature protection too, because it is above 2250 W (Cl 4.13.3.1). A pump on a fire-protection service has neither (Cl 4.13.3.2).

Step 5. Compare the starters

Each row changes only the starter. The cable and the breaker stay at 16 mm² on 32 A type D.

StarterStarting currentContactorsRelay setting and range
Direct on line226.4 AMain 32 A28.3 A in 23 to 32 A
Star-delta75.47 AMain 18 A, delta 18 A, star 12 A16.34 A in 12 to 18 A
Soft starter, limit 3.5 times99.05 ABypass 32 A28.3 A in 23 to 32 A
Drive42.45 ANoneSet in the drive, 28.3 A

Open the star-delta case. A star-delta starter needs six cables to the motor. Each one carries 28.3 ÷ √3 = 16.34 A.

Step 6. Try type C

A type C breaker trips from about 5 times its rating. Open the same pump on type C. The 32 A rating no longer clears 226.4 A, so the tool moves up to 50 A. The result is 10 mm² on 50 A type C. The breaker is larger, but the cable is smaller. Type D suits this start better.

The result

ItemDirect on line
Full load current28.3 A
Locked-rotor current226.4 A
Cable and breaker16 mm² on 32 A type D
Contactor, AC-332 A
Overload relay28.3 A in 23 to 32 A
Isolating switch, AC-2328.3 A or more

The contactor frames, relay ranges and breaker bands are generic. They are not from a standard. Check the maker's catalogue and coordination tables before you order. For the earth loop and the disconnection time, see Earth fault loop impedance and disconnection time. For the running current alone, use the motor calculator.

使用这些输入试用

断路器类型
D 型曲线
效率
0.9
轴功率
15 kW
路径长度
30 m
功率因数
0.85
相
三相
启动器
直接在线启动
电压
400 V
配电箱处的 Ze
0.35 Ω
使用这些输入打开计算器

下一步

其背后的概念

更多示例

AmpSize 是设计辅助工具。请对照现行标准核实结果。

这是否有用?

有问题,或数值看起来有误?联系我们。