Bỏ qua nội dung
AmpSize

This page is not in Tiếng Việt yet, so you are reading the English.

· Đọc 4 phút

Motor circuit for a 15 kW pump: DOL or star-delta

Công cụ tính mạch động cơ

+2 references

Worked to AS/NZS 3000:2018. Tables checked 1 Oct 2026.

A drawn result card from the Motor Circuit tool: cable and circuit-breaker 16 mm² on 32 A type D.

A motor circuit has more parts than a cable and a breaker. It has a starter, an overload relay and an isolating switch too. This guide sizes all of them for one pump with the motor circuit calculator. The ideas are in Motor starters, contactors and overload relays and Motor circuits and starting.

The pump

  • A 15 kW pump, 400 V three‑phase, power factor 0.85, efficiency 0.9.
  • The board is 30 m away. The cable runs in enclosed air.
  • The breaker is type D. The earth loop impedance at the board, Ze, is 0.35 Ω.
  • The pump starts direct on line.

Step 1. Find the running and starting current

The full load current is 28.3 A. The maker gives no locked-rotor figure, so the tool takes 8 times full load current. That is 226.4 A (AS/NZS 3000:2018 Cl 4.13.1.2(i)). A direct on line start draws all of it.

Open the tool with this pump.

Step 2. Pick the circuit-breaker and the cable

The smallest standard rating at or above 28.3 A is 32 A. A type D breaker does not trip on a start below about 10 times its rating. For 32 A, the tool takes that as 320 A. The 226.4 A start is below it, so the breaker rides through.

The cable size tool then sizes the cable for the 32 A breaker. The result is 16 mm² on 32 A type D. The voltage drop is 0.45 %.

Step 3. Pick the contactor and the relay

The tool gives a 32 A AC-3 contactor. The overload relay is set to 28.3 A, in the 23 to 32 A range. The isolating switch must be 28.3 A or more at AC-23. It can then break the locked-rotor current.

Step 4. Check the motor protection

At 15 kW the motor needs overload protection (Cl 4.13.2). It needs overtemperature protection too, because it is above 2250 W (Cl 4.13.3.1). A pump on a fire-protection service has neither (Cl 4.13.3.2).

Step 5. Compare the starters

Each row changes only the starter. The cable and the breaker stay at 16 mm² on 32 A type D.

StarterStarting currentContactorsRelay setting and range
Direct on line226.4 AMain 32 A28.3 A in 23 to 32 A
Star-delta75.47 AMain 18 A, delta 18 A, star 12 A16.34 A in 12 to 18 A
Soft starter, limit 3.5 times99.05 ABypass 32 A28.3 A in 23 to 32 A
Drive42.45 ANoneSet in the drive, 28.3 A

Open the star-delta case. A star-delta starter needs six cables to the motor. Each one carries 28.3 ÷ √3 = 16.34 A.

Step 6. Try type C

A type C breaker trips from about 5 times its rating. Open the same pump on type C. The 32 A rating no longer clears 226.4 A, so the tool moves up to 50 A. The result is 10 mm² on 50 A type C. The breaker is larger, but the cable is smaller. Type D suits this start better.

The result

ItemDirect on line
Full load current28.3 A
Locked-rotor current226.4 A
Cable and breaker16 mm² on 32 A type D
Contactor, AC-332 A
Overload relay28.3 A in 23 to 32 A
Isolating switch, AC-2328.3 A or more

The contactor frames, relay ranges and breaker bands are generic. They are not from a standard. Check the maker's catalogue and coordination tables before you order. For the earth loop and the disconnection time, see Earth fault loop impedance and disconnection time. For the running current alone, use the motor calculator.

Thử với các đầu vào này

Loại aptomat
Đường đặc tính D
Hiệu suất
0.9
Công suất trục
15 kW
Chiều dài tuyến
30 m
Hệ số công suất
0.85
Các pha
Ba pha
Bộ khởi động
Khởi động trực tiếp
Điện áp
400 V
Ze tại tủ điện
0.35 Ω
Mở công cụ tính với các dữ liệu nhập này

Tiếp theo

Các khái niệm đứng sau nó

Thêm ví dụ tính toán

AmpSize là công cụ hỗ trợ thiết kế. Hãy đối chiếu kết quả với tiêu chuẩn hiện hành.

Thông tin này có hữu ích không?

Có câu hỏi, hoặc giá trị có vẻ sai? Liên hệ chúng tôi.