Ngā ture puna hiko, RCD me te whakamātautau mō tētahi wāhi hanga.

Reads AS/NZS 3012:2019. Tables checked 1 Oct 2026.

Ngā whakauru

He tauira mahi me ngā whakauru taunoa.

Whenua
Aotearoa
Pūtake tuku
Te matua a te kaituku hiko
Ara iahiko
Ko te final sub‑circuit e tīmata ana i te construction switchboard
Te tūkino e pā ana
Kāore
Ko tāu e whakamanatia ana
Ngā taputapu pūkoro ka kawea ki te mahi: ngā taputapu me ngā taputapu hiko, ngā taura, ngā pūtau toronga, ngā kaihanga hiko me ngā inverter
He RCD pūkoro te RCD
Āe
He taputapu rīhi tēnei
Kāo
He mīhini metara ūkui kei roto i te huinga hanga hiko
Kāo

Whakamarutanga tāpiri ā-RCD

E hiahiatia ana, 30 mA

Upoko tuku
AS/NZS 3012:2019 Cl 2.1.1(a)
Upoko whakamarutanga
AS/NZS 3012:2019 Cl 2.4.6.1
Wā tirohanga me whakamātautau
3months
Whakamātautau pātene RCD
Connect the portable RCD to the supply socket, then press its test button before you connect equipment. Do this again every day while it is in use
Whakamātautau wā mahi RCD
3months

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

Ngā hīkoi tātaitanga

  1. Whakaritenga punaTe matua a te kaituku hiko

    AS/NZS 3012:2019 Cl 2.1.1(a)

  2. Me whai tiaki āpitiĀe

    AS/NZS 3012:2019 Cl 2.4.6.1

  3. Au toenga teitei rawa o te ine30mA

    AS/NZS 3012:2019 Cl 2.4.6.1

  4. Wā ārahi me te wā whakamātautau3months

    AS/NZS 3012:2019 Table 6

  5. Whakamātautau pātene pana RCDConnect the portable RCD to the supply socket, then press its test button before you connect equipment. Do this again every day while it is in use

    AS/NZS 3012:2019 Table 6

  6. Whakamātautau wā mahi RCD3months

    AS/NZS 3012:2019 Table 6

  7. Ngā socket‑outlets i runga i te switchboard10A

    AS/NZS 3012:2019 Cl 2.3.4

  8. Teitei tohu isolating switch6mm

    AS/NZS 3012:2019 Cl 2.4.4

Mō tēnei tātaitai

How this is calculated

The tool gives the supply arrangement and the RCD protection for a construction or demolition site. It reads AS/NZS 3012:2019.

  1. Supply arrangement. You pick the source, such as a distributor main. The tool finds the supply clause, here Cl 2.1.1(a).
  2. Additional protection. It reads Cl 2.4.6.1 for the circuit type and the exceptions. It says whether RCD protection is required.
  3. Residual current. It gives the maximum rated residual current for that circuit.
  4. Test intervals. It reads Table 6 for the inspection and test interval of the equipment.
  5. RCD tests. Table 6 also gives the push-button test and the operating time test.
  6. Switchboard points. It points at Cl 2.3.4 for socket‑outlets and Cl 2.4.4 for the isolating switch marking.

Worked example

Limits

The RCD must trip on every active conductor and the neutral. Where a board feeds two or more lighting circuits, spread them across the RCDs. New Zealand sites also complete a Record of Assessment in the Appendix G form. The tool does not size cable. It does not check the cord length.

The tool gives one supply arrangement at a time. Pick the arrangement that matches the board in front of you. Then read the clause the tool names. Test the RCD on the site, as the intervals say. Record the results with the date.

See also: Construction site supplies to AS/NZS 3012, Builder's pole, RCDs and cord lengths and Site cord length.

Pātai

He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.

He aha te mahi a te taputapu Puna Hiko Wāhi Hanga?

Ka whakaatu te taputapu i ngā whakaritenga supply e whakaaetia ana i tētahi wāhi hanga, wāhi whakaheke rānei, i te RCD protection mō te ara iahiko, me ngā wā arotake me te whakamātautau mō ngā taputapu. Ka mahi ia i raro i AS/NZS 3012:2019.

He aha te RCD e hiahiatia ana e tētahi wāhi hanga?

Ka whakamaru a Clause 2.4.6.1 i ia rere final sub‑circuit mai i te papa hiko wāhi hanga me tētahi RCD 30 mA te nui rawa, ka whakakore i ia kaikawe ora me te neutral. E toru ngā whakahāngaitanga: ka raru pea te mahi mīkini, te puna SELV, PELV rānei, me tētahi transformer wehe haumaru.

He aha te auau o te whakamātau i ngā RCD wāhi?

Tōmua he RCD pūkaha, ka tīmata rānei te generator, te inverter e mau ana i tētahi, kātahi ka pāwhiri i tana pātene whakamātau i mua i te hono taputapu. Mahia tēnei ia rā ka whakamahia. Pāwhiritia te pātene whakamātau o tētahi RCD whakatū ia marama. Mahia te whakamātautau wā mahi ia 3 marama mō tētahi RCD pūkaha, ia 12 marama mō tētahi RCD whakatū.

Ko ēhea ngā puna hiko e whakaaetia ana i tētahi wāhi?

Ka whakaae a Clause 2.1.1 i te main a tētahi kaiwhakawhiti hiko, i tētahi papa hiko o te whakaurunga pūmau, i tētahi huanga whakaputa voltage iti e whakaaetia ana e te whakaurunga ki AS/NZS 3010, i tētahi inverter ki AS/NZS 4763. Koia AS/NZS 3012:2019; i te putanga 2010 i ingoa anō a AS 2790 mō te generator. Ko ngā momo wiriwiri motuhake ka tuku anake ki tētahi ara wehe.

Ka uru te taputapu ki te aukati insulation mō ngā kaiwelder?

Āe, engari mō ngā arc welder kua hangaia ki ngā generating set anake, ko tērā te whānui e hoatu ana e Clause 3.5.4 ki Table 7 o AS/NZS 3012:2019. Ko ētahi atu taputapu ka whai i AS/NZS 3760; ka uru te taputapu Test and Tag a AmpSize ki aua arotake.

Ngā tauira mahi

Kōrero o muri

Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu

Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi

Ngā tūtohi i arotakehia whakamutunga i te 1 Oct 2026.

He whai hua tēnei?

He pātai, he uara rānei e kitea ana he hē? Whakapā mai.