Aratohu tae waea hiko

Kimihia ngā tae waea mō ngā waea whakatū me ngā taura, tawhito me te hou.

Reads AS/NZS 3000:2018 and AS/NZS 3760:2022. Tables checked 1 Oct 2026.

Ngā whakauru

He tauira mahi me ngā whakauru taunoa.

Pātai
He aha te tae o ia kaiwhakahaere
Whenua
Aotearoa
Uaua
Uaua whakauru kua whakatūria
Ngā wāhanga
Wāhanga kotahi
Whakaurunga
Kāinga
Pakeke
Tae au

Active · neutral · earth

Red or brown · Black · Green/yellow

Ora, e tūtohua ana
Red or brown
Neutral
Pango
Whenua tiaki
Kākāriki/kōwhai
Here equipotential
Kākāriki/kōwhai

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

Ngā hīkoi tātaitanga

  1. Ora, e tūtohua anaRed or brown

    AS/NZS 3000:2018 Table 3.4 Note 2(a)

  2. KorePango

    AS/NZS 3000:2018 Table 3.4 Note 4

  3. Whenua tiakiKākāriki/kōwhai

    AS/NZS 3000:2018 Table 3.4

  4. Here equipotentialKākāriki/kōwhai

    AS/NZS 3000:2018 Table 3.4

  5. Ora, e whakaaetia anaTētahi tae atu i green, yellow, green/yellow, black or light blue

    AS/NZS 3000:2018 Table 3.4

Mō tēnei tātaitai

How this is calculated

The tool answers two questions. The first is what colour each conductor should be. The second is what a conductor of a given colour can be, when you find one on site.

For fixed installation wiring the tool reads the wiring rules' table of conductor colours. Protective earth and equipotential bonding conductors are green/yellow. A neutral is black or light blue, except in a New Zealand domestic installation, where it is black only. An active may be any colour other than green, yellow, green/yellow, black or light blue. The table's notes recommend red or brown for a single‑phase active, and red, white or blue for the actives of a multiphase circuit. The tool shows those as recommendations, beside the rule.

An older installation may carry colours from a previous edition. A bare or green earthing or bonding conductor may stay, and so may a yellow live conductor. New terminations on them take sleeving: green/yellow on the earth, white on the yellow active.

For flexible cords the tool reads the in-service testing standard. Its colour table gives the international scheme and the superseded one, which older and imported cord sets still use. A second table gives the cores of each modern cord, single phase or three phase, Class I or Class II, with or without a neutral.

To identify a colour, the tool checks every row of both standards and lists each function the colour can carry, and where.

StepTable or clauseWhat it decides
Earth, bonding and neutralTable 3.4The colour of each function in fixed wiring
Recommended activesTable 3.4 Note 2Red or brown, or red, white and blue
New Zealand domestic neutralTable 3.4 Note 4Black only
Older earths and activesCl 3.8.2.2 and Cl 3.8.2.3What may stay, and the sleeve at a new termination
Cord colours, current and supersededAS/NZS 3760 Table C.1.1The active, neutral and earth of a cord
Cord coresAS/NZS 3760 Table C.1.2The cores of each modern cord

Worked examples

  • A New Zealand house. The recommended active is red or brown, the neutral black, and the protective earth and bonding green/yellow.
  • An Australian three‑phase board. The recommended actives are red, white or blue, the neutral black or light blue, and the earth and bonding green/yellow.
  • A five-core cord. The phases are brown, black and grey, the neutral blue, and the earth green/yellow.
  • A yellow conductor in an older house. It can only be an active from a previous edition. Treat it as live and sleeve it white at a new termination.
  • A black conductor on site. Neutral or active: a neutral in fixed wiring and in a superseded cord, a phase in a modern three‑phase cord.

Limits

A colour says what a conductor should be, not what it is: prove it by test before work. The tool does not cover the special applications of Cl 3.8.3, such as numbered cores, or the internal wiring of equipment. It does not set a phase order for red, white and blue, because the table sets none.

See also: Wire colours in NZ and Australia, old and new, Reading the wiring in an older house and Test and Tag.

Pātai

He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.

He aha te tae o te waea neutral i Aotearoa?

Te pango i tētahi whakaurunga kāinga: Ka kore e whakaaetia tētahi atu tae i reira e AS/NZS 3000 Table 3.4 Note 4. Ki waho o te whakaurunga kāinga, me Ahitereiria, ka taea te neutral te pango, te kikorangi mārama rānei.

He aha te tae o te waea active?

Ko tētahi tae i tua atu i te kākāriki, te kōwhai, te green/yellow, te pango me te kikorangi mārama. E tūtohutia ana te whero, te parauri rānei mō te active wāhanga kotahi, ā, te whero, te mā, te kikorangi rānei mō ngā active o tētahi ara iahiko wāhanga maha.

He aha ngā tae waea tawhito?

He whakaurunga tawhito pea he whakawhenua kākāriki, he whakawhenua kore taupoki rānei, he kōwhai ngā kaikawe ora. Ka noho pea, engari ka whakamahia he hoaka green/yellow, ma rānei mō ngā mutunga hou ki reira. I whakamahia e ngā taura ngāwari tawhito te whero, te pango me te kākāriki.

He aha ngā tae o tētahi taura ngāwari flexible?

Parauri mō te active, kikorangi mārama mō te neutral, me green/yellow mō te whakawhenua. He parauri, pango, hina ngā wāhanga o tētahi taura wāhanga toru, me tētahi neutral kikorangi ina whai neutral.

Ka taea te whakakotahi i ngā tae Pūrope me NZ, AU rānei?

Ehara i roto i tētahi enclosure kotahi, i tētahi taura multicore kotahi rānei, e ai ki Table 3.4 Note 3. Ka uaua te pānui i ngā wāhanga ina tata ngā core parauri me te hina ki ngā core whero, mā, kikorangi.

Ngā tauira mahi

Kōrero o muri

Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu

Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi

Ngā tūtohi i arotakehia whakamutunga i te 1 Oct 2026.

He whai hua tēnei?