Arotake wāhi power point
Ngā power point tata ki te kaupoi kai, te ipu gas, te kōrere, te tōrino rānei.
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
Whakamātau mahi 4
Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.
- Check a power point beside a cooktopA socket‑outlet 100 mm from the cooktop edge.
- Place a power point near a gas bottleA socket‑outlet 1.2 m from an exchange gas cylinder outdoors.
- Check a light near a gas relief ventA light 1 m ahead of a 20 mm gas relief vent.
- Place the cooktop isolating switchThe cooktop switch 600 mm from the cooktop edge.
Ngā whakauru
He tauira mahi me ngā whakauru taunoa.
- Whenua
- Aotearoa
- Taputapu āpiti
- Pūrere (power point)
- Tata
- Cooktop (te mata tunu tuwhera)
- Tawhiti whakapae
- 300 mm
- Teitei ki runga i te papa, rānei i te whenua
- 1,100 mm
- Teitei o te mata tunu
- 900 mm
- Hūdi kāpata, kabete rānei i runga
- 0 mm
- Koia te whakawhiti papa kai
- Kāo
Tēnei tūnga
Whakaaetia
- Ture
- Cl 4.7.3
- Tauira
- Figure 4.17
He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.
Ngā hīkoi tātaitanga
- Mai i te tapa o te mata tunu kai300mm
- Kua aukatia i roto i150mm
AS/NZS 3000:2018 Cl 4.7.3
- Kua aukatia mai i900mm
AS/NZS 3000:2018 Cl 4.7.3
- Kua aukatia tae atu ki2,500mm
AS/NZS 3000:2018 Cl 4.7.3
- Teitei ki runga i te papa1,100mm
- Tēnei tūngaHuaWhakaaetia
AS/NZS 3000:2018 Cl 4.7.3
Mō tēnei tātaitai
How this is calculated
AS/NZS 3000 keeps socket‑outlets and switches out of a few places in a kitchen and around gas, and sets one rule near the floor. You pick the accessory, what it is near and the distances. The tool finds the rule, draws its zone and says whether the position is inside it.
Beside a cooktop, no socket‑outlet or switch may sit within 150 mm of the edge of an open gas or electric cooking surface. That band runs up from the cooking surface to the range hood, cupboard or ceiling above it, or to 2.5 m above the floor, whichever is lower. The cooktop's own switch must also be near it, in sight, not on the appliance and not reached across the cooking surface. The standard advises within 2 m, so the tool warns beyond that.
Around an outdoor gas cylinder, no ignition source may sit in the hazardous area. It is widest at the base and narrower at the top, 0.5 m above the cylinder, and an in-situ fill cylinder has a larger area than an exchange cylinder. The standard dimensions the base and the top. Between them the tool takes the edge as a straight line, as drawn, and says when a result rests on that reading. A gas relief vent has a zone ahead of it and a smaller one behind, scaled up for a vent over 50 mm. New Zealand adds an indoor cylinder compartment and the zone about a reticulated gas regulator.
Sinks, basins, baths and showers have zones of their own. The tool sends those to the wet area zones tool.
| Step | Table or clause | What it decides |
|---|---|---|
| Near the floor | Cl 4.4.2.2(b) | How a low socket‑outlet is fitted |
| Beside a cooktop | Cl 4.7.3 and Figure 4.17 | The prohibited band beside and above the cooking surface |
| The cooktop switch | Cl 4.7.1 | Where the cooktop's own switch goes |
| An outdoor gas cylinder | Cl 4.18.2.1 and Figure 4.18 | The hazardous area by cylinder type |
| An indoor cylinder | Cl 4.18.3 | No ignition source in the compartment, New Zealand |
| A gas relief vent | Cl 4.18.4 and Figure 4.19 | The exclusion zone by vent size |
| A gas regulator | Cl 4.18.5 and Figure 4.20 | The zone about the riser, New Zealand homes |
Worked examples
- A power point 100 mm from the cooktop edge. The position is Not allowed and fails: it is inside the 150 mm band, below 2.5 m.
- The cooktop switch 600 mm from the edge. The position is Allowed: outside the band, within 2 m and not reached across.
- A power point 1.2 m from a gas bottle, 300 mm up. The position is Not allowed and fails: at that height the hazardous area of an exchange cylinder reaches 1,333 mm. That figure is the straight-line reading between A and B.
- A light 1 m ahead of a gas relief vent. The position is Not allowed and fails: the zone of a 20 mm vent runs 1,500 mm along the discharge.
- A power point beside a kitchen sink. The position is Check in the wet area zones tool. Section 6 sets the zones about the sink.
Limits
The tool checks the rules named here. It does not check the hazardous area classification of Cl 7.7, equipment rated for a Zone 2 area, or the gas fitting standards. It does not set general mounting heights: AS/NZS 3000 sets none outside the rules above and Section 6. Measure on site where a result is close to a boundary.
See also: Power points near a cooktop, gas bottle and sink, Kitchen power points and the cooktop zone and Wet area zones.
Pātai
He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.
He tawhiti pēhea te tika o tētahi power point mai i tētahi cooktop?
Kaua he socket‑outlet, he switch rānei i roto i te 150 mm o te tapa o tētahi papa tunu kāsi, hiko rānei kua whakatuwhera. Ko te rohe e toro atu ana mai i te papa tunu ki te range hood, te kāpata, te tuanui rānei kei runga ake, ki te 2.5 m i runga i te papa rānei, ko te mea iti ake.
He tawhiti pēhea te tika o tētahi power point mai i tētahi gas bottle?
I waho o te rohe mōrearea o AS/NZS 3000 Figure 4.18. Mō tētahi ipu hoatu, ka tae ki te 1500 mm i te tūāpapa me te 500 mm i te tihi, 0.5 m i runga ake i te ipu. Mō tētahi ipu whakakī-ā-wāhi, 3500 mm me 1500 mm.
He tawhiti pēhea te tika o tētahi power point mai i tētahi sink?
Ka whakatakoto a AS/NZS 3000 i tēnei i Section 6, mā ngā rohe huri i te tōrino, i te ipu wai. Whakamahia te taputapu wet area zones me te tōrino kua kōwhiria. Ka hipoki tēnei taputapu i ngā kaupoi kai, te hau me ngā papa.
Kei hea te whakatakoto i te cooktop isolating switch?
Tata ki te kaupoi kai, kitea ana, ngāwari te tae atu, engari ehara i runga i te taputapu, ehara hoki i te wāhi e totohe ai te kaiwhakamahi i te papa tunu. E tohutohu ana te paerewa ki roto i te 2 m. Kāore e taea te noho ki te rohe kua aukatia i te taha o te kaupoi kai.
Ka taea te whakanoho i tētahi power point tata ki te papa?
Āe. Ina tata ki te 75 mm o te papa, ka whakaurua kia puta pai te plug i te taha pāhiko, engari mēnā he floor socket‑outlet i hangaia mō tērā. Ko ngā rūma wai he mātāwāhi papa tōna ake i Section 6.
Ngā tauira mahi
Kōrero o muri
Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu
- AS/NZS 3000:2018 Cl 4.4.2.2(b)Socket‑outlets near a floor
- AS/NZS 3000:2018 Cl 4.7.1Switch for a cooktop
- AS/NZS 3000:2018 Cl 4.7.3Clearance from a cooktop
- AS/NZS 3000:2018 Cl 4.18.2.1Gas cylinders outdoors
- AS/NZS 3000:2018 Cl 4.18.3Gas cylinders indoors, New Zealand
- AS/NZS 3000:2018 Cl 4.18.4Gas relief vents
- AS/NZS 3000:2018 Cl 4.18.5Reticulated gas regulators, New Zealand
- AS/NZS 3000:2018 Cl 4.4.2.2, Cl 4.7 and Cl 4.18Where socket‑outlets, switches and other accessories may not go: floors, cooktops and gas
Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi
Ngā tūtohi i arotakehia whakamutunga i te 1 Oct 2026.
Ngā taputapu hononga
He whai hua tēnei?
He pātai, he uara rānei e kitea ana he hē? Whakapā mai.