NZS 4512:2010

Cl 406

Alerting device sound pressure levels

The sounder level tool reads the 10 dB and 5 dB margins over the residual level, the 65 dB to 100 dB band, the bedhead and balcony levels, the 90 dB visual device trigger, the care area margin and the measurement height, from Clauses 406.3, 406.4 and 406.7.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 62–63. I tirohia 26 Sept 2026.

Ngā unit: Level dB LAFmax, Trigger dB LAeq(10min), Margin dB, Height m

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi NZS 4512:2010

1 rārangi

Cl 406, Alerting device sound pressure levels
Min dbMax dbBedhead min dbBalcony min dbMargin voice dbMargin tone dbVisual trigger dbHospital margin dbMeasurement height M
6510075651059051.8