Whakawhiti ki te ihirangi
AmpSize

This page is not in Te reo Māori yet, so you are reading the English.

· 4 meneti te pānui

Solar DC string and array cable, AS/NZS 5033

Tātaitai PV string

+5 references

Worked to AS/NZS 5033:2021 and AS/NZS 3008.1.1:2025 (AU). Tables checked 2 Oct 2026.

A drawn result card from the PV String Sizing tool: modules per string 5 to 11.

An Australian roof gets two strings of ten modules. The strings run 30 m to the inverter. This guide finds the cable currents from AS/NZS 5033 and sizes the d.c. cables for a hot roof. It then sizes the a.c. cable on AS/NZS 3008.1.1:2025.

The system

  • Modules: 49.5 V Voc, 41.5 V Vmp, 13.9 A Isc. Voc coefficient −0.27 %/K, Vmp coefficient −0.35 %/K.
  • Site: record low 2 °C, record high 40 °C. A 600 V inverter with a 150 V to 550 V MPPT window.
  • Two strings of 10 modules in parallel.

The currents

Open the string run. The tool allows 5 to 11 modules per string. Ten fit. The string reaches 525.7 V at the coldest cell. Its Vmp at the hottest cell is 342.4 V.

The tool counts the string current as 1.25 × KI × Isc under AS/NZS 5033:2021 Cl 3.3.3.1. That gives 17.38 A. Table 4.2 sets the array cable at both strings together: 34.75 A. The smallest conductor is 4 mm² (Cl 4.4.2.3).

The hot roof

Cl 4.4.2.2 takes the cable temperature near the modules as the record high plus 40 K. The tool gives 80 °C. 75 °C PVC cannot work there. The d.c. cable size tool refuses a PVC entry at that air temperature. Use XLPE.

Open the string cable. The inputs are 342.4 V, 17.38 A and 30 m. The cables are two single‑core. The drop limit is 3 %. The air is at 80 °C. The ambient factor from Table 3.44 is 0.45. The tool picks 6 mm². The corrected rating is 21.15 A and the drop is 1.2 %.

At 40 °C air the same string needs only 2.5 mm² for current and drop. The 5033 minimum of 4 mm² then governs. The roof temperature sets the size, so use the hot value.

The array cable

The array cable runs 12 m from the combiner to the inverter. At 40 °C, the tool picks 4 mm². The corrected rating is 37 A and the drop is 1.44 %. At 45 °C the rating falls to 35.15 A. 4 mm² still passes.

The tool does not count grouping here. Add grouped circuits when cables touch. It also does not check the d.c. protective device. Check that rating against Iz.

The a.c. side

The inverter output is 21.7 A at 230 V. Run it 15 m to the board on the 2025 edition. Open the a.c. run. The tool picks 2.5 mm², rated 22 A, with a drop of 2.55 %. The margin is only 0.3 A. A longer or hotter run needs 4 mm².

The array isolator

The PV array tool reads the same currents. It gives a string cable current of 17.38 A and an array cable current of 34.75 A. The d.c. isolator needs at least 34.75 A at 525.7 V. The earth or bonding conductor is at least 4 mm² under Table 4.6.

Those figures match the cable run. The isolator, the cable and the protection all rest on the same two currents. Read the maker's data for the isolator ratings.

Before you order

Check each cable against the data sheets. The module maker sets the maximum series fuse. The inverter maker sets the voltage and current limits. The tool reads the inputs you give it, and nothing else.

Roof cable is exposed to sun and weather. Use cable marked for d.c. and UV exposure, and clip it clear of the roof sheet. The tool sizes the conductor. It does not choose the cable type.

The result

CableSizeCorrected ratingDrop
String, 80 °C roof, 30 m6 mm²21.15 A1.2 %
Array, 40 °C, 12 m4 mm²37 A1.44 %
A.c. to the board, 15 m2.5 mm²22 A2.55 %

Try it with these inputs.

This page is a design aid. Verify every value against the current edition of the standard.

See also: Solar string sizing for a 600 V inverter, PV string voltage and temperature and DC cable size for a 48 V battery and PV array.

Whakamātau ki ēnei whakauru

Uara d.c. teitei rawa o te inverter
600 V
Module Isc
13.9 A
Pūtau aho teitei rawa o te module
25 A
Ngā module ia takirua
10
Uara MPPT teitei rawa
550 V
Uara MPPT iti rawa
150 V
Pāmahana teitei rawa i rekodia
40 °C
Pāmahana iti rawa i rekodia
2 °C
Ngā aho takirua
2
Tauwhāinga pāmahana Vmp
−0.35 %/K
Module Vmp
41.5 V
Tauwhāinga pāmahana Voc
−0.27 %/K
Module Voc
49.5 V
Whakatuwhera te tātaitai me ēnei whakauru

Hei whai ake

Ngā whakaaro o muri i tēnei

Ētahi atu tauira mahi

He āwhina hoahoa a AmpSize. Arotakehia ngā otinga ki te paerewa o nāianei.

He whai hua tēnei?

He pātai, he uara rānei e kitea ana he hē? Whakapā mai.