Test results checker

Tingnan ang nasukat na test results laban sa Section 8 limits.

Reads Electricity (Safety) Regulations 2010, AS/NZS 3000:2018 and AS/NZS 3017:2022. Tables checked 26 Sept 2026.

Mga input

Worked example gamit ang mga default na input.

Protective device
Type B circuit-breaker
Device rating
20 A
Disconnection time
0.4 s
Active conductor
2.5 mm²
Kaso ng insulation test
General circuit sa 500 V
Suriin ang insulation resistance
Oo
Sinukat na insulation resistance
50 MΩ
Suriin ang earth continuity
Oo
Sinukat na resistance ng earth conductor ng subcircuit
0.3 Ω
Suriin ang loop impedance
Oo
Sinukat na Zs
1.2 Ω
Suriin ang trip time ng RCD
Hindi
Kumpirmadong polarity
Oo

Verification

Pasa

Insulation resistance
Pasado. 50 MΩ, pinakamababang 1 MΩ
Earth continuity, subcircuit earth conductor
Pasado. 0.3 Ω, pinakamataas na 0.9 Ω
Earth fault loop impedance
Pasado. 1.2 Ω, pinakamataas na 2.9 Ω

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Limit ng insulation resistance1MΩ

    AS/NZS 3000:2018 Cl 8.3.6

  2. Test voltage500V

    AS/NZS 3000:2018 Cl 8.3.6

  3. Limit ng earth continuity, subcircuit earth conductor0.9Ω

    AS/NZS 3000:2018 Table 8.2

  4. Pinakamataas na earth fault loop impedance2.9Ω

    AS/NZS 3000:2018 Table 8.1

  5. Pinakamataas na Rphe sa 80 porsiyento ng rated current1.8Ω

    AS/NZS 3000:2018 Table 8.2

  6. Pinakamataas na Re sa 80 porsiyento ng rated current0.9Ω

    AS/NZS 3000:2018 Table 8.2

  7. Limit ng insulation resistance, AS/NZS 3017:20221MΩ

    AS/NZS 3017:2022 Cl 4.5.4

  8. Main earth at bonding limit, AS/NZS 3017:20220.5Ω

    AS/NZS 3017:2022 Cl 4.4.4

  9. Polarity at mga koneksyon ng circuitNakumpirma

    AS/NZS 3017:2022 Cl 4.6.4

  10. Pumasa ang mga pagsusuri3 of 3

Tungkol sa calculator na ito

How this is calculated

The tool compares your measured test values with the limits for the circuit. Tick the tests you did. The tool checks only those.

  1. Insulation resistance. The tool reads the minimum and the test voltage from AS/NZS 3000 Cl 8.3.6. It also reads the AS/NZS 3017:2022 figure from Cl 4.5.4.
  2. Earth continuity. It reads the limit for the earth conductor size from Table 8.2. It also reads the limit at 80 % of the rated current. AS/NZS 3017:2022 Cl 4.4.4 gives the main earth and bonding limit.
  3. Loop impedance. It reads the maximum Zs for the device and disconnection time from Table 8.1.
  4. RCD trip time. It compares your measured time with the limit for the rated residual current.
  5. Polarity. You confirm polarity and connections. The tool does not measure them. It points at AS/NZS 3017:2022 Cl 4.6.4.
  6. Verdict. The result passes only when every test you ticked passes.

Worked example

Limits

The tool does not take your readings. It does not correct a loop reading for temperature. A pass here is not a certificate. A competent person signs the verification. Use the loop impedance calculator to predict Zs before the test.

See also: Testing to Section 8, Earth fault loop impedance and maximum Zs and Table 8.1 maximum Zs explained.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng Test Results tool?

Ikinukumpara ng tool ang mga value na sinukat mo sa site sa acceptance limit ng AS/NZS 3000 Section 8. Sinusuri nito ang insulation resistance, earth continuity, loop impedance at RCD trip time. Ang bawat check ay nagbibigay ng pass o fail. Ang pangkalahatang verdict ay pass, fail, o not verified.

Ano ang minimum insulation resistance?

Ang Clause 8.3.6.3 ay nagbibigay ng 1 megohm sa 500 V direct. Ang sheathed heating element ay 0.01 megohm, at ang RCD functional earth connection ay 0.05 megohm. Kapag may surge protective o electronic equipment, puwedeng ibaba ang test voltage sa 250 V.

Aling loop impedance limit ang ginagamit nito?

Ang nakalistang maximum Zs mula sa AS/NZS 3000:2018 Table 8.1 para sa uri ng device, rating at disconnection time. Iniuulat din ng tool ang maximum Rphe at Re ng Table 8.2 sa 80 porsyento ng rated current, na kapaki-pakinabang sa pagsubok na walang load.

Bakit sinasabi ng tool na Not verified?

Hindi nagawa ang test na hiniling mo. Walang row sa Table 8.1 para sa device rating, o walang test na napili. Hindi nag-uulat ang tool ng pass sa check na hindi nito nagawa. Baguhin ang rating, o gamitin ang loop impedance tool.

Saan pumapasok ang AS/NZS 3017:2022?

Ibinibigay ng AS/NZS 3017:2022 ang mga paraan para sa bawat verification test. Tugma ang insulation at main earth limits nito sa Section 8, kaya binabanggit ng tool ang dalawa. Nire-round sa isang decimal ang loop impedance table nito, kaya ginagamit ng tool ang Table 8.1 para sa Zs.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 26 Sept 2026.

Nakatulong ba ito?

May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.