Test and tag intervals

Mga retest interval at pass limit para sa portable gear.

Reads AS/NZS 3760:2022. Tables checked 1 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Environment
1 · Mga pabrika, workshop, paggawa, assembly, maintenance
Kagamitan
Class I equipment
RCD
Walang RCD
Suriin ang earth continuity
Oo
Sinukat na earth resistance
0.4 Ω
Suriin ang insulation resistance
Oo
Sinukat na insulation resistance
25 MΩ
Suriin ang leakage current
Hindi
Suriin ang tripping time ng RCD
Hindi

Agwat ng retest

6months

Pagtatago ng talaan
7 taon
Earth continuity
0.4 laban sa 1
Insulation resistance
25 laban sa 1

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Agwat ng retestResulta6months

    AS/NZS 3760:2022 Table 2.4

  2. Limit ng earth continuity1Ω

    AS/NZS 3760:2022 Cl 2.4.3.1

  3. Limit ng insulation resistance1MΩ

    AS/NZS 3760:2022 Table 2.2

  4. Limit ng leakage current5mA

    AS/NZS 3760:2022 Table 2.1

  5. Limit ng oras ng trip ng RCD300ms

    AS/NZS 3760:2022 Table 2.3

  6. Limit ng oras ng trip ng RCD, permanenteng nakakabit na may external timing300ms

    AS/NZS 3760:2022 Cl 2.4.3.4

  7. Pagtatago ng talaan7

    AS/NZS 3760:2022 Cl 2.6.2

Tungkol sa calculator na ito

How this is calculated

The tool gives the retest interval for portable electrical equipment. It checks test readings against the limits of AS/NZS 3760:2022. It does not print a tag.

  1. Interval. You pick the environment, from 1 to 8. The tool reads the retest interval for that environment and the equipment class from Table 2.4.
  2. Earth continuity. For Class I equipment, the tool reads the earth continuity limit from Cl 2.4.3.1 and compares your reading.
  3. Insulation resistance. It reads the minimum insulation resistance for the equipment from Table 2.2. Your reading must not be lower.
  4. Leakage current. Table 2.1 gives the leakage limit. The tool checks it only when you enter a reading.
  5. RCD trip time. Table 2.3 gives the trip time limit for a portable or fixed RCD. A permanently wired RCD with external timing uses Cl 2.4.3.4.
  6. Records. Cl 2.6.2 sets how long you keep the test record. The tool states that period.
StepTable or clauseWhat it decides
IntervalAS/NZS 3760:2022 Table 2.4How often you retest
Earth continuityCl 2.4.3.1The highest resistance that passes
Insulation resistanceTable 2.2The lowest resistance that passes
Leakage currentTable 2.1The highest leakage that passes
RCD trip timeTable 2.3 and Cl 2.4.3.4The slowest trip that passes
RecordsCl 2.6.2How long you keep the record

Worked example

  • Class I equipment in environment 2. Environment 2 covers flexing cord, abuse or a hostile place. The retest interval is 12 months. The tool keeps the record for 7 years. An earth reading of 0.4 Ω passes against a limit of 1 Ω. An insulation reading of 25 MΩ passes against 1 MΩ.

Limits

The tool reports the interval and compares the readings you type. It does not run a test. It does not print a tag. Cl 2.5.2.1 says what a tag must carry. Check the tag against that clause.

The tool gives one interval for one environment. Equipment used in more than one environment needs your own decision.

See also: Testing to Section 8, the test results checker and the assessment intervals tool.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng Test and Tag tool?

Iniuulat ng tool ang retest interval para sa environment na pipiliin mo. Iniuulat nito ang push-button at operating time interval para sa portable o fixed RCD. Ibinibigay nito ang pass limit para sa leakage current, earth continuity at insulation resistance. Pagkatapos, sinusuri nito ang mga value na sinukat mo.

Gaano kadalas dapat subukan ang equipment?

Itinatakda ng AS/NZS 3760:2022 Table 2.4 ang interval ayon sa environment. Nagbibigay ito ng 6 na buwan para sa factories, workshops at commercial cleaning. Nagbibigay ito ng 12 buwan kapag gumagalaw ang cord, o kapag malupit o bukas sa pang-aabuso ang lugar. Nagbibigay ito ng 5 taon kapag walang nalalapat, at 2 taon sa hotel residential areas. 3 buwan ang hire equipment.

Ano ang mga pass limit?

Hindi dapat lumampas sa 1 ohm ang protective earth circuit. 1 megohm ang insulation resistance, pareho para sa Class I at Class II. 0.05 megohm ito para sa PRCD functional earth, at 0.01 megohm para sa sheathed heating element. 5 mA ang leakage para sa Class I at 1 mA para sa Class II.

Anong trip time ang dapat tugunan ng RCD?

Nagbibigay ang Table 2.3 ng 300 ms para sa 30 mA Type II device at 40 ms para sa 10 mA Type I device. Ibinibigay ng Clause 2.4.3.4 ang parehong oras para sa RCD na permanenteng nakakabit sa loob ng equipment at tinatimingan mula sa labas. Ang 2010 edition ay nagbigay ng 150 ms doon, kaya ang fixed RCD na nasa pagitan ng 150 at 300 ms ay pumapasa na ngayon.

Aling edition ang ginagamit ng tool?

AS/NZS 3760:2022, sa printing nito na may Amendment 1. Tugma ang limits at intervals sa 2010 edition. Dinadagdagan ng Table 2.4 ang second-hand equipment, na tumuturo sa AS/NZS 5761. Inirerekomenda ng Clause 2.6.2 ang 7 taon kapag may nakatalang records, at ipinauubaya ito sa regulator.