Fault level calculator

Prospective fault current sa board mula sa source nito.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Mga input

Worked example gamit ang mga default na input.

Pinagmulan
Transformer
Rating ng transformer
500 kVA
Transformer impedance
4.5 %
Line voltage
400 V
Standard
NZ · AS/NZS 3008.1.2
Haba ng submain
30 m
Laki ng conductor
35 mm²
Material
Tanso
Insulation
PVC 75 °C
Mga core
Multicore
Mga cable na parallel
1
Breaking capacity ng circuit-breaker
15 kA

Three-phase fault current sa board

10.01kA

Phase-earth fault current, maximum
3.18kA
Phase-earth fault current, cable hot
2.63kA
Source impedance kada phase
14.4mΩ
Breaking capacity
15kA

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Impedance ng transformer kada phase, U² ÷ S × Z%0.01Ω
  2. Fault current sa source16.04kA
  3. Submain phase resistance sa operating temperature0.02Ω

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  4. Submain phase resistance sa 20 °C0.02Ω

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  5. Submain phase reactance0Ω

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  6. Laki ng protective conductor10mm²

    AS/NZS 3000:2018 Table 5.1

  7. Protective conductor resistance sa 20 °C0.06Ω

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  8. Three‑phase fault current sa board, U0 ÷ |Z|Resulta10.01kA
  9. Phase-earth fault current sa board, pinakamataas3.18kA
  10. Phase-earth fault current, cable sa operating temperature2.63kA
  11. Breaking capacity ng circuit-breaker15kA

Tungkol sa calculator na ito

How this is calculated

The tool finds the fault current at a board. The source is a transformer or a stated supply fault level. A submain then adds impedance. The tool compares the result with the breaking capacity of your device.

  1. Source impedance. For a transformer, the tool works Z = U² ÷ S × Z% per phase. It takes the source as all reactance. That gives the highest current for the size.
  2. Source current. It gives the fault current at the transformer terminals.
  3. Submain impedance. It reads the resistance and reactance of the submain for your size, length and material. The tables are Table 30 for reactance and Tables 34 and 35 for resistance. It scales the resistance to 20 °C for the maximum figure.
  4. Protective conductor. It reads the earth conductor size from Table 5.1 of AS/NZS 3000:2018. It adds that resistance to the earth loop.
  5. Fault currents. It gives the three‑phase current as U0 ÷ |Z|. It also gives the phase-earth current, maximum and with the cable hot.
  6. Breaking capacity. It compares the three‑phase current with the rating you enter.
StepTable or clauseWhat it decides
Submain reactanceAS/NZS 3008.1.2 Table 30The reactance of the submain
Submain resistanceAS/NZS 3008.1.2 Tables 34 and 35The resistance of the submain
Earth conductorAS/NZS 3000 Table 5.1The size of the protective conductor

Worked example

Limits

  • The tool works at nominal voltage. It does not apply the IEC 60909 voltage factors.
  • It takes the network above the transformer as infinite. A real network lowers the current a little.
  • It takes the phase-earth loop at the transformer as its phase impedance, as for a Dyn transformer.
  • It does not add motor contribution. It does not grade devices. Use the IDMT tool for grading.
  • The result is an estimate for sizing. Ask the network company for the supply fault level at the point of supply.

See also: Prospective fault current at a board, Fault level at a sub‑board on a 300 kVA transformer and Fault rating.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Paano kinakalkula ng fault level tool ang current?

Idinadagdag nito ang impedance kada phase. Ang transformer ay nagbibigay ng U² ÷ S × Z%, at ang supply ay nagbibigay ng phase voltage na hinati sa fault level nito. Idinadagdag ng submain ang resistance at reactance nito mula sa AS/NZS 3008.1 impedance tables. Ang phase voltage na hinati sa kabuuan ang three‑phase fault current sa board.

Bakit may dalawang phase-earth figure?

Nakalista sa table ang resistance sa operating temperature ng conductor. Ang malamig na cable ang nagbibigay ng pinakamataas na current, kaya ang maximum ay ini-scale ang resistance sa 20 °C. Ang hot figure ang mas mababa, para sa disconnection time check sa loop impedance tool.

Ano ang ipinapalagay ng tool tungkol sa source?

Itinuturing nito ang source bilang puro reactance, at ang network sa itaas ng transformer bilang walang hanggan. Parehong nagbibigay ng pinakamataas na current para sa mga figure na iniinput mo. Gumagamit ito ng nominal voltage nang walang IEC 60909 voltage factor. Kailangan ng supply source ng Ze sa origin para sa phase-earth figures.

Ano ang gagawin ko sa resulta?

Ikumpara ito sa breaking capacity ng circuit-breaker sa board. Pagkatapos, dalhin ito sa fault rating tool, na tumitingin kung kayang tiisin ng mga cable ang fault sa clearing time.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 27 Sept 2026.

Nakatulong ba ito?

May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.