फ़ॉल्ट लेवल कैलकुलेटर
स्रोत से किसी बोर्ड पर संभावित फ़ॉल्ट करंट।
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.
कोई प्रोजेक्ट आज़माएँ 8
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Find the fault level at a sub‑boardThe fault current at a board 45 m from a 300 kVA transformer, against 6 kA breakers.
- Check breakers beside a 1000 kVA transformerWhether 25 kA breakers suit a main board 20 m from a 1000 kVA transformer.
- Find the fault level at a house boardThe fault current at the end of 20 m of 16 mm² mains.
- Find the fault level at a shedThe fault current 60 m down a 16 mm² submain.
- Find the fault level at an MCCThe fault current 30 m from a 500 kVA transformer.
- Check 6 kA breakers at a tenancy boardWhether 6 kA devices suit the fault level at the board.
- Find the fault level on parallel feedersThe fault current with two cables per phase.
- Find fault level from a 10 kA serviceThe fault current at a board in Australia.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- स्रोत
- ट्रांसफ़ॉर्मर
- ट्रांसफ़ॉर्मर रेटिंग
- 500 kVA
- ट्रांसफ़ॉर्मर इम्पीडेंस
- 4.5 %
- लाइन वोल्टेज
- 400 V
- मानक
- NZ · AS/NZS 3008.1.2
- सबमेन की लंबाई
- 30 m
- कंडक्टर का आकार
- 35 mm²
- सामग्री
- तांबा
- इंसुलेशन
- PVC 75 °C
- कोर
- मल्टीकोर
- समानांतर केबल
- 1
- सर्किट-ब्रेकर की ब्रेकिंग क्षमता
- 15 kA
बोर्ड पर थ्री-फ़ेज़ फ़ॉल्ट धारा
10.01kA
- फ़ेज़-अर्थ फ़ॉल्ट धारा, अधिकतम
- 3.18kA
- फ़ेज़-अर्थ फ़ॉल्ट धारा, केबल गर्म अवस्था में
- 2.63kA
- प्रति फ़ेज़ स्रोत इम्पीडेंस
- 14.4mΩ
- ब्रेकिंग कैपेसिटी
- 15kA
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- ट्रांसफ़ॉर्मर इम्पीडेंस प्रति फ़ेज़, U² ÷ S × Z%0.01Ω
- स्रोत पर फ़ॉल्ट करंट16.04kA
- परिचालन तापमान पर सबमेन फ़ेज़ प्रतिरोध0.02Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- 20 °C पर सबमेन फ़ेज़ प्रतिरोध0.02Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- सबमेन फ़ेज़ रिएक्टेंस0Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- सुरक्षात्मक कंडक्टर आकार10mm²
AS/NZS 3000:2018 Table 5.1
- 20 °C पर सुरक्षात्मक कंडक्टर प्रतिरोध0.06Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- बोर्ड पर तीन-फ़ेज़ फ़ॉल्ट करंट, U0 ÷ |Z|परिणाम10.01kA
- बोर्ड पर फ़ेज़-अर्थ फ़ॉल्ट करंट, अधिकतम3.18kA
- फ़ेज़-अर्थ फ़ॉल्ट करंट, परिचालन तापमान पर केबल2.63kA
- सर्किट-ब्रेकर की ब्रेकिंग क्षमता15kA
इस कैलकुलेटर के बारे में
How this is calculated
The tool finds the fault current at a board. The source is a transformer or a stated supply fault level. A submain then adds impedance. The tool compares the result with the breaking capacity of your device.
- Source impedance. For a transformer, the tool works Z = U² ÷ S × Z% per phase. It takes the source as all reactance. That gives the highest current for the size.
- Source current. It gives the fault current at the transformer terminals.
- Submain impedance. It reads the resistance and reactance of the submain for your size, length and material. The tables are Table 30 for reactance and Tables 34 and 35 for resistance. It scales the resistance to 20 °C for the maximum figure.
- Protective conductor. It reads the earth conductor size from Table 5.1 of AS/NZS 3000:2018. It adds that resistance to the earth loop.
- Fault currents. It gives the three‑phase current as U0 ÷ |Z|. It also gives the phase-earth current, maximum and with the cable hot.
- Breaking capacity. It compares the three‑phase current with the rating you enter.
| Step | Table or clause | What it decides |
|---|---|---|
| Submain reactance | AS/NZS 3008.1.2 Table 30 | The reactance of the submain |
| Submain resistance | AS/NZS 3008.1.2 Tables 34 and 35 | The resistance of the submain |
| Earth conductor | AS/NZS 3000 Table 5.1 | The size of the protective conductor |
Worked example
- 500 kVA transformer with a 30 m 35 mm² submain. The transformer has 4.5 % impedance. The three‑phase fault current at the board is 10.01 kA. The maximum phase-earth current is 3.18 kA. A 15 kA device passes.
Limits
- The tool works at nominal voltage. It does not apply the IEC 60909 voltage factors.
- It takes the network above the transformer as infinite. A real network lowers the current a little.
- It takes the phase-earth loop at the transformer as its phase impedance, as for a Dyn transformer.
- It does not add motor contribution. It does not grade devices. Use the IDMT tool for grading.
- The result is an estimate for sizing. Ask the network company for the supply fault level at the point of supply.
See also: Prospective fault current at a board, Fault level at a sub‑board on a 300 kVA transformer and Fault rating.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
फ़ॉल्ट लेवल टूल करंट कैसे निकालता है?
यह प्रति फ़ेज़ इम्पीडेंस जोड़ता है। ट्रांसफ़ॉर्मर U² ÷ S × Z% देता है, और सप्लाई फ़ेज़ वोल्टेज को उसके फ़ॉल्ट लेवल से भाग देकर देती है। सबमेन AS/NZS 3008.1 की इम्पीडेंस टेबल से अपना रेज़िस्टेंस और रिएक्टेंस जोड़ता है। कुल पर फ़ेज़ वोल्टेज ही बोर्ड पर थ्री-फ़ेज़ फ़ॉल्ट करंट है।
दो फ़ेज़-अर्थ आंकड़े क्यों हैं?
टेबल कंडक्टर के ऑपरेटिंग तापमान पर रेज़िस्टेंस देती हैं। ठंडी केबल सबसे ज़्यादा करंट देती है, इसलिए अधिकतम करंट के लिए रेज़िस्टेंस को 20 °C पर स्केल किया जाता है। गर्म केबल वाला आँकड़ा कम होता है, और वह लूप इम्पीडेंस टूल में डिस्कनेक्शन टाइम की जाँच के लिए है।
टूल स्रोत के बारे में क्या मानता है?
यह स्रोत को पूरी तरह रिएक्टेंस और ट्रांसफ़ॉर्मर के ऊपर के नेटवर्क को अनंत मानता है। दोनों दर्ज आँकड़ों के लिए सबसे अधिक करंट देते हैं। यह IEC 60909 वोल्टेज फ़ैक्टर के बिना नॉमिनल वोल्टेज इस्तेमाल करता है। सप्लाई स्रोत को फ़ेज़-अर्थ आँकड़ों के लिए ओरिजिन पर Ze चाहिए।
परिणाम का मैं क्या करूँ?
इसकी तुलना बोर्ड पर लगे सर्किट-ब्रेकर की ब्रेकिंग कैपेसिटी से करें। फिर इसे फ़ॉल्ट रेटिंग टूल पर ले जाएँ, जो जाँचता है कि केबल क्लियरिंग टाइम के लिए फ़ॉल्ट को विदस्टैंड कर सकते हैं या नहीं।
हल किए गए उदाहरण
- Starting a loaded conveyorA 22 kW conveyor that needs 120 % torque to break away. Why star-delta and a soft starter will not start it, and what a drive or autotransformer does.
- Fault level at a sub‑board, 300 kVA transformerWork the prospective fault current at a sub‑board 45 m from a 300 kVA transformer, three‑phase and phase-earth, and check 6 kA and 10 kA breakers against it.
बैकग्राउंड
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 3000:2018 Table 5.1Minimum earthing conductor size by active conductor size
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2025 Table 4.1(A), 4.1(B), 4.5(A), 4.5(B)Reactance at 50 Hz and a.c. resistance at 50 Hz
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 27 Sept 2026 को जाँची गईं।
संबंधित टूल
- केबल फ़ॉल्ट रेटिंग कैलकुलेटरCheck that a conductor can withstand the fault current.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- केबल आकार कैलकुलेटरFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- ट्रांसफ़ॉर्मर कैलकुलेटरCalculate transformer full load current and impedance.कोई मानक नहीं
क्या यह उपयोगी था?