Battery location checker
Tingnan kung saan puwedeng ilagay ang home battery ayon sa AS/NZS 5139.
Reads AS/NZS 5139:2019. Tables checked 1 Oct 2026.
Subukan ang isang job 4
Nilalagyan ng halimbawang value ang bawat job. Palitan ang mga ito ng sarili mong value.
- Check a battery beside a hot water unitA garage battery 450 mm from the hot water cylinder.
- Check a battery on a bedroom wallThe barrier an outdoor battery needs on a weatherboard wall to a bedroom.
- Check a battery in a corridorThe egress width left past a battery in an apartment corridor.
- Check the working space at a batteryA 700 mm space against the maker’s 1 m clearance.
Mga input
Worked example gamit ang mga default na input.
- Uri ng baterya
- All-in-one (pre-assembled integrated BESS)
- Location
- Garahe
- IP code ng baterya
- IP55
- Distance to the nearest exit
- 1,500 mm
- Distance to a window or vent
- 0 mm
- Distance to an appliance
- 800 mm
- Exit, bintana, o kagamitan sa itaas nito
- Hindi
- Sa pader papunta sa tirahang kuwarto
- Hindi
- Gap to the ceiling
- 1,100 mm
- May fire indication panel ang gusali
- Hindi
- Working space in front
- 1,000 mm
- Umaabot ang mga panel sa 230 V a.c. na koneksyon
- Oo
- Maker’s clearance
- 0 mm
AS/NZS 5139 Section 4
8 sa 9 na panuntunan ang natugunan
- Natugunan ang mga panuntunan
- 8
- Hindi natugunan ang mga panuntunan
- 0
- Hindi pa nasusuri
- 1
Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.
Mga hakbang ng kalkulasyon
- Clearance sa exit, bintana o vent, o appliance, hindi bababa sa600mm
AS/NZS 5139:2019 Cl 4.2.2.2
- Malinaw sa ibaba ng mga item na iyon, hindi bababa sa900mm
AS/NZS 5139:2019 Cl 4.2.2.2(e)
- IP code sa loob, hindi bababa saIP2X
AS/NZS 5139:2019 Cl 4.2.3.2
- Working space, hindi bababa sa900mm
AS/NZS 5139:2019 Cl 4.2.5
Tungkol sa calculator na ito
How this is calculated
The tool checks a site for an all-in-one home battery. It reads AS/NZS 5139:2019 Section 4. It shows each rule as met, not met or not assessed. A distance you leave blank stays not assessed.
- Place. It tests the location against the restricted places (Cl 4.2.2.2(a) to (k)). These are switchboard-restricted places, ceiling spaces, wall cavities, roofs unless deemed suitable, under stairways or access walkways, and escape routes. They also include habitable rooms of homes and hazardous areas.
- Clearances. It compares your distances to an exit, a window or vent of a habitable room, and another appliance with the 600 mm rule. An item above the battery needs the 900 mm rule. In a corridor it checks the 1 m left for egress (Cl 4.2.2.1).
- IP code. It wants IP2X indoors and IP23 outdoors (Cl 4.2.3.2). It compares each digit of your code.
- Barrier. If the battery is on a wall to a habitable room, the wall must be non‑combustible (Cl 4.2.4.2). On a combustible wall, a non‑combustible barrier must reach 600 mm past each side, 900 mm above and down to the bottom.
- Ceiling. If the ceiling is within 900 mm of the top, it must be non‑combustible for 600 mm past the battery (Cl 4.2.4.2).
- Working space. It wants 600 mm on the working side, or 900 mm where panels reach the 230 V a.c. connections. It takes the maker's figure if that is larger (Cl 4.2.5).
- Notes. It adds notes for a smoke alarm or fire panel detector (Cl 4.3.4, a "should") and for the maker's ventilation instructions (Cl 4.3.5).
| Check | Clause | What it decides |
|---|---|---|
| Location | Cl 4.2.2.2 | Whether the place is restricted |
| Exit, window, appliance | Cl 4.2.2.2 | The side and below clearances |
| Corridor | Cl 4.2.2.1 | The width left for egress |
| IP rating | Cl 4.2.3.2 | The least enclosure rating |
| Barrier | Cl 4.2.4.2 | The non‑combustible wall behind the battery |
| Ceiling | Cl 4.2.4.2 | The non‑combustible ceiling above it |
| Working space | Cl 4.2.5 | The clear space to work in |
Worked example
- A garage wall that backs onto a bedroom. The tool gives 4 of 9 rules not met: the appliance clearance, the barrier, the ceiling and the working space. The hot water unit is 400 mm away. The barrier reaches 300 mm each side and 500 mm above. The ceiling is 700 mm over the battery. The working space is 700 mm.
- The same wall, fixed. The tool gives 9 of 9 rules met.
Limits
- The tool covers a pre-assembled integrated BESS, Section 4. It does not assess other battery types. AmpSize does not hold Sections 5 and 6.
- AmpSize does not hold Amendment 1 (2025). Check it for changes.
- The tool tests the numbers you enter. It does not know your site. A roof needs a check that it is deemed suitable.
- It does not size the battery, the cable or the protection.
See also: Home battery location and clearances, Where can a home battery go, Solar battery size for a family home and the home battery tool.
Mga tanong
Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.
Saan hindi puwedeng ilagay ang home battery?
Inilalayo ng AS/NZS 5139:2019 Cl 4.2.2.2 ang all-in-one battery sa habitable rooms, ceiling spaces, wall cavities, espasyo sa ilalim ng hagdan o walkway, escape routes at hazardous areas. Pinapayagan lang ang bubong kapag itinuring na angkop.
Gaano kalayo dapat ang battery mula sa pinto, bintana o hot water unit?
Hindi bababa sa 600 mm sa gilid ng exit, bintana o vent ng habitable room, o ng ibang appliance gaya ng hot water unit o air conditioner. Dapat din itong nasa hindi bababa sa 900 mm sa ibaba ng alinman sa mga iyon.
Puwede bang ilagay ang battery sa pader na katabi ng bedroom?
Oo, kung hindi nasusunog ang pader, gaya ng brick, concrete, cement sheet o tiles. Sa nasusunog na pader, maglagay ng non‑combustible barrier na 600 mm ang lampas sa bawat gilid at 900 mm sa itaas. Ang kisameng nasa loob ng 900 mm ay nangangailangan din nito.
Gaano karaming espasyo ang kailangan ng battery sa harap nito?
Hindi bababa sa 600 mm sa working side, o 900 mm kapag umaabot ang panels sa 230 V a.c. connections. Kapag humingi ng higit ang maker, kukunin ng tool ang mas malaking figure.
Sakop ba ng tool ang bawat battery?
Sakop nito ang all-in-one home battery, Section 4 ng AS/NZS 5139. Walang hawak na Section 5 at 6 rules ang AmpSize para sa ibang system, o Amendment 1 (2025). Sinasabi ito ng tool sa halip na manghula.
Mga worked example
Background
Mga clause at table na binabasa ng tool na ito
- AS/NZS 5139:2019 Cl 4.2.2.2Restricted locations for a home battery
- AS/NZS 5139:2019 Cl 4.2.3.1Battery location by risk assessment
- AS/NZS 5139:2019 Cl 4.2.3.2IP rating of a home battery
- AS/NZS 5139:2019 Cl 4.2.4.2Barrier to a habitable room
- AS/NZS 5139:2019 Cl 4.2.5Working space at a home battery
- AS/NZS 5139:2019 Cl 4.3.4Smoke alarm or detector at a home battery
- AS/NZS 5139:2019 Cl 4.3.5Ventilation of a home battery
- AS/NZS 5139:2019 Cl 4.2.2 to 4.2.5Location, clearance and barrier rules for a pre-assembled integrated BESS
Bawat clause at table, kasama kung paano ito na-verify
Huling na-check ang mga table noong 1 Oct 2026.