Transformer current and secondary fault level

Working level

A drawn boards and supply schematic for Transformer current and secondary fault level: supply, meter and main switchboard.

A transformer nameplate gives a rating in kVA. A designer needs amps. The amps set the cable, the main switch and the fault rating of the board. This page shows how to get from the nameplate to those numbers.

Three numbers from four inputs

The tool needs four inputs.

  • The rating in kVA
  • The number of phases
  • The primary and secondary voltages
  • The impedance, as a percentage

It gives three results. They are the primary full load current, the secondary full load current and the secondary fault current.

Full load current

Power is the same on both sides. The side with the lower voltage carries the higher current.

For a three‑phase transformer the current is I = S / (√3 × V). S is the rating in volt-amperes. V is the line voltage. For a single‑phase unit the √3 drops out.

The secondary current sizes the main cable and the main switch. The primary current sizes the fuse or the protection on the high-voltage side.

Fault current at the secondary

The impedance is the key to the fault. It is a percentage of the rated voltage. It limits how much current flows when the secondary is shorted.

The tool divides the secondary full load current by the impedance as a fraction. A 6 % unit gives a fault 100 / 6 times its full load current. A lower impedance gives a higher fault.

The tool assumes an infinite upstream source. That is a worst case. A real network has some impedance, so the real fault is a little lower. A network figure from the utility gives a better result.

A worked unit

Take a 500 kVA three‑phase transformer. The primary is 11 kV. The secondary is 400 V. The impedance is 6 %.

  • Primary full load current: 500 000 / (√3 × 11 000) = 26.24 A
  • Secondary full load current: 500 000 / (√3 × 400) = 721.69 A
  • Secondary fault current: 721.69 / 0.06 = 12 028.13 A

The secondary fault is about 12 kA. A board on this transformer needs a fault rating above that figure.

Open the transformer tool with these inputs.

What changes with the impedance

Keep the unit at 500 kVA. Change the impedance to 4 %. The full load currents stay the same. The secondary fault current rises to 18 042.2 A.

A larger unit also raises the fault. A 1000 kVA unit at 5 % gives a secondary full load current of 1443.38 A. The secondary fault current is 28 867.51 A.

Open the transformer tool with the 1000 kVA unit.

Using the results

Use the secondary full load current as the starting point for the main cable. The cable size tool takes it as a design current. Add the load growth you expect.

Use the fault current to check two things. The first is the fault rating of the main switchboard. The second is the fault withstand of the main cable. Read Cl 2.5.4.1 of AS/NZS 3000:2018 for the fault current rules.

The fault level tool adds the cable impedance between the transformer and a downstream board. That figure is lower than the secondary value. Use it at each board.

Where it goes wrong

The line voltage is mixed with the phase voltage. The three‑phase formula takes the line voltage. Enter 400 V, not 230 V.

The impedance is left at a default. The impedance comes from the nameplate or the maker data sheet. A default can be wrong by a wide margin.

The infinite source is forgotten. The fault figure is a ceiling at the terminals. It is not the figure at a downstream board.

The tap and the vector group are ignored. The tool does not model them. Check the nameplate for any change from the nominal ratio.

Full load current is used as the design current. A transformer is rarely loaded to its rating. Use the real load for the cable, and the rating for the protection.

This page is a design aid. Verify every value against the current edition of the standard.

See also: Prospective fault current at a board, Transformer secondary fault current for 500 kVA and Transformer full load current for 1000 kVA at 11 kV.