Lumaktaw sa nilalaman
AmpSize

This page is not in Filipino yet, so you are reading the English.

· 5 min basahin

Battery classes and arc flash in AS/NZS 5139

Working level

A drawn solar and storage schematic for Battery classes and arc flash: PV array, d.c. isolator and inverter.

Before a battery system goes in, AS/NZS 5139 asks what it is. Section 3 classes it by its hazards, its voltage and the energy an arc at its terminals would release. Section 6 then uses that energy for the risk assessment and for where the system may go. This page walks through each step.

The hazards and the fire hazard level

Table 3.1 lists, for each chemistry, which hazards it carries: electrical, energy, mechanical, fire, explosive gas, chemical and toxic fume. The fire column is given as a level.

ChemistryFire hazard level
Lead acid2
Nickel alkaline2
Lithium ion1
FlowNot applicable
Hybrid ionNot applicable

Two notes to the table lift the level. Note 1 covers pre-assembled lithium ion equipment that meets the industry Best Practice Guide. Note 2 covers lead acid and nickel alkaline batteries in cases rated V0. Either then takes no fire hazard level. A note also says that not applicable is a classification only. It does not mean the hazard is absent.

The decisive voltage class

Table 3.2 sorts the system by its highest voltage into a decisive voltage class (DVC). For a battery, the d.c. limit is the one that counts.

ClassD.c. voltage
DVC-A60 V or less
DVC-BAbove 60 V, up to 120 V
DVC-CAbove 120 V

A 48 V battery is DVC-A. A stacked home battery at a few hundred volts is DVC-C. Note 2 to the table makes a DVC-B or DVC-C battery system a low voltage installation under AS/NZS 3000.

The arc flash energy

Cl 3.2.4 gives one equation for the incident energy, Equation 3.2.4(1). It multiplies:

  • 0.01, the coefficient;
  • the battery voltage, V;
  • the arcing current, which Equation 3.2.4(2) takes as half the bolted fault current;
  • the arcing time divided by the square of the working distance;
  • a multiplying factor for where the arc is.

The result is in cal/cm². The inputs have rules of their own:

InputRuleClause
Working distance45 cm at mostCl 3.2.4.2.2
Arcing time2 s where the device time is not known, or the work is on its battery sideCl 3.2.4.2.3
Multiplying factor, enclosure or cabinet3 at leastCl 3.2.4.3
Multiplying factor, battery room1.5 at leastCl 3.2.4.3

A 48 V lithium battery with 6 kA at its terminals, at 2 s, gives 4.27 cal/cm². Open the 48 V battery.

The energy is in proportion to the time. Inter-string fuses that clear the arc in 0.1 s bring the same battery to 0.21 cal/cm². Open the 48 V battery at 0.1 s.

Appendix F prints tables of this equation at 45 cm and a factor of 3, at 2 s without inter-string protection and 0.1 s with it. The tool reproduces every printed row.

The arc flash boundary

The boundary is the distance at which the energy falls to 1.2 cal/cm² (Equation F.4). It does not depend on the working distance. For the 48 V battery at 2 s it is 849 mm.

The PPE level

Table 3.3 turns the energy into a PPE level, from 0 to 4. Each level names a set of arc-rated clothing and protection; read the table for what each one includes.

Energy, cal/cm²PPE level
00
Above 0, up to 41
Above 4, up to 82
Above 8, up to 253
Above 25, up to 404
Above 40None

Above 40 cal/cm² no level applies. The system has to be arranged, with inter-string protection or smaller blocks, so that no one works at that energy. A 350 V system with 15 kA gives 77.78 cal/cm², and the tool fails it. Open the 350 V system.

The consequence level

The risk assessment of Section 6 grades the consequence of an arc by its energy, in Table 6.1. The likelihood comes from your own assessment of the work.

Energy, cal/cm²Consequence
Below 1.2Insignificant
1.2 to below 4Minor
4 to below 8Moderate
8 to below 40Major
40 or moreCatastrophic

The limits in and outside a home

Cl 6.3.2.3 limits the energy by where the system goes.

WhereEnergyWhat the tool flags
In or at a homeAbove 4 cal/cm²A dedicated room or enclosure, or fire hazard level 1; not inside or against a building with habitable rooms
In or at a home40 cal/cm² or moreA fail: it must be below 40 cal/cm²
Outside, not connected to a building with habitable rooms8 cal/cm² or moreIt should be below; otherwise isolate into blocks of 4 cal/cm² at most

A 24 V lead acid bank in a battery room away from the house takes the room factor of 1.5. With 12 kA at 2 s it gives 2.13 cal/cm², PPE Level 1, inside every limit. Open the lead acid bank.

A 48 V lithium cabinet with 12 kA outside the house gives 8.53 cal/cm², and the tool warns. Open the outdoor cabinet.

The edition

This page and the tool read AS/NZS 5139:2019 as published. Amendment 1 (2025) is not checked here, so confirm any change it makes before you rely on a figure.

Class a battery with the battery arc flash and class tool. A worked job is in Arc flash at a 48 V home battery. To size the battery, use the home battery tool. Arc flash on an a.c. switchboard uses the IEEE 1584 model instead: see Arc flash basics.

Saan ito ginagamit

Mga worked example

Design aid ang AmpSize. I-verify ang mga resulta laban sa kasalukuyang standard.

Nakatulong ba ito?

May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.