How many amps can 2.5 mm² cable carry?

فحص الدائرة القائمة

+2 references

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

التصنيف المصحح Iz

23A

أكبر جهاز بمنحنى C يسمح به الكابل
20A
هبوط الجهد
3.13%
أقصى Zs للجهاز
1.53Ω
فتح الحاسبة بهذه المدخلات

هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.

A drawn result card from the Circuit Check tool: circuit on 2.5 mm² passes.

2.5 mm² copper multicore PVC cable carries 23 A enclosed in air at 30 °C in New Zealand. That is its corrected rating Iz from AS/NZS 3008.1.2:2017 Table 13. The largest curve C breaker it allows is 20 A, the usual power point circuit.

The case

The circuit is single‑phase at 230 V and runs 20 m at the full 20 A of the breaker. The voltage drop is 3.13 % and the earth fault loop impedance is 0.71 Ω, inside the 1.53 Ω that Table 8.1 allows.

The circuit check reads Passes.

What changes the rating

Clipped direct to a surface, the cable carries 25 A.

Grouping is the common trap. Bunched with two other circuits, the factor is 0.7 and the cable carries 16.1 A. That is below a 20 A breaker, so the circuit fails.

See also: What size cable for power points in NZ? and Ib, In and Iz.

جرّبه بهذه المدخلات

درجة الحرارة المحيطة
30 °C
الأسلاك الداخلية
متعدد القلوب
منحنى الجهاز
المنحنى C
الدوائر المجمّعة
1
العزل
PVC 75 °C
طول المسار
20 m
تيار التصميم
20 A
المادة
النحاس
طريقة التركيب
Enclosed in air
معامل القدرة
1
الأطوار
طور واحد
القيمة الاسمية للجهاز
20 A
حجم الكابل المركب
2.5 mm²
الجهد
230 V
المعاوقة الخارجية Ze
0.35 Ω