تخطَّ إلى المحتوى
AmpSize

This page is not in العربية yet, so you are reading the English.

· قراءة 4 دقيقة

What size cable for an oven in Australia

حاسبة مقاس الكابل

+5 references

Worked to AS/NZS 3000:2018 and AS/NZS 3008.1.1:2025 (AU). Tables checked 27 Sept 2026.

A drawn result card from the Cable Size tool: conductor size 2.5 mm².

A 3.6 kW wall oven on 230 V takes 2.5 mm² cable on a 20 A breaker, over a 12 m run in Australia. The size comes from the 2025 edition of AS/NZS 3008.1.1, which the cable size tool reads when you set the Standard to Australia. This guide runs the case, then changes the route.

How many amps does a 3.6 kW oven draw?

3.6 kW divided by 230 V is 15.7 A. That is the design current, Ib. A double oven or an oven with a hob on the same circuit is a bigger load, and the last case below covers it.

What size cable for a 15.7 A oven on a 20 A breaker?

Run the oven. The cable is multicore copper in an enclosed route at 30 °C, one circuit. The tool reads Table 3.18 of the 2025 edition and applies an ambient factor of 1.13 at 30 °C (Tables 3.44 and 3.45).

Check the current first. Without the breaker, 1.5 mm² passes with 15.82 A of derated capacity. It clears 15.7 A by 0.12 A. Add the 20 A breaker and 1.5 mm² fails, because the breaker rating may not exceed the cable's capacity (Cl 2.5.3.1). The next size, 2.5 mm², gives 22.6 A and passes.

Check2.5 mm² resultLimit
Derated capacity22.6 A15.7 A load, 20 A breaker
Voltage drop1.34 %5 %
Loop impedance0.57 Ω1.53 Ω

The 1.53 Ω limit is the Table 8.1 figure for a 20 A C curve breaker. The tool sizes the earth conductor at 2.5 mm².

What if the oven is in a hot roof space?

Set a 45 °C ambient and group one other circuit with it. Run that route. The total derating factor is 0.74. The cable must now carry 21.1 A of tabulated current, and 4 mm² is the smallest size that does it, with 18.6 A derated. 2.5 mm² gives 14.88 A and fails. Most oven circuits run in a wall. If yours crosses a roof space, run the real route.

What if the oven is 40 m from the board?

Run 40 m on a 20 A breaker. 2.5 mm² still passes. The drop is 4.45 %, close to the 5 % limit, and the loop impedance is 1.07 Ω against 1.53 Ω. 1.5 mm² fails the breaker check, the drop at 8.14 % and the loop impedance at 1.67 Ω. The tool assumes an Ze of 0.35 Ω, so measure the real one before you rely on the margin.

What if the oven shares a circuit with a hob?

A 7.2 kW hob and the oven on one 32 A circuit is a bigger load. Take 31.3 A. Run it at 12 m. The tool returns 6 mm², with 37.29 A and a 1.12 % drop. 4 mm² gives 28.25 A and fails. The Table 8.1 loop impedance limit for a 32 A C curve breaker is 0.96 Ω, and 6 mm² reads 0.5 Ω.

The result

RouteSize that passes
3.6 kW, 12 m, 20 A breaker, 30 °C2.5 mm²
Same, current check only1.5 mm²
Hot roof space at 45 °C, one other circuit4 mm²
40 m run2.5 mm²
Oven and hob, 31.3 A, 32 A breaker6 mm²

What this guide does not cover

The tool checks the breaker you enter. It does not choose the breaker, and it does not read the oven maker's instructions. Check the nameplate for the supply the oven needs. It does not test the finished circuit, and Cl 3.6.2 voltage drop is a design check, not a measurement.

New Zealand readers use the 2017 tables. The induction hob guide runs a 7.2 kW case on them.

See also: AS/NZS 3008.1.1:2025 tables against 2017, What size breaker for 4 mm² cable and Correction factors in 2017 and 2025.

جرّبه بهذه المدخلات

درجة الحرارة المحيطة
30 °C
منحنى الجهاز
المنحنى C
تحقق من جهاز الحماية
نعم
الإصدار
AS/NZS 3008.1.1:2025
المعيار
AU · AS/NZS 3008.1.1
طول المسار
12 m
تيار التصميم
15.7 A
طريقة التركيب
Enclosed in air
الأطوار
طور واحد
القيمة الاسمية للجهاز
20 A
الجهد
230 V
فتح الحاسبة بهذه المدخلات

الخطوة التالية

المفاهيم التي تقوم عليه

أمثلة محلولة إضافية

AmpSize أداة مساعدة للتصميم. تحقق من النتائج مقابل المعيار الحالي.

هل كان هذا مفيداً؟

سؤال، أو قيمة تبدو خاطئة؟ اتصل بنا.