变频器电动机电缆检查
检查变频器的电动机电缆:峰值电压、长度及电缆规格。
Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.
尝试一个工程 4
每项工作都会预填示例数值。请替换为您自己的数值。
- Check a drive motor leadWhether a pump on a drive needs an output filter for its motor lead.
- Check a long fan lead on a VSDA fan motor far from its drive, against the drive maker limit.
- Size a conveyor drive lead with a filterA long conveyor lead on a sine filter and the current for its cable.
- Check an inverter-rated motor on a driveWhether an inverter-rated motor takes the reflected peak without a filter.
输入
使用默认输入值的示例计算。
- 电动机功率
- 22 kW
- 供电电压
- 400 V
- 电动机功率因数
- 0.85
- 电动机额定峰值电压
- 1,000 V
- 电动机引线长度
- 60 m
- 电缆
- 屏蔽,对称
- 输出滤波器
- 无
- 厂商引线长度限值,无滤波器
- 100 m
- 脉冲上升时间
- 0.1 µs
- 电缆中的脉冲速度
- 150 m/µs
电动机导线
未通过
- 电动机处峰值,最高可达
- 1,131V
- 制造商导线长度限值
- 100m
- 临界导线长度
- 7.5m
- 电缆规格对应的电流
- 41.51A
- 驱动直流母线
- 565.7V
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 电缆规格对应的电流41.51A
- 驱动直流母线565.7V
- 上升时间为 0.1 µs 时的临界引线长度7.5m
- 电动机处峰值,最高可达1,131V
- 电机绝缘,额定峰值1,000V
- 制造商引线限值,无滤波器100m
- 电动机导线结果不合格
关于此计算器
How this is calculated
A variable speed drive does not send a smooth sine wave down the motor lead. It sends fast pulses at the voltage of its d.c. bus, and each pulse can reflect at the motor. On a long enough lead the reflection nearly doubles the voltage at the motor terminals, which can break down the insulation of a motor not rated for it. This tool works that peak, checks the lead against the drive maker's limit, and gives the current to size the cable for.
The bus voltage is the supply voltage times √2. The critical length is how far a pulse travels in half its rise time; on a lead longer than that the reflection is full and the peak at the motor reaches about twice the bus. On a shorter lead the tool scales it down. A dv/dt filter or an output reactor slows the edge but does not end the reflection, so the tool makes no estimate of its own: you enter the peak at the motor from the filter maker's data for your lead, and the result says it is the maker's figure. Only a sine filter brings the peak down to the bus voltage. The peak is compared with the motor maker's rating. The lead is compared with the drive maker's limit, with or without the filter.
The current is the motor tool's full load current. The rise time, the pulse speed, the limits and the motor's rating are makers' data, entered by you, so the result calls them assumptions. AS/NZS 3000 warns of high frequency current on the protective earth, and notes the cable tables are for 50 Hz.
| Step | Table or clause | What it decides |
|---|---|---|
| Cable current | The motor tool | The current for the cable size |
| Bus voltage | Supply voltage times √2 | The height of each pulse |
| Critical length | Pulse speed times half the rise time | Where the reflection becomes full |
| Peak at the motor | Up to twice the bus; the filter maker's figure with a dv/dt filter or reactor; the bus with a sine filter | The voltage the motor sees |
| Lead length | The drive maker's limit | Whether the lead needs a filter |
| Earthing and ratings | AS/NZS 3000 Cl 5.4.8 and Cl 4.12.8 Note 1 | The earth current and the 50 Hz basis |
Worked examples
- A 22 kW pump on a 60 m lead, standard motor fails: the peak can reach 1,131 V against the motor's 1000 V rating. The cable carries 41.51 A.
- The same pump with a dv/dt filter passes if the filter maker gives a peak of 900 V at the motor for 60 m. The tool prints that 900 V as the maker's figure; it is an example, not an estimate.
- The same pump with an inverter-rated motor passes with a peak of up to 1,131 V on a 1600 V rating.
- A 7.5 kW fan on a 150 m lead fails on length: the drive maker allows 100 m with no filter, though the peak of up to 1,131 V is within the motor's rating.
- A 55 kW conveyor on a 250 m lead with a sine filter passes with a peak near 566 V, inside the 300 m limit with the filter.
Limits
The peak is a first estimate from the lead length alone. The real peak depends on the cable's and motor's surge impedance, the switching pattern and the drive's own output stage, which the makers test. The tool does not size the cable for harmonics on the drive's supply side, the cable's capacitive charging current, or bearing currents.
See also: Motor, Motor starting and Cable size.
问题
结果仅供设计参考。请依据现行标准核对。
为何变频器的长电动机电缆很重要?
变频器发出快速电压脉冲。在长引线上,每个脉冲会在电动机端反射,该处电压可能接近翻倍。这可能击穿未按此额定的电动机绝缘。
临界电缆长度是多少?
脉冲在其上升时间的一半内所行进的长度。超过该长度后,反射为全反射。当上升时间为 0.1 µs、脉冲速度为 150 m/µs 时,该长度为 7.5 m,因此大多数电动机电缆都超过此长度。
我需要 dv/dt 滤波器或正弦波滤波器吗?
当电缆长度超过变频器制造商的限值,或峰值超过电动机额定值时。dv/dt 滤波器或电抗器可减缓上升沿,但仍有一定过冲,因此工具从滤波器制造商的数据中取该峰值。正弦滤波器可将输出平滑至接近正弦波。
变频器应采用什么电缆?
屏蔽对称电缆,按变频器制造商的要求在两端全周向连接屏蔽层。按电动机电流选型,并注意 AS/NZS 3008.1 的额定值基于 50 Hz。
为何变频器可能通过接地金属造成电击?
AS/NZS 3000 Cl 5.4.8 警告,变频器可能在保护接地上产生高频电流,接触电压可达 100 V。50 Hz 测试仪可能无法显示该情况。请按制造商要求对变频器接地。
本工具读取的条款和表格
- AS/NZS 3000:2018 Cl 4.12.8Equipment on a converter output
- AS/NZS 3000:2018 Cl 5.4.8Variable frequency devices
- AS/NZS 3000:2018 Cl 5.4.8 and Cl 4.12.8Variable frequency drives
表格最后核对于 2 Oct 2026。