RCD 配置检查
检查每个 RCD 的回路数及照明分配。
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
尝试一个工程 4
每项工作都会预填示例数值。请替换为您自己的数值。
- Find an RCD with too many circuitsA house board with four circuits on one RCD.
- Split a large board onto three RCDsNine circuits and three lighting circuits spread over three RCDs.
- Check an Australian board of RCBOsEvery final subcircuit on its own RCBO in an AU home.
- Check the lighting split in an officeOffice lighting circuits spread over two RCDs.
输入
使用默认输入值的示例计算。
- 国家
- 新西兰
- 安装
- 住宅
- 配电板上的末端分路
- 8 行
RCD 配置
通过
- 配电板上的 RCD
- 2
- 需要 RCD 的回路
- 6
- 单个 RCD 所带最多回路数
- 3
- 照明回路
- 2
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 回路 1照明
- 回路 1 额定值10A
- 回路 1 RCDRCD 1
- 回路 1 所需 RCD 不超过30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- 回路 2插座
- 回路 2 额定值20A
- 回路 2 RCDRCD 1
- 回路 2 所需 RCD 不超过30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- 回路 3插座
- 回路 3 额定值20A
- 回路 3 RCDRCD 1
- 回路 3 所需 RCD 不超过30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- 回路 4照明
- 回路 4 额定值10A
- 回路 4 RCDRCD 2
- 回路 4 所需 RCD 不超过30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- 回路 5插座
- 回路 5 额定值20A
- 回路 5 RCDRCD 2
- 回路 5 所需 RCD 不超过30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- 回路 6插座
- 回路 6 额定值20A
- 回路 6 RCDRCD 2
- 回路 6 所需 RCD 不超过30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- 回路 7固定或静止设备
- 回路 7 额定值32A
- 回路 7 RCD无
- 回路 7 需要安装 RCD不属于本工具所校核的条款
AS/NZS 3000:2018 Cl 2.6.3.3.1
- 回路 8固定或静止设备
- 回路 8 额定值20A
- 回路 8 RCD无
- 回路 8 需要安装 RCD不属于本工具所校核的条款
AS/NZS 3000:2018 Cl 2.6.3.3.1
- RCD 13 个回路,1 照明
- RCD 23 个回路,1 照明
- 配电板上的 RCD2
- 需要 RCD 的回路6
- 单个 RCD 所带最多回路数3
AS/NZS 3000:2018 Cl 2.6.2.4(b)(i)
关于此计算器
How this is calculated
You list the final subcircuits on one switchboard. For each circuit you give what it supplies, its rating and the RCD it sits on. An RCBO is an RCD with one circuit, so give each RCBO its own number. A circuit on no RCD has the number 0.
First the tool asks, circuit by circuit, whether the clauses call for additional protection by an RCD, and at what rated residual current. It reads the same rows as the RCD selection tool. In New Zealand homes that is every circuit that supplies socket‑outlets, lighting points or hand-held equipment. In Australian homes it is every final subcircuit. Schools, childcare, outdoor and public places and other buildings follow their own items. A circuit that needs an RCD and sits on none fails.
Then it groups the circuits by RCD and checks the arrangement clause. In every installation with more than one RCD and more than one lighting circuit, the lighting circuits must be on more than one RCD, so one trip does not put out every light. In a residential installation, one RCD may protect three final subcircuits at most. Every circuit on that RCD counts, even one that would not need it. A residential board with more than one circuit that needs an RCD must have at least two RCDs.
The result lists each circuit, each RCD with its count, and the four checks with their clause.
| Step | Table or clause | What it decides |
|---|---|---|
| Which circuits need an RCD, New Zealand | Cl 2.6.3.3.1 and Cl 2.6.3.3.2 | The circuits that must be on an RCD, and its rated residual current |
| Which circuits need an RCD, Australia | Cl 2.6.3.2.2 and Cl 2.6.3.2.3.3 | The same for an Australian installation |
| Lighting spread | Cl 2.6.2.4(a) | Lighting circuits on more than one RCD |
| Circuits on one RCD | Cl 2.6.2.4(b)(i) | The most final subcircuits one residential RCD may protect |
| Number of RCDs | Cl 2.6.2.4(b)(ii) | The fewest RCDs on a residential board |
Worked examples
- A house board with four circuits on RCD 1. The arrangement fails: 4 on the fullest RCD, one more than a residential RCD may protect. Move one circuit to RCD 2.
- A larger house on three RCDs. The arrangement passes every check, with 3 on the fullest RCD and a lighting circuit on each RCD. The car charger counts as one of the three on RCD 3.
- An Australian home of RCBOs. The arrangement passes every check, with 1 on the fullest RCD. Every final subcircuit needs an RCD in an Australian home, the oven and water heater too, and each has its own.
- An office with both lighting circuits on RCD 1. The arrangement fails the lighting spread, with 3 on the fullest RCD. The count limit does not apply outside a residential installation, but the lighting spread does.
Limits
The tool checks one board. It takes each socket‑outlet as 10 A; use the RCD selection tool for a larger socket‑outlet, a trip time or a device type. It does not check the exceptions in Cl 2.6.3, such as a dedicated cooking socket‑outlet or equipment where a trip is more dangerous. It does not check discrimination between RCDs, or standing leakage on one RCD.
See also: How many circuits can go on one RCD, RCD arrangement for a house board and RCD selection.
问题
结果仅供设计参考。请依据现行标准核对。
一个 RCD 可接多少个回路?
在住宅装置中,依据 AS/NZS 3000 Cl 2.6.2.4,每个 RCD 最多三条终端分支回路。接于该 RCD 的每条回路均计入在内,包括本不需要 RCD 的回路。其他装置在该条款中没有数量限制。
住宅是否需要两个 RCD?
是的,当不止一条终端分支回路需要 RCD 保护时。Cl 2.6.2.4 要求住宅装置至少设两个 RCD,使一次跳闸不会断开整幢房屋的供电。
为何将照明分布到各个 RCD 上?
这样一个 RCD 跳闸就不会使整栋建筑断电。若配电箱设有多个 RCD 和多条照明回路,则照明回路应分别接于不同的 RCD。此规定适用于所有装置。
RCBO 如何计数?
RCBO 即为仅带一个回路的 RCD。请在清单中为每个 RCBO 指定其独立的 RCD 编号。由 RCBO 组成的配电箱本身即满足每个 RCD 三个回路的规定以及照明分配要求。
哪些回路需要 RCD?
工具的结果与 RCD 选型工具相同,依据 Cl 2.6.3。在新西兰住宅中,适用于插座、照明及手持设备回路。在澳大利亚住宅中,适用于每条终端分支回路。其他装置按其各自条目执行。
计算示例
背景
本工具读取的条款和表格
- AS/NZS 3000:2018 Cl 2.6.2.4Arrangement of circuits on RCDs
- AS/NZS 3000:2018 Cl 2.6.3.2.2Additional protection in Australia, domestic and residential
- AS/NZS 3000:2018 Cl 2.6.3.2.3.3Additional protection in Australia, non‑domestic
- AS/NZS 3000:2018 Cl 2.6.3.3.1Additional protection in New Zealand, residential
- AS/NZS 3000:2018 Cl 2.6.3.3.2Additional protection in New Zealand, non‑residential
- AS/NZS 3000:2018 Cl 2.6.2.4Arrangement of final subcircuits on RCDs
- AS/NZS 3000:2018 Cl 2.6.3, Cl 7.9.3 and Cl 7.9.4Additional protection by RCD, required residual current and circuit limits
表格最后核对于 1 Oct 2026。
相关工具
这是否有用?
有问题,或数值看起来有误?联系我们。