跳至内容
AmpSize

按相最大需量计算器

将负荷分配至三相,并查看不平衡情况。

Reads AS/NZS 3000:2018. Tables checked 19 Sept 2026.

输入

使用默认输入值的示例计算。

负荷表
Table C1 · 住宅
相电压
230 V
按相划分的负荷
4 行

负荷最重相,L1

18.04A

L1
18.04A
L2
15A
L3
17.39A
三相需量之和
50.43A
不平衡
16.85%

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. L1 相负荷18.04A

    AS/NZS 3000:2018 Table C1

  2. L2 相负荷15A

    AS/NZS 3000:2018 Table C1

  3. L3 相负荷17.39A

    AS/NZS 3000:2018 Table C1

  4. 负载最重的相L1
  5. 负载最重相的负荷结果18.04A

    AS/NZS 3000:2018 Table C1

  6. 三相需量之和50.43A
  7. 不平衡16.85%

关于此计算器

How this is calculated

The tool assigns each AS/NZS 3000 Appendix C load group to a phase. It then reads the demand on L1, L2 and L3, the heaviest phase and the imbalance. The max demand calculator assumes an even spread. This tool does not.

  1. Phase for each load. You tag every load group with L1, L2 or L3.
  2. Table. You pick Table C1 for a house or Table C2 for another occupancy. Each phase runs as a single installation.
  3. Demand on each phase. The tool applies the group rule to the loads on that phase alone. It gives the demand in amperes.
  4. Heaviest phase. It names the phase with the greatest demand. That figure is the primary result.
  5. Sum and imbalance. It adds the three phase demands. It then gives the imbalance between the heaviest and the lightest phase.
StepTable or clauseWhat it decides
Demand on each phaseAS/NZS 3000 Table C1 or C2The group rules applied per phase
Heaviest phaseParagraphs C2.3.2.2 and C2.4.2The phase that sets the supply

Worked example

A house with 30 lighting points on L1, 25 socket‑outlets on L2, 8 kW of cooking on L3 and a 3 kW water heater on L1. The phase voltage is 230 V. L1 carries 18.04 A, L2 carries 15 A and L3 carries 17.39 A. L1 is the heaviest. The three demands sum to 50.43 A. The imbalance is 16.85 %.

Limits

  • The tool applies the demand rule to each phase on its own. The sum of the phases can differ from the single‑phase total.
  • Enter the phase voltage, line to neutral. The tool refuses a line voltage on three phases.
  • It does not move loads for you. Change the phase tags and run it again.
  • It does not size the cable or the main switch.

See also: Maximum demand and diversity, Domestic maximum demand with Table C1 and Commercial maximum demand with Table C2.

问题

结果仅供设计参考。请依据现行标准核对。

按相最大需量工具有什么作用?

将每个负荷组分配至 L1、L2 或 L3。AmpSize 对各相上的负荷单独应用 AS/NZS 3000:2018 Appendix C 的需量规则。随后报告每相的需量及各相之间的不平衡情况,并指出负荷最重的一相。

为何该规则按相应用,而非整个装置?

AmpSize 先将负荷分配到各相,然后再应用需量规则。因此结果为负荷最重一相的需量,而非总量的平均分摊。AS/NZS 3000:2018 的 Paragraphs C2.3.2.2 和 C2.4.2,以及 Table C1 的 Note 2 涵盖了分相处理方式。

不平衡度如何求出?

不平衡度为最重相与最轻相之差,以最重相的百分比表示。这是 AmpSize 自行计算的数值,并非标准中的数值。超过 20% 时显示警告。将负荷在各相之间调整,并观察该数值的变化。

应选择哪个需量表?

住宅装置选用 Table C1,非住宅装置选用 Table C2。Table C2 随后询问用途为居住还是商业,因为其为每类设有一列。两张表均包含最大需量工具所使用的 AS/NZS 3000:2018 Appendix C 数据。

这能否替代最大需量工具?

否。最大需量工具涵盖单一装置及居住单元组。本工具适用于您已知每个负荷所在相别的情况。两者均采用相同的Appendix C 计算引擎,因此同一相上的负荷在两个工具中得出的需量相同。

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 19 Sept 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。