AmpSize

修正系数计算器

读取每个修正系数,以及电缆所需的额定值。

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

输入

使用默认输入值的示例计算。

标准
NZ · AS/NZS 3008.1.2
敷设方式
在空气中封闭敷设
环境温度
40 °C
成组回路
3
相
单相
设计电流
32 A
电缆截面
6 mm²
材料
铜
绝缘
PVC 75 °C
芯线
多芯
并联电缆
1

综合修正系数

0.62x

所需表列电流
51.95A
6 mm² 的表列额定值
38A
修正后载流量 Iz
23.41A
环境温度修正系数
×0.88
成组修正系数
×0.70

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 环境温度修正系数×0.88

    AS/NZS 3008.1.2:2017 Table 27(1) p.88

  2. 成组修正系数×0.70

    AS/NZS 3008.1.2:2017 Tables 22, 25(1), 25(2) p.79, p.84–85

  3. 综合修正系数结果×0.62
  4. 表列要求电流51.95A

    AS/NZS 3000:2018 Cl 3.4

  5. 6 mm² 的表列额定值38A

    AS/NZS 3008.1.2:2017 Table 13 p.62–64

  6. 修正后的额定值 Iz23.41A

    AS/NZS 3000:2018 Cl 3.4

关于此计算器

How this is calculated

The tool reads every factor that lowers or raises the current a cable can carry on your route. It is the same code the cable size calculator runs before it tests each size.

  1. Ambient. It reads the factor for the air temperature, or the soil temperature on a buried route. AS/NZS 3008.1.2 rates New Zealand cables for 30 °C air and 15 °C soil. AS/NZS 3008.1.1 rates Australian cables for 40 °C air and 25 °C soil, so a cooler route gives a factor above 1.
  2. Grouping. It reads the factor for the circuits that share the route, by how they sit. On a tray, ladder, rack or cleats, pick the cable support. Each parallel cable set counts as a circuit.
  3. Buried cable. For a buried route it reads the soil thermal resistivity factor and the burial depth factor. Cable buried direct reads its depth factor by conductor size.
  4. Harmonics. On three phases with third harmonic current, it reads the reduction factor. Above 33 %, it sizes on the neutral current.
  5. Product. It multiplies the factors into one correction factor (derating factor in 2017). It divides the design current by that factor to give the tabulated current the cable needs.
  6. One size. It reads the tabulated rating of the size you pick and multiplies it by the factor. The result is Iz, which it checks against the design current.
StepTable or clauseWhat it decides
AmbientTables 27(1) and 27(2)The factor for the air or soil temperature
GroupingTables 22, 25(1) and 25(2)The factor for circuits run together
Cable supportTables 23 and 24The factor on a tray, ladder, rack or cleats
Buried cableTable 29, Tables 28(1) and 28(2)The factors for soil resistivity and depth
HarmonicsTable 2 and Cl 3.5.9The reduction for third harmonic current in the neutral
Required currentAS/NZS 3000 Cl 3.4The current the cable must carry in the table
Current ratingTable 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single coreThe tabulated rating of the size you pick

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section, such as Table 3.44 for Table 27(1).

Common routes, worked with the tool

Each line states its route. Every line uses multicore copper cable with PVC insulation, except where a line names single‑core cable.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 the tool reads. For Australia, the Edition select picks 2025 or the superseded 2017 edition. The 2025 edition changed several ambient and grouping factors, so run both when you check an older design.

To size the cable from these factors, use the cable size calculator. To check a cable that is already installed, use the circuit check.

问题

结果仅供设计参考。请依据现行标准核对。

修正系数与降容系数是否相同?

是的。AS/NZS 3008.1.1:2025 称之为修正系数,2017 年各部分称之为降容系数。两者都与表列额定值相乘,得出电缆在所走路径上实际承载的电流。

如何组合这些系数?

将它们相乘。环境温度、成组、土壤热阻系数、埋深和谐波系数均对额定值起作用。将设计电流除以该乘积,即得电缆所需的表列电流。

澳大利亚电缆在 30 °C 时为何系数大于 1?

AS/NZS 3008.1.1 的电缆额定值基于 40 °C 空气和 25 °C 土壤。较凉的敷设路径可使电缆承载更大电流。AS/NZS 3008.1.2 的新西兰电缆额定值基于 30 °C 空气和 15 °C 土壤。

并联电缆是否计为成组回路?

是的。并联回路的每组电缆在该组中均计为一个回路。三个回路,每个回路由两组并联电缆组成,则按六个回路取系数。

为何较大电缆的深度系数不同?

对于直接埋地的电缆,埋深表按导体截面划分系数区间:50 mm² 及以下,50 mm² 以上至 300 mm²,以及 300 mm² 以上。本工具读取您所选截面所在的区间。

计算示例

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 27 Sept 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。