选择通信电缆并检查线路长度。

无标准数据审核中

Reads AS/NZS 3000:2018 and Industrial communications sources 2019-2024. Tables checked 26 Sept 2026.

输入

使用默认输入值的示例计算。

接口
RS-485
环境
固定安装
敷设长度
100 m
护套材料
PVC
电缆带屏蔽层
是
传输速率
187.5 kbps
母线电缆系列
标准型、加强型、FRNC、食品级、地埋或船用

敷设长度

限值内

长度限值
1,000m
电缆结构
1 pair or more, 2 cores, larger than 0.34 mm2, required screen
屏蔽层
必需
屏蔽检查
通过
每端的终端连接
120Ω
每线单位负载
32
环境检查
通过
类别检查
不适用
备注
A PROFIBUS DP segment at 187.5 kbps on standard bus cable may run 1000 m, from a cable maker network manual. The held table falls from 1000 m at 9.6 kbps to 100 m from 3 Mbps up. TIA-485 itself sets no maximum line length, and a separate report gives a nominal 1.2 km on 24 AWG cable.

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 接口RS-485

    Industrial communications sources 2019-2024

  2. 回路长度100m
  3. 长度限值1,000m

    Industrial communications sources 2019-2024

  4. 长度校核通过
  5. 结构1 pair or more, 2 cores, larger than 0.34 mm2, required screen

    Industrial communications sources 2019-2024

  6. 需要屏蔽required

    Industrial communications sources 2019-2024

  7. 屏蔽检查通过
  8. 环境固定安装

    Industrial communications sources 2019-2024

  9. 环境检查通过
  10. 类别检查不适用
  11. 传输速率187.5 kbps
  12. 印刷速度行187.5 kbps

    Industrial communications sources 2019-2024

  13. 母线电缆系列标准总线电缆

    Industrial communications sources 2019-2024

  14. 两端端接120Ω

    Industrial communications sources 2019-2024

  15. 每线单位负荷32

    Industrial communications sources 2019-2024

  16. 每段总线接入点数32

    Industrial communications sources 2019-2024

关于此计算器

How this is calculated

The tool picks the cable construction for a control or data link. It checks your run length against the limit for the interface. No AmpSize figure here comes from a printed Standard. The figures come from maker data and course notes, which the tool labels as secondary sources.

  1. Interface. You pick 24 V d.c., 4–20 mA, RS-485, Ethernet or PROFINET. For RS-485 you also pick the data rate and the bus cable family.
  2. Length limit. The tool reads the longest run for that interface. For RS-485 the limit falls as the data rate rises.
  3. Length check. It compares your run with the limit. It reports the run as inside or over the limit.
  4. Construction. It gives the pairs, the cores and the smallest core size. It says whether a screen is required, and checks the screen you enter.
  5. Environment. It checks the sheath and the bend radius for a fixed or a flexing installation. For Ethernet it checks the category.
  6. Termination. For RS-485 it gives the termination at each end and the unit loads per line.
StepSourceWhat it decides
Length limitIndustrial communications sources 2019 to 2024The longest run for the interface
Construction and screenIndustrial communications sources 2019 to 2024The cable build
TerminationIndustrial communications sources 2019 to 2024The resistor at each end

Worked example

Limits

  • The figures are secondary source and maker data. They are not a Standard. Confirm each one with the device maker.
  • The tool does not size power conductors. Use the DC cable size calculator for a 24 V supply.
  • The tool does not check segregation from power cables. Use the segregation checker.
  • The termination value suits typical cable. Match it to the cable you use.
  • The 32 unit loads on an RS-485 line are not a device count.

See also: Control panels and PLC wiring, 24 V DC instrument loop voltage drop and Loop power.

问题

结果仅供设计参考。请依据现行标准核对。

通信电缆选型工具有什么作用?

为 24 V 直流、4–20 mA、RS-485、以太网或 PROFINET 链路指明电缆结构,并说明线路长度是否在该接口的限值之内。它还会根据环境检查护套、屏蔽层和弯曲半径。

RS-485 段的最大长度是多少?

工具依据电缆制造商手册报告 PROFIBUS DP 段长度:标准总线电缆在 187.5 kbps 及以下为 1000 m,500 kbps 时为 400 m,1.5 Mbps 时为 200 m,3 Mbps 及以上为 100 m。柔性和扭转电缆的线路应更短。

RS-485 的 32 个上限指的是什么?

以单位负载计,而非按设备数量计。一个单位负载在 12 V 共模应力下耗电 1 mA。输入电阻超过 12 kΩ 的接收器仅相当于一个单位负载的一部分,因此一条线路可接入超过 32 个接收器。

RS-485 需要什么终端匹配?

终端电阻等于线路的特性阻抗。所用的源按两端各 120 ohm 工作,因此应与所用电缆匹配。足够短、可按集总参数处理的线路无需终端电阻。

24 V 直流和 4–20 mA 适用什么长度限制?

两者均无公布的长度。24 V 直流线路受电压降限制,因此请在 24 V 下使用 AmpSize 电压降工具。4–20 mA 回路受回路负载和变送器供电电压限制。

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 26 Sept 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。