蓄电池电弧闪络与等级
蓄电池 DVC、危险等级、电弧闪络能量及个人防护装备等级。
Reads AS/NZS 5139:2019. Tables checked 1 Oct 2026.
尝试一个工程 4
每项工作都会预填示例数值。请替换为您自己的数值。
- Check a 48 V home battery's arc flashThe energy, PPE level and home limit for a 48 V lithium battery.
- See what inter-string fuses saveThe arc flash of a 48 V battery when a fuse clears the arc in 0.1 s.
- Class a lead acid bank in a shedA 24 V lead acid bank in a battery room away from the house.
- Class a high voltage home batteryThe decisive voltage class and energy of a pre-assembled lithium battery.
输入
使用默认输入值的示例计算。
- 化学
- 锂离子
- 按最佳实践指南预装,或采用 V0 级外壳
- 否
- 电池最高直流电压
- 51.2 V
- 作业处的螺栓故障电流
- 6 kA
- 电弧时间
- 2 s
- 工作距离
- 45 cm
- 外壳
- 电池外壳或机柜(系数 3)
- 位置
- 位于住宅内或住宅处
电弧闪络入射能量
4.55cal/cm²
- PPE 等级
- 第 2 级
- 后果等级
- 中等
- 电弧闪络边界
- 876mm
- 决定电压等级
- A
- 火灾危险等级
- 第 1 级
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 决定性电压等级A
AS/NZS 5139:2019 Table 3.2
- 火灾危险等级第 1 级
AS/NZS 5139:2019 Table 3.1
- 已列明的危险电气、能量、机械、爆炸性气体及有毒烟雾
AS/NZS 5139:2019 Table 3.1
- 电弧电流,为螺栓故障电流的一半3kA
AS/NZS 5139:2019 Eq 3.2.4(2)
- 乘数系数3
AS/NZS 5139:2019 Cl 3.2.4.3
- 电弧闪络入射能量结果4.55cal/cm²
AS/NZS 5139:2019 Eq 3.2.4(1)
- 电弧闪络边界876mm
AS/NZS 5139:2019 Eq F.4
- PPE 等级第 2 级
AS/NZS 5139:2019 Table 3.3
- 后果等级中等
AS/NZS 5139:2019 Table 6.1
关于此计算器
How this is calculated
AS/NZS 5139 asks for a battery system to be classed before it is installed: which hazards its chemistry carries, which voltage class it is in, and how much energy an arc at its terminals would release. This tool works all three from a few inputs and reads the tables that follow from them.
The hazards and the fire hazard level come from the chemistry. Lithium ion is fire hazard level 1, lead acid and nickel alkaline level 2. A note to the table lifts the level for pre-assembled lithium equipment that meets the industry Best Practice Guide, and for lead acid or nickel alkaline in cases rated V0. The decisive voltage class comes from the battery's highest d.c. voltage.
The arc flash energy uses the standard's equation. It multiplies the battery voltage, the arcing current, the arcing time divided by the working distance squared, and a factor for where the arc is: at least 3 in an enclosure and 1.5 in a room. The arcing current is half the bolted fault current. The working distance is 45 cm at most. The arcing time is 2 s where the protective device's time is not known, or where the work is on its battery side. The boundary is the distance where the energy falls to 1.2 cal/cm². The appendix tables are this equation at 45 cm and a factor of 3, and a test runs every printed row through it.
The energy then sets the PPE level, the consequence level for the risk assessment, and, in a home or outside one, the limits on where the system may go.
| Step | Table or clause | What it decides |
|---|---|---|
| Hazards and fire hazard level | AS/NZS 5139 Table 3.1 | What the chemistry carries |
| Decisive voltage class | AS/NZS 5139 Table 3.2 | DVC-A, B or C from the d.c. voltage |
| Arcing current and energy | AS/NZS 5139 Cl 3.2.4 | The incident energy at the working distance |
| Arc flash boundary | AS/NZS 5139 Equation F.4 | Where the energy falls to the boundary level |
| PPE level | AS/NZS 5139 Table 3.3 | The arc-rated clothing level |
| Consequence level | AS/NZS 5139 Table 6.1 | The consequence for the risk assessment |
| Home and outdoor limits | AS/NZS 5139 Cl 6.3.2.3 | Where the system may go at that energy |
Worked examples
- A 48 V lithium home battery with 6 kA at its terminals releases 4.27 cal/cm² over 2 s, PPE Level 2. Above 4 cal/cm² in a home it needs a dedicated room or fire hazard level 1.
- The same battery with inter-string fuses clearing in 0.1 s releases 0.21 cal/cm², PPE Level 1.
- A 24 V lead acid bank in a battery room away from the house releases 2.13 cal/cm² at a factor of 1.5, PPE Level 1.
- A 204.8 V pre-assembled lithium home battery with 9 kA is DVC-C and releases 27.31 cal/cm², PPE Level 4.
- A 350 V system with 15 kA in a plant room releases 77.78 cal/cm², so it fails: no PPE level applies above 40.
Limits
The tool works the energy at one point with one arcing time. It does not find the bolted fault current, which comes from the battery maker or the home battery tool, or a fuse's clearing time at that current, which comes from its curve. It does not grade the likelihood side of the risk matrix.
The tool reads the 2019 edition as published. Amendment 1 (2025) is not on hand, so check any change it makes before relying on a figure.
See also: Home battery, Arc flash and Battery.
问题
结果仅供设计参考。请依据现行标准核对。
蓄电池电弧闪络能量如何求出?
AS/NZS 5139 Cl 3.2.4 将蓄电池电压、电弧电流、电弧时间除以工作距离的平方,再乘以外壳系数。电弧电流为金属性短路电流的一半。
应采用多长的电弧时间?
保护装置动作时间未知,或作业位于其蓄电池侧时,采用 2 s。在另一侧,则采用该保护装置在此故障电流下的动作时间。组串之间设置熔断器可缩短时间并降低能量。
蓄电池的决定性电压等级是什么?
AS/NZS 5139 Table 3.2 将直流蓄电池分类:60 V 及以下为 DVC-A,120 V 及以下为 DVC-B,超过者为 DVC-C。DVC-B 或 DVC-C 系统属于 AS/NZS 3000 所规定的低压装置。
家用储能电池的入射能量能否超过 4 cal/cm²?
是的,低于 40 cal/cm²。高于 4 时,须设在专用房间或外壳中,该房间或外壳不得附接于有居住房间的建筑,或须符合火灾危险等级 1,且不得设于此类建筑内部或紧靠其设置。组串间保护可降低该数值。
需要哪个等级的个人防护装备?
AS/NZS 5139 Table 3.3 按能量规定个人防护装备等级:等级 1 为 4 cal/cm² 及以下,等级 2 为 8,等级 3 为 25,等级 4 为 40。超过 40 时不适用任何个人防护装备等级。
计算示例
背景
本工具读取的条款和表格
- AS/NZS 5139:2019 Cl 3.2.4Battery arc flash energy
- AS/NZS 5139:2019 Cl 3.2.4.2.3Arc duration for a battery
- AS/NZS 5139:2019 Cl 3.2.4.3Arc flash multiplying factor
- AS/NZS 5139:2019 Cl 6.3.2.3Arc flash limits for a home battery
- AS/NZS 5139:2019 Eq 3.2.4(1)Battery arc flash incident energy
- AS/NZS 5139:2019 Eq 3.2.4(2)Battery arcing current
- AS/NZS 5139:2019 Eq F.4Battery arc flash boundary
- AS/NZS 5139:2019 Tables 3.1 to 3.3, 6.1 and F.1 to F.4Battery system hazard classes, decisive voltage class, arc flash energy, PPE level and consequence level
表格最后核对于 1 Oct 2026。