跳至内容
AmpSize

AS/NZS 5139:2019

Cl 4.2.2 to 4.2.5

Location, clearance and barrier rules for a pre-assembled integrated BESS

The home battery tool and the battery location check read the places an all-in-one battery must not go, and the clearance, barrier, IP and access figures. Amendment 1 (2025) is not held.

已核验:对照印刷版标准阅读,页码 34–37 (PDF 42–45)。检查于 1 Oct 2026。

单位:Value mm mm

这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。

返回 AS/NZS 5139:2019 页面上的对应卡片

23 行

Cl 4.2.2 to 4.2.5, Location, clearance and barrier rules for a pre-assembled integrated BESS
KindValue mmClausePageIp
location—4.2.2.2(a)34
clearance6004.2.2.2(b)34
clearance6004.2.2.2(c)34
clearance6004.2.2.2(d)34
clearance9004.2.2.2(e)34
location—4.2.2.2(f)34
location—4.2.2.2(g)34
location—4.2.2.2(h)34
location—4.2.2.2(i)34
location—4.2.2.2(j)34
location—4.2.2.2(k)34
location—4.2.2.234
clearance10004.2.2.134
location—4.2.2.235
ip—4.2.3.235IP2X
ip—4.2.3.235IP23
barrier3004.2.4.236
barrier6004.2.4.2(i)36
barrier9004.2.4.2(ii)36
barrier9004.2.4.236
barrier6004.2.4.236
access6004.2.537
access9004.2.537

读取它的工具 (2)