AS/NZS 3000:2018
Section 6 RCD and bonding
RCD, bonding and floor clearance rules for damp situations
The wet area zones tool reads the Section 6 RCD rules, the 0.3 m floor rule and the 4 mm² bonding conductor here.
已核验:对照印刷版标准阅读,页码 124, 127, 307–308, 312, 320, 338–341, 349–352, 355, 358, 360–361 (PDF = page + 4)。检查于 1 Oct 2026。
单位:Value unit column
这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。
30 行
| Rule | Jurisdiction | Group | Zone | Equipment | Value (unit column) | Unit | Alternatives | Clause | Page |
|---|---|---|---|---|---|---|---|---|---|
| rcd | both | bath-shower-container | 2 | socket | 30 | mA | shaver-unit | 6.2.4.2(b) | 320 |
| rcd | both | bath-shower-container | 3 | socket | 30 | mA | separated-circuit, selv-pelv | 6.2.4.2(c) | 320 |
| rcd | both | pool-spa | 0 | other | 30 | mA | separated-circuit | 6.3.3.3 | 338 |
| rcd | both | pool-spa | 1 | socket | 30 | mA | separated-circuit, selv-pelv | 6.3.4.3(b) | 340 |
| rcd | both | pool-spa | 2 | socket | 30 | mA | separated-circuit, selv-pelv | 6.3.4.3(c) | 340 |
| rcd | both | pool-spa | 1 | luminaire | 30 | mA | selv-pelv, class-2-fixed | 6.3.4.5.4 | 341 |
| rcd | both | pool-spa | 1 | other | 30 | mA | selv-pelv, class-2-fixed | 6.3.4.5.4 | 341 |
| rcd | both | pool-spa | 2 | luminaire | 30 | mA | selv-pelv, separated-circuit, class-2 | 6.3.4.5.5 | 341 |
| rcd | both | pool-spa | 2 | other | 30 | mA | selv-pelv, separated-circuit, class-2 | 6.3.4.5.5 | 341 |
| rcd | both | fountain | 1 | luminaire | 30 | mA | selv-pelv, class-2-fixed | 6.4.4.5.4 | 352 |
| rcd | both | fountain | 1 | other | 30 | mA | selv-pelv, class-2-fixed | 6.4.4.5.4 | 352 |
| rcd | both | fountain | any | any | 30 | mA | isolating-transformer | 6.4.3.2.1 | 349 |
| rcd | both | sauna | any | any-but-heater | 30 | mA | — | 6.5.3.3 | 355 |
| rcd | both | refrigeration-room | room | door-seal-heater | 30 | mA | — | 6.6.3.6 | 360 |
| rcd-section-2 | nz | residential | any | socket-lighting-hand-held | 30 | mA | — | 2.6.3.3.1 | 127 |
| rcd-section-2 | au | domestic | any | any | 30 | mA | — | 2.6.3.2.2 | 124 |
| floor-clearance | both | bath-shower-container | any | socket-or-switch | 0.3 | m | — | 6.2.4.2 | 320 |
| floor-clearance | both | pool-spa | any | socket | 0.3 | m | — | 6.3.4.3 | 339 |
| pool-socket-height | both | pool-spa | 1 | socket | 0.45 | m | — | 6.3.4.3(b) | 339 |
| pool-socket-distance | both | pool-spa | 1 | socket | 1.25 | m | — | 6.3.4.3(b) | 339 |
| bonding-conductor | both | shower-bathroom-pool-spa | any | bonding | 4 | mm² | — | 5.6.3.2(b) | 312 |
| bonding-reinforcing | both | shower-bathroom | any | reinforcing | — | — | — | 5.6.2.5 | 307 |
| bonding-pool-resistance | both | pool-spa | any | bonding | 0.5 | Ω | — | 5.6.2.6.1 | 308 |
| bonding-pool-equipment | both | pool-spa | any | extraneous-parts | — | — | — | 6.3.3.2 | 338 |
| prohibited-measures | both | bath-shower-container | any | obstacles-or-out-of-reach | — | — | — | 6.2.3 | 320 |
| prohibited-measures | both | pool-spa | any | obstacles-or-out-of-reach | — | — | — | 6.3.3.1 | 338 |
| prohibited-measures | both | fountain | any | obstacles-or-out-of-reach | — | — | — | 6.4.3.2.2 | 350 |
| prohibited-measures | both | sauna | any | obstacles-or-out-of-reach | — | — | — | 6.5.3.2 | 355 |
| prohibited-measures | both | refrigeration-room | any | obstacles-or-out-of-reach | — | — | — | 6.6.2.2 | 358 |
| prohibited-measures | both | hosing-down | any | obstacles-or-out-of-reach | — | — | — | 6.7.3.2 | 361 |