Wire colours in NZ and Australia, old and new

基础级别

A drawn cables schematic for Wire colours in NZ and Australia: supply, board, cable run, junction and load.

The colour of a conductor's insulation tells you what it is meant to be. AS/NZS 3000 sets the colours for fixed installation wiring, and AS/NZS 3760 gives the colours of flexible cords. This page sets them out for New Zealand and Australia, with the colours older work still carries.

Fixed wiring

FunctionColour
Protective earthGreen/yellow
Equipotential bondingGreen/yellow
NeutralBlack or light blue
ActiveAny colour other than green, yellow, green/yellow, black or light blue
  • New Zealand homes. In a domestic installation the neutral is black only (Table 3.4 Note 4).
  • Recommended actives. Red or brown for a single‑phase active; red, white or blue for the actives of a multiphase circuit. These are recommendations. The table sets no phase order.
  • Never live. Green, yellow and green/yellow are never an active or a neutral in installation wiring (Cl 3.8.1).
  • No mixing. Australian and New Zealand colours and European colours do not go in one enclosure or one multicore cable.

Older installations

An installation wired to a previous edition may carry:

  • a bare or green earthing or bonding conductor, which may stay; a new termination on it is sleeved green/yellow (Cl 3.8.2.2);
  • a yellow live conductor, which may stay; a new termination on it is sleeved white (Cl 3.8.2.3).

Sleeving can also mark a black or light blue conductor as an active, or another colour as a neutral, at each termination. It never turns a green, yellow or green/yellow conductor into either.

Flexible cords

FunctionModern cordSuperseded cord
ActiveBrownRed
NeutralLight blueBlack
EarthGreen/yellowGreen

A modern three‑phase cord has brown, black and grey phases, a blue neutral where it has one, and a green/yellow earth on Class I equipment. A Class II cord has no earth. Old and imported cord sets may follow neither scheme.

Before you trust a colour

A colour is what the installer meant. Prove a conductor dead and prove what it is by test before you work on it.