Whakawhenua whare o waho
Whakawhenuatia he whare iti: he whenua me te submain, he MEN motuhake rānei.
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
Whakamātau mahi 4
Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.
- Earth a shed through the submainThe earth to run with a 10 mm² submain to a shed.
- Set up a shed as its own MENThe PEN, main earth and rod depth for a 16 mm² submain.
- Check a sleep-out with a metal water pipeA separate MEN where a metal pipe joins the buildings.
- Earth a farm shed in AustraliaA separate MEN on a strip electrode for a 25 mm² three phase submain.
Ngā whakauru
He tauira mahi me ngā whakauru taunoa.
- Whenua
- Aotearoa
- Whare waho
- Takitahi: he hanga kotahi me tōna ake poari
- Whakaritenga whenua
- Rerenga whenua me te submain
- Wāhanga matua-iti
- Wāhanga kotahi
- Rahi matua-iti e mahi ana
- 6 mm²
- Kaikawe
- Parahi
- Ratonga whakarau i waenga i ngā whare
- Kāo
Te kaiwhakahaere whenua tiaki
2.5mm²
- Whakaaetia mō tēnei whare waho
- Whenua me te submain, he MEN motuhake rānei
He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.
Ngā hīkoi tātaitanga
- Whare wahoTakitahi
AS/NZS 3000:2018 Cl 1.4.88
- Whakaritenga whenuaWhenua me te ara-iti matua
AS/NZS 3000:2018 Cl 5.5.3.1(a)(i)
- Whakaaetia ki koneiĀe
AS/NZS 3000:2018 Cl 5.5.3.1(a)(i)
- Kaiwhakahaere whenua whakamarutangaHua2.5mm²
AS/NZS 3000:2018 Table 5.1
Mō tēnei tātaitai
How this is calculated
A shed, garage, sleep-out or workshop with its own board, fed by a submain, is an outbuilding. AS/NZS 3000 gives it two ways to be earthed. The tool asks which outbuilding it is and which way you plan, then checks the plan and gives the sizes.
An individual outbuilding is one structure, separated by land from the building whose board supplies it. It may take a protective earthing conductor run with the submain, connected at the main switchboard. Or it may be a separate MEN installation: the submain neutral becomes a PEN, the outbuilding board has its own MEN link, and an electrode is driven at the outbuilding. Combined outbuildings share a foundation, a metal roof or a metal frame. They take the earth with the submain only, so a separate MEN for them fails.
The sizes come from the same table as the earthing tool. With an earth in the submain, it is the protective earthing conductor for the submain's active size. With a separate MEN, the lead from the outbuilding board to its electrode is a main earthing conductor, sized from the submain. The PEN must be at least the neutral the submain needs and at least that earthing conductor, so the tool gives the larger. The electrode is one of the types the electrode table accepts, driven to the depth or laid to the length and cover for your country.
| Step | Table or clause | What it decides |
|---|---|---|
| Individual or combined | Cl 1.4.88 and Cl 1.4.89 | Which arrangements the outbuilding may take |
| Earth with the submain | Cl 5.5.3.1(a)(i) and Cl 5.5.2.1 | Where the earth connects |
| Separate MEN | Cl 5.5.3.1(a)(ii) and (c) | The MEN link, the board and the main earthing conductor |
| Combined outbuilding | Cl 5.5.3.1(b) | No separate MEN |
| Earthing conductor sizes | Table 5.1 | The protective and main earthing conductors |
| PEN size | Cl 3.5.2(c) | The least PEN of the submain |
| Electrode | Table 5.2 and Cl 5.3.6.3 | The electrode, and its depth, length and cover |
Worked examples
- A shed on a 10 mm² submain, earthed through the submain. The protective earthing conductor is 4 mm². No electrode is needed at the shed.
- A shed on a 16 mm² submain as its own MEN. The PEN is at least 16 mm², the main earthing conductor 6 mm², and the rod goes at least 1.8 m deep.
- A sleep-out with a metal water pipe to the house. The PEN is at least 6 mm². The tool warns that the pipe can carry neutral current in parallel with the PEN.
- A farm shed in Australia on a strip electrode. The PEN is at least 25 mm² and the main earthing conductor 6 mm². The copper strip is at least 3 m long with 0.5 m cover.
- Two sheds on one slab as a separate MEN. The arrangement is Not allowed and fails: combined outbuildings take an earth with the submain only.
Limits
The tool does not size the submain itself; use the cable size or total voltage drop tools for that. It does not check the earth fault-loop impedance at the outbuilding, which the loop impedance tool does. It does not decide whether a structure is an outbuilding: that is the definition and your site. Bonding of water pipes and other services follows the earthing tool.
See also: Earthing an outbuilding: earth or its own MEN, Shed earthing on a 16 mm² submain and Earthing and bonding.
Pātai
He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.
Me whai earth stake ōna anō te whare o waho?
Ehara i te mea i ngā wā katoa. Ka whakaaetia e AS/NZS 3000 Cl 5.5.3.1 tētahi whare o waho takitahi kia whai i te rerenga whakawhenua me te submain, kāore he electrode. Ahakoa he whakaurunga MEN motuhake pea, me whai electrode me te MEN link ōna anō.
He aha te rerekē i waenga i tētahi whare o waho takitahi me tētahi whare o waho kua whakakotahi?
Ko te whare o waho takitahi he hanga kotahi me tōna ake papa, he wehe whenua i te whare e tuku hiko ana ki a ia. Ko ngā whare o waho kua honoa he taketake, he tuanui whakarake, he anga whakarake rānei ō rātou. Ka mau ngā whare o waho kua honoa i te whenua mā te submain anake.
He rahi pēhea te PEN ki tētahi whare o waho MEN motuhake?
Me neutral iti rawa e hiahiatia ana e te submain, arā, te rahi active mō te submain wāhanga kotahi, me te kaikawe whakawhenua iti rawa mai i Table 5.1. Ka hoatu e te taputapu te nui ake.
He hōhonu pēhea te earth electrode?
Ka werohia te rākau whenua kia 1.8 m te hōhonu i te iti rawa i Aotearoa, kia 1.2 m i Ahitereiria. Ko te rīpene whenua i roto i te waikeri, kia 0.5 m te iti rawa o te oneone ki runga, ā, kia 7.5 m te roa i te iti rawa i Aotearoa, kia 3 m rānei i Ahitereiria.
He aha ngā paipa rino i waenga i ngā whare e whai take ai?
Ina wehe te MEN motuhake, ko te neutral submain he whakawhenua anō hoki. Ka taea e tētahi paipa wai rino, tētahi ara hīkoi i waenga i ngā whare te kawe i tētahi wāhanga o te Iahiko Neutral i te parallel. Ka whakatūpato te taputapu, ā, ka karo te whakawhenua me te submain i tērā.
Ngā tauira mahi
Kōrero o muri
Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu
- AS/NZS 3000:2018 Cl 1.4.88Outbuilding definition
- AS/NZS 3000:2018 Cl 3.5.2(c)PEN conductor to an outbuilding
- AS/NZS 3000:2018 Cl 5.3.6.3Installing an earth electrode
- AS/NZS 3000:2018 Cl 5.5.2.1Where the protective earthing conductor connects
- AS/NZS 3000:2018 Cl 5.5.3.1Earthing an outbuilding
- AS/NZS 3000:2018 Cl 5.5.3.1Earthing arrangements for an outbuilding
- AS/NZS 3000:2018 Table 5.1Minimum earthing conductor size by active conductor size
- AS/NZS 3000:2018 Table 5.1Minimum copper earthing conductor size for aluminium active conductors
Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi
Ngā tūtohi i arotakehia whakamutunga i te 1 Oct 2026.
Ngā taputapu hononga
- Tātaitai hōhonu taura i raro i te whenuaDepth of cover and separation for a buried cable.AS/NZS 3000
- Tātaitai rahi tauraFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Tātaitai whakawhenua me te bondingSize earthing, main earth and bonding conductors.AS/NZS 3000
He whai hua tēnei?
He pātai, he uara rānei e kitea ana he hē? Whakapā mai.