Tātaitai ara iahiko mōtā
Taura, breaker, contactor me te overload mō tētahi mōtā.
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3000:2018 and AS/NZS 3008.1.1:2025 (AU). Tables checked 1 Oct 2026.
Whakamātau mahi 4
Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.
- Kit out a pump motor circuitCable, breaker, contactor and overload for a 7.5 kW pump 40 m away.
- Kit a star-delta starter for a fanThe three contactors and the relay for a 37 kW fan.
- Size a soft starter circuitA 22 kW conveyor motor on a soft starter limited to 3 × FLC.
- Kit a single‑phase motor circuitA 2.2 kW compressor at 230 V, 25 m from the board.
Ngā whakauru
He tauira mahi me ngā whakauru taunoa.
- Pūngao tahanga
- 15 kW
- Ngā wāhanga
- Wāhanga toru
- Voltage
- 400 V
- Power factor
- 0.85
- Pai
- 0.9
- Iahiko rotor kua aukatia
- 0 × FLC
- Kaitīmata
- Direct on line
- Momo circuit-breaker
- Kauwhata D
- Reiti circuit-breaker
- 0 A
- Paerewa
- NZ · AS/NZS 3008.1.2
- Te roa o te ara
- 30 m
- Tikanga whakaurunga
- Kua kōpakina ki te hau
- Kaikawe
- Parahi
- Insulation
- PVC 75 °C
- Pāmahana taiao
- 30 °C
- Ngā ara iahiko kua whakarōpūtia
- 1
- Ze i te poari
- 0.35 Ω
- Ka rere kāore e tirotirohia
- Kāo
- Ratonga whakamarumaru ahi
- Kāo
Waea me te kaiwhakatere
16 mm² i 32 A momo D
- Iahiko Uta Katoa
- 28.3A
- Au tīmata
- 226.4A
- Main contactor, AC-3
- 32A
- Whakatakotoranga relay overload
- 28.3A
- Awhe relay ārai
- 23 ki te 32 A
- Kaiwhakawehe whakawhiti, AC-23, iti rawa
- 28.3A
He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.
Ngā hīkoi tātaitanga
- Au utanga katoa28.3A
- Au rotor aukati226.4A
AS/NZS 3000:2018 Cl 4.13.1.2(i)
- Te au tīmatanga, tīmata tika i te raina226.4A
- Circuit-breaker, momo D32A
- Pito iti o te whānui wawe (whānui)320A
- Te contactor matua, AC-3, iti rawa28.3A
- Tautuhinga relay ārai28.3A
- Reiti isolating switch, i te iti rawa atu28.3A
AS/NZS 3000:2018 Cl 4.13.1.2
- Tiaki overloadHiahiatia
AS/NZS 3000:2018 Cl 4.13.2
- Tiaki pāmahana nuiHiahiatia
AS/NZS 3000:2018 Cl 4.13.3.1(b)
- Tauutu whakaheke pāmahana taiao×1.00
AS/NZS 3008.1.2:2017 Tables 27(1), 27(2) p.88
- Tauwehe whakaheke whakarōpū×1.00
One circuit, no grouping factor
- Tauwehe whakaiti oneone×1.00
AS/NZS 3008.1.2:2017 Table 29 p.90
- Tauutu whakaheke hōhonu tanu×1.00
AS/NZS 3008.1.2:2017 Tables 28(1), 28(2) p.89
- Tauwhāinga whakaiti katoa×1.00
- Au ripanga e hiahiatia ana28.3A
AS/NZS 3000:2018 Cl 3.4
- Rahi kaikawe kua kōwhiria16mm²
AS/NZS 3008.1.2:2017 Table 13 p.62–64
- Kaha au whakaheke66A
AS/NZS 3000:2018 Cl 3.4
- Heke whakahiato0.45%
- Reiti taputapu In32A
AS/NZS 3000:2018 Cl 2.5.3.1
- Rahi kaikawe whenua6mm²
AS/NZS 3000:2018 Table 5.1
- Ārai ara hapa whenua i 230 V wae ki te whenua0.5Ω
AS/NZS 3000:2018 Table 8.1
Mō tēnei tātaitai
How this is calculated
The tool sizes the circuit for one motor: the cable, the circuit-breaker, the contactor, the overload relay and the isolating switch. It reads AS/NZS 3000:2018 Cl 4.13 and sizes the cable with the cable size tool.
- Full load current. It divides the shaft power by the supply factor, the power factor and the efficiency. This is the same figure as the motor tool.
- Locked-rotor current. It takes the maker's multiple of full load current. With none, it takes 8 times full load current (Cl 4.13.1.2(i)).
- Starting current. Direct on line, the start equals the locked-rotor current. Star-delta gives a third of it. A soft starter gives the limit you enter. A drive gives about 1.5 times full load current (generic).
- Circuit-breaker. It picks the smallest standard rating at or above full load current. The low end of its instantaneous band must clear the start. The bands are generic: type B 3, type C 5 and type D 10 times the rating.
- Cable. The cable size tool sizes it with that breaker. The cable current capacity must be at least the breaker rating. It also checks the voltage drop and the earth loop with the Ze you type.
- Contactor and overload relay. It picks an AC-3 frame and a relay range from generic lists. Direct on line and soft start use full load current. Star-delta uses full load current divided by √3 for the main contactor, the delta contactor and the relay. The star contactor uses full load current divided by 3.
- Isolating switch. It must carry full load current and break the locked-rotor current. An AC-23 switch at or above full load current does both (Cl 4.13.1.2).
- Motor protection. Overload protection applies above 370 W (Cl 4.13.2). Overtemperature protection applies above 2250 W, or above 240 VA for a motor that runs unattended (Cl 4.13.3.1). A motor on a fire-protection service has neither (Cl 4.13.3.2).
| Step | Clause or source | What it decides |
|---|---|---|
| Full load current | Motor tool | The running current |
| Locked-rotor current | Cl 4.13.1.2(i) | The current at standstill |
| Starting current | Starter type, generic | The current the device must ride through |
| Circuit-breaker | Generic bands | The rating and the type |
| Cable | Cable size tool | The conductor size |
| Contactor and relay | Generic frames and ranges | The AC-3 frames and the relay setting |
| Isolating switch | Cl 4.13.1.2 | The AC-23 rating |
| Motor protection | Cl 4.13.2 and Cl 4.13.3 | Overload and overtemperature protection |
Worked example
- 15 kW, 400 V, three‑phase pump, direct on line, 30 m, type D. The tool gives a full load current of 28.3 A and a locked-rotor current of 226.4 A. The result is a 16 mm² cable on a 32 A type D circuit-breaker. The contactor frame is 32 A. The relay setting is 28.3 A in the 23 to 32 A range. The isolating switch must be 28.3 A or more at AC-23.
Limits
- The contactor frames, relay ranges, breaker bands and the soft starter and drive starting currents are generic. They are not from a standard. Check the maker's catalogue and coordination tables.
- The locked-rotor figure of 8 times full load current is a default. Use the maker's figure when you have it.
- The cable is sized to the breaker rating. Where the overload relay protects the cable, a smaller cable can be allowed.
- Star-delta needs six cables to the motor. Each carries full load current divided by √3.
- A drive can draw a different input current. Size the supply from the drive data sheet.
- The tool does not check the prospective fault current or the breaker breaking capacity.
See also: Motor circuit for a 15 kW pump: DOL or star-delta, Motor starters, contactors and overload relays, Motor circuits and starting, the motor calculator and the cable size calculator.
Pātai
He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.
He aha tā te taputapu Ara Iahiko Mōtā e hoatu ana ki ahau?
Tētahi hua mō tētahi mōtā: te iahiko uta katoa me te iahiko locked-rotor, te iahiko tīmata, te taura, te circuit-breaker, ngā contactor, te tautuhinga me te awhe o te overload relay, me te reiti o te isolating switch.
He aha e kōwhiri ai ia i tētahi circuit-breaker Type D?
Ka tango te tīmata direct-on-line i ngā wā maha o te uta katoa mō ētahi hēkona. Ka whakakore wawe te breaker momo D i te nui rawa atu i tōna reiti, nā reira ka whakahaere ia i te tīmata. Ka whakapiki te taputapu i te reiti momo C kia mutu ai te tīmata.
Me pēhea te rahi o tētahi starter star-delta?
Ko ngā contactor main me delta me te overload relay e kawe ana i te iahiko wāhanga, te uta katoa ka wehea ki te √3. Ka kawe te contactor star i te tuatoru o te uta katoa. Ko ngā taura e ono ki te mōtā, ia kawe ana i te iahiko wāhanga anō.
Nō hea mai te iahiko locked-rotor?
Whakauru mai i te kaihanga, i te reta waehere rānei. Ki te kore, ka tango te taputapu i te waru ngā wā o te uta katoa, te tauanga e hoatu ana a AS/NZS 3000 Cl 4.13.1.2 mō tētahi mōtā a.c. Me whati e te isolating switch.
He paerewa ngā rahi contactor me relay?
Kāo. He tatauranga whānui ngā rahi anga, ngā whānuitanga relay me ngā pae circuit-breaker. Ka whakaatu ēnei i te momo wāhanga hei rapu. Arotakehia te katarāgi a te kaihanga me ōna tūtohi whakarite i mua i te hoko.
Ngā tauira mahi
Kōrero o muri
Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu
- AS/NZS 3000:2018 Cl 4.13.1.2Rating of a motor switch
- AS/NZS 3000:2018 Cl 4.13.2Overload protection of a motor
- AS/NZS 3000:2018 Cl 4.13.3.1Overtemperature protection of a motor
- AS/NZS 3000:2018 Cl 4.13Motor switching, overload and overtemperature figures
- AS/NZS 3000:2018 Table 8.1Maximum earth fault loop impedance multipliers by MCB curve
- AS/NZS 3008.1.2:2017 Table 13Current ratings, multicore cable with three or four cores, thermoplastic 75 °C
- AS/NZS 3008.1.1:2025 Table 3.18Current ratings, multicore cable with three or four cores, thermoplastic 75 °C
Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi
Ngā tūtohi i arotakehia whakamutunga i te 1 Oct 2026.
Ngā taputapu hononga
- Tātaitai mōtāFind motor full load current, starting current and torque.Kāore he paerewa
- Tātaitai rahi tauraFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Whakataurite tikanga tīmatanga mōtāCompare DOL, star-delta, soft start and drive starts.Kāore he paerewa
He whai hua tēnei?
He pātai, he uara rānei e kitea ana he hē? Whakapā mai.