Kaiwhakarerekē rahi taura imperial
Kimihia te reiti taputapu mō tētahi taura imperial tawhito.
Reads AS/NZS 3000:2018. Tables checked 26 Sept 2026.
Whakamātau mahi 3
Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.
Ngā whakauru
He tauira mahi me ngā whakauru taunoa.
- Rahi uaua iāri
- 7/.029
- Tikanga whakaurunga
- Kore kēhi
- Insulation
- V75
Reiti circuit-breaker nui rawa
32A
- Pūtau, rānei circuit-breaker whakauru kua tāpaetia
- 20A
- Rohe kua tātarihia
- 2.98mm²
- Rahi mētric tata rawa
- 2.5mm²
He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.
Ngā hīkoi tātaitanga
- Waea i roto i te kaiwhakahaere7
- Diameter waea, inihi0.03
- Rohe kaikawe kua tātarihia2.98mm²
- Rahi mita e tata ana2.5mm²
- Ine circuit-breaker teitei rawaHua32A
AS/NZS 3000:2018 Table I1
- Reiti wōhanga here anō, circuit-breaker tomo-atu nui rawa kua tūturu20A
AS/NZS 3000:2018 Table I1
Mō tēnei tātaitai
How this is calculated
The tool finds the largest fuse or circuit-breaker for an old imperial-size cable. You use it when you alter or repair existing wiring. It reads AS/NZS 3000:2018 Appendix I, Table I1.
- Wires. You pick the size as the wire count and the wire diameter in inches, such as 7/.029.
- Calculated area. The tool works out the conductor area from the wire count and the diameter. This is a calculation. It is not a table value.
- Nearest metric size. It gives the nearest metric size for that area.
- Method and insulation. You pick how the cable is installed, unenclosed or partially surrounded, and the insulation, V75 or V60.
- Circuit-breaker rating. The tool reads the maximum circuit-breaker rating from Table I1.
- Existing device. It also reads the maximum rating for an existing rewireable fuse or plug-in circuit-breaker.
| Step | Table or clause | What it decides |
|---|---|---|
| Maximum rating | AS/NZS 3000 Table I1 | The largest breaker for the size, method and insulation |
| Existing device | Table I1 and Cl 2.5.2 | The largest fuse or plug-in breaker already in place |
Worked example
A 7/.029 conductor, unenclosed, with V75 insulation. The calculated area is 2.98 mm². The nearest metric size is 2.5 mm². The maximum circuit-breaker rating is 32 A. The maximum existing fuse or plug-in breaker is 20 A.
Limits
- Check the scope of Appendix I. It is written for existing imperial conductors.
- The second rating is for a device already in place. Read Clause 2.5.2 before you plan a new device.
- The two notes under Table I1 set conditions. Read them on the page.
- Do not use the area for conductors in parallel. Read Paragraph I3 and Table I2.
- The tool does not check voltage drop or the condition of the old insulation.
See also: Cable size calculator, What size breaker for 4 mm² cable and Checking an existing circuit.
Pātai
He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.
He aha te mahi a te taputapu taura imperial?
Ka pānui te taputapu i AS/NZS 3000:2018 Table I1. Kōwhiria te rahi imperial, te insulation me te tikanga whakaurunga. Ka whakaatu a AmpSize i te circuit-breaker nui rawa e tā ana te tūtohi mō taua kaikawe. Ka whakaatu anō i te fuse kei reira kē nui rawa, i te circuit-breaker tomo kei reira kē rānei. Ko Appendix I te whakaatu i te whānui.
Ka taea te whakauru i tētahi fuse rewireable ki tētahi ara iahiko tawhito?
Kāo. Ka whakaaro a AmpSize he taputapu kei reira kē anake te pou tuarua o Table I1. Ko Clause 2.5.2 e whakahaere ana i taua kaupapa, ā, ko Note 2 i raro i te tūtohi e tohu ana ki reira. Whakamahia taua reiti ina kei te whakarerekētanga, i te whakatikatanga rānei he fuse e taea ana te whakawaea anō, he circuit-breaker tomo rānei.
Me pēhea te tātai i te metric ōrite?
Ka tatau a AmpSize i te horanga kaikawe mai i te maha o ngā waea me te diameter waea, kātahi ka whakaatu i te rahi metric paerewa tata rawa. Ko taua horanga he tatauranga, ehara i te uara i pānuitia mai i te paerewa. Kāore a AmpSize e whakauru ana i Table I2, te ripanga mō ngā taura honoa ōrite. Pānuitia i te paerewa mō taua keehi.
Ka pā ngā reiti Table I1 ki ia whakaurunga?
Kāo. Ko te Note 1 i raro i a Table I1 e whakatakoto ana i ngā āhuatanga e tika ai ngā reiti. Pānuitia i te whārangi. Kātahi ka tirotiro i te ara, i te whakarōpūtanga me te heke voltage i mua i tō whakawhirinaki ki tētahi uara.
Ngā tauira mahi
Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu
- AS/NZS 3000:2018 Cl 2.5.2Protective devices already installed
- AS/NZS 3000:2018 Paragraph I3Imperial conductors in parallel
- I1Protective device ratings for imperial cables in alterations and repairs
Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi
Ngā tūtohi i arotakehia whakamutunga i te 26 Sept 2026.
Ngā taputapu hononga
- Tātaitai rahi tauraFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Tātaitai heke voltageCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Tātaitai PV stringModules per string, string current and isolator for PV.AS/NZS 5033AS/NZS 4777.2
He whai hua tēnei?
He pātai, he uara rānei e kitea ana he hē? Whakapā mai.