AmpSize

Rapu taura pūoho ahi

Rapua ngā ture taura me te ara iahiko mō ngā pūnaha pūoho ahi.

Reads NZS 4512:2010. Tables checked 26 Sept 2026.

Ngā whakauru

He tauira mahi me ngā whakauru taunoa.

Momo ara iahiko
Ara iahiko kaitirotiro, kaitohu ringa rānei
Ngā ngākau o te uaua
2

Rahi kaikawe iti rawa

0.75mm²

E hiahiatia ana he kaiwhakahaere whiri
Āe
Ōkeroa insulation i runga ake
5MΩ
Reiti ahi
Kāore i whakaritea e tēnei upoko
Clause
402.1

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

Ngā hīkoi tātaitanga

  1. Te clause e pā ana402.1

    NZS 4512:2010 Cl 402.2

  2. Ngā matua i roto i te uaua2

    NZS 4512:2010 Cl 402.1

  3. Rahi kaikawe iti rawaHua0.75mm²

    NZS 4512:2010 Cl 402.1

  4. Kaiwhakahaere whiri e hiahiatia anaĀe

    NZS 4512:2010 Cl 402.1

  5. Ka pā te whiri i raro iho1mm²

    NZS 4512:2010 Cl 402.1

  6. Ārai whakamaherehanga teitei ake5MΩ

    NZS 4512:2010 Cl 402.2

  7. Ine ahiKāore i whakaritea e tēnei upoko

    NZS 4512:2010 Cl 402.2

Mō tēnei tātaitai

How this is calculated

The tool looks up what a fire alarm circuit needs from NZS 4512:2010 Clauses 402.1 and 402.2. It gives the conductor size, the stranding, the insulation resistance and the fire rating.

  1. Circuit. You pick the circuit: detector, alerting device, transmission, staged evacuation, data link or mains supply.
  2. Clause. The tool picks the clause. Cl 402.1 covers detector and alerting device circuits. Cl 402.2 covers the rest.
  3. Cores. You enter the number of cores in the cable. The size rule in Cl 402.1 reads it.
  4. Conductor size. The tool gives the minimum conductor size and says whether it must be stranded.
  5. Insulation resistance. From Cl 402.2 it gives the minimum insulation resistance.
  6. Fire rating. It gives the fire rating, or says that this clause does not set one.
StepTable or clauseWhat it decides
Conductor size and strandingNZS 4512 Cl 402.1The smallest conductor and its construction
Insulation resistanceCl 402.2The minimum test result
Fire ratingCl 402.2The rating, where the clause sets one

Worked example

A detector circuit in 2‑core cable. The minimum conductor size is 0.75 mm². The conductor must be stranded. The insulation resistance must be above 5 MΩ. This clause sets no fire rating.

Limits

  • The tool reads Cl 402.1 and 402.2 only. Check the cable specification and the mechanical protection in Cl 402.1.
  • Clause 402.2(g) is the other size driver. Read it in full.
  • Check the earthing rules for zone circuit wiring in Cl 402.2(i).
  • Check the separation and identification rules in Cl 402.2(k).
  • The tool does not check voltage drop on the circuit.
  • NZS 4512:2021 supersedes the 2010 edition this tool reads.

See also: Fire alarm battery, Detector spacing and the segregation checker.

Pātai

He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.

He rahi taura pēhea e hiahiatia ana e tētahi ara pūoho ahi?

Ka hoatu a NZS 4512:2010 Clause 402.1 i te 0.75 mm² ia kaikawe mō te taura rua-kaikawe, me te 0.5 mm² ia kaikawe ina neke atu i te rua ngā kaikawe o te taura. Ka whakaatu hoki a AmpSize i te paepae whiri 1 mm² o taua clause. Pānuitia Clause 402.1 mō ngā momo taura me te whakamaru e whakaaetia ana e ia.

Ko ēhea ngā ara iahiko pūoho ahi e hiahia ana i te fire-rated cable?

Ka whakaatu a AmpSize i ngā keehi e rua. Ka hoatu a Clause 402.2(m) i te 15 meneti tōtuia ki AS/NZS 3013 Classification WS11 mō tētahi ara iahiko tuku. Ka hoatu a Clause 402.2(r) i te WS51W mō ngā taura whakawaho whiwhi wāhanga. Pānuitia kātoa ngā clause e rua, nā te mea he tikanga kei roto i ia tētahi e kore e tirohia e tēnei taputapu.

Me whai ara iahiko puna motuhake te pūoho ahi?

Āe. Ka tono a Clause 402.2(f) mō tētahi final subcircuit motuhake me tētahi tohu pūmau. Ka tā a AmpSize i te kōrero tohu e hoatu ana e te clause, FIRE ALARM. Pānuihia a Clause 402.2(f) mō te wāhi e tīmata ai te subcircuit, me te wāhi e tika ai te tohu.

He aha te aukati insulation e tūmanako ana?

Ka whakatakoto a Clause 402.2(j) i te paearu ki runga ake i te 5 MΩ, ā, ka whakaatu a AmpSize i tērā tauanga. Ka kawe a Clause 402.2(i) me Clause 402.2(k) i ngā ture whakawhenua me te wehenga mō taua waea ōrite. Pānuitia ēnei e toru i mua i tō rekoata i tētahi hua whakamātautau.

Ka whakamana tēnei taputapu i te whakaurunga e ea ana?

Kāo. Ka pūrongo a AmpSize i ngā tatauranga o NZS 4512:2010 Clauses 402.1 me 402.2 mō te ara iahiko ka kōwhiria e koe. He tohu anake tēnei, ehara i te whakataunga. Ka arotakehia te whakaurunga pūoho ahi ki te paerewa katoa, ā, ki ngā ture waea hoki.

Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu

Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi

Ngā tūtohi i arotakehia whakamutunga i te 26 Sept 2026.