पावर फ़ैक्टर करेक्शन कैलकुलेटर
पावर फ़ैक्टर बढ़ाने के लिए कैपेसिटर kvar खोजें।
Reads AS/NZS 3000:2018.
कोई प्रोजेक्ट आज़माएँ 10
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Correct a factory power factorThe kvar and bank steps to lift a 250 kW load from 0.78 to 0.95.
- Free supply capacity with power factor correctionThe kVA a 400 kVA site gets back when its power factor rises to 0.98.
- Correct a motor boardThe kvar to lift a 75 kW motor load from 0.82 to 0.95.
- Choose the capacitor stepsThe bank in 25 kvar steps for a 300 kVA load.
- Check a bank for resonanceThe bank against the fault level and 20 % harmonic load.
- Correct a single‑phase loadThe kvar for a 15 kW single‑phase load at 0.7.
- Size a capacitor at a motorThe largest capacitor a pump motor can take, and its new line current.
- Correct a small motor at the motorWhy a small motor capacitor stops short of the target power factor.
- Cut the line current of a large motorThe current a capacitor at a large motor takes off its cable and starter.
- Check a motor capacitor for self-excitationThe no-load limit on a capacitor at a small conveyor motor.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- सुधारें
- लोड या बोर्ड
- फ़ेज़
- थ्री-फ़ेज़
- वोल्टेज
- 400 V
- लोड इकाई
- kW
- लोड
- 100
- वर्तमान पावर फ़ैक्टर
- 0.75
- लक्ष्य पावर फ़ैक्टर
- 0.95
- बैंक स्टेप
- 25 kvar
- धारा का हार्मोनिक विरूपण (THDi)
- 0 %
- बैंक पर फ़ॉल्ट स्तर
- 0 MVA
सुधार आवश्यक
55.32kvar
- बैंक इंस्टॉल
- 3 × 25kvar
- बैंक के साथ पावर फ़ैक्टर
- 0.991
- पहले धारा
- 192.45A
- बाद में धारा
- 145.59A
- मुक्त क्षमता
- 32.47kVA
- बैंक कंडक्टर, कम से कम
- 146.14A
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- रियल पावर100kW
- वर्तमान पावर फ़ैक्टर पर रिएक्टिव पावर88.19kvar
- लक्ष्य पावर फ़ैक्टर पर रिएक्टिव पावर32.87kvar
- सुधार आवश्यकपरिणाम55.32kvar
- बैंक स्टेप
3 × 25 kvar
- बैंक के साथ पावर फ़ैक्टर0.99
- पहले की धारा192.45A
- बाद की धारा145.59A
- मुक्त क्षमता32.47kVA
- बैंक की रेटेड धारा108.25A
- बैंक कंडक्टरों की न्यूनतम क्षमता, 135 %146.14A
AS/NZS 3000:2018 Cl 4.15.2.3
इस कैलकुलेटर के बारे में
How this is calculated
The tool finds the capacitor bank that lifts a load to a target power factor. It then gives the current before and after.
- Real power. You enter kW, or kVA with a power factor. The tool finds the real power.
- Reactive power. It finds the reactive power at the present power factor. It does the same at the target.
- Correction required. The difference is the kvar the bank must supply.
- Bank steps. It rounds up to whole steps of the size you enter. It then recalculates the power factor with that bank.
- Currents. It finds the current before and after. The difference is the capacity the bank releases.
- Bank conductors. It sizes the bank conductors at 135 % of the bank rated current. This follows AS/NZS 3000 Cl 4.15.2.3.
AS/NZS 3000 Cl 4.15.2.2 covers switching, and Cl 4.15.3.1 covers discharge.
Worked example
- 100 kW three‑phase load at 400 V, 0.75 to 0.95, 25 kvar steps. The correction required is 55.32 kvar. The bank is 3 × 25 kvar. The power factor with the bank is 0.991. Current falls from 192.45 A to 145.59 A. The released capacity is 32.47 kVA. The bank conductors need at least 146.14 A.
One motor
Set Correct to one motor to size a capacitor fitted at a motor and switched with it. The capacitor must not supply more than the motor's own magnetising kvar. If it does, the motor, still turning after it is switched off, can excite itself from the capacitor and raise its voltage. The tool takes the no-load current as all magnetising and keeps the capacitor to 90 % of the no-load kvar, a rule of practice. It fits the smaller of that and the kvar to reach the target at full load, then gives the line current with it from the motor tool's full load current.
- A 30 kW motor at 0.85 with 17 A no-load current can take 10.6 kvar at most. The 9.7 kvar to reach 0.95 fits, and the line current falls from 56.6 A to 50.64 A.
- An 11 kW motor at 0.8 with 7.5 A no-load current can take 4.68 kvar at most, which lifts it to 0.939 and cuts the line current to 18.79 A. Correct the rest at the board.
- A 55 kW motor at 0.75 with 30 A no-load current can take 18.71 kvar at most, which lifts it to 0.867 and cuts the line current to 101.78 A.
Limits
The tool does not assess harmonics unless you enter the THDi. Switch each step with a device rated for capacitors. The tool does not model resonance with the supply.
See also: Power factor and reactive power, Power factor correction for a 250 kW factory and Three phase power.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
मोटर पर कितना बड़ा कैपेसिटर लगाया जा सकता है?
मोटर के नो-लोड kvar के लगभग 90 % से अधिक नहीं; यह व्यवहार का एक नियम (rule of thumb) है। इससे बड़ा कैपेसिटर स्विच बंद होने के बाद मोटर को सेल्फ़-एक्साइट कर सकता है। टूल में "एक मोटर" चुनें और नो-लोड करंट दर्ज करें।
kvar कैसे निकाला जाता है?
टूल मौजूदा पावर फ़ैक्टर पर और लक्ष्य पर रिएक्टिव पावर निकालता है, दोनों रियल पावर से। अंतर वह kvar है जो बैंक को सप्लाई करना होगा। फिर यह पूरे बैंक स्टेप तक ऊपर राउंड करता है।
करेक्शन के बाद करंट क्यों घटता है?
रियल पावर वही रहती है, पर बैंक साइट पर रिएक्टिव पावर सप्लाई करता है। इसलिए सप्लाई कम अपैरेंट पावर ले जाती है। करंट उसी अनुपात में घटता है, और जो kVA यह मुक्त करता है, वही मुक्त हुई क्षमता है।
मुझे डीट्यून्ड बैंक कब चाहिए?
ड्राइव, रेक्टिफ़ायर और LED ड्राइवर हार्मोनिक करंट खींचते हैं। सादे कैपेसिटर सप्लाई के साथ रेज़ोनेट कर सकते हैं और उन्हें बढ़ा सकते हैं। अंगूठे का नियम: लगभग 10 % THDi से ऊपर सीरीज़ रिएक्टर वाला डीट्यून्ड बैंक लगाएँ। 20 % से ऊपर हार्मोनिक अध्ययन करवाएँ।
रेज़ोनेंस ऑर्डर का क्या मतलब है?
कैपेसिटर बैंक और सप्लाई मिलकर एक ट्यून्ड सर्किट बनाते हैं। ऑर्डर फ़ॉल्ट लेवल और बैंक kvar के अनुपात का वर्गमूल है। 5वें, 7वें, 11वें या 13वें हार्मोनिक के पास टूल चेतावनी देता है।
हल किए गए उदाहरण
बैकग्राउंड
वे Clauses और Tables जो यह टूल पढ़ता है
संबंधित टूल
क्या यह उपयोगी था?
कोई सवाल, या कोई मान गलत लगता है? हमसे संपर्क करें।