केबल लॉस रनिंग कॉस्ट
एक केबल आकार ऊपर करने से ऊर्जा, लागत और CO2 में क्या बचता है।
Reads AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3008.1.1:2017 (AU). Tables checked 24 Sept 2026.
कोई प्रोजेक्ट आज़माएँ 4
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- What a size up saves on a feederThe yearly saving of 120 over 95 mm² on a 200 A feeder that never stops.
- Running cost of a heat pump circuitThe energy a 6 mm² heat pump circuit loses a year, against 10 mm².
- Payback of a larger submainHow fast 35 mm² pays back over 25 mm² on a busy 80 m submain.
- CO2 saved by a larger aluminium cableThe kWh and CO2 a year of 120 over 95 mm² aluminium at 150 A.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- क्षेत्राधिकार
- NZ · AS/NZS 3008.1.2
- फ़ेज़
- थ्री-फ़ेज़
- चालू धारा, RMS
- 100 A
- वर्ष के चालू घंटे
- 4,000 h
- रूट की लंबाई
- 60 m
- कंडक्टर
- तांबा
- इंसुलेशन
- XLPE 90 °C
- जो आकार पास होता है
- 35 mm²
- तुलना के लिए आकार तक
- 50 mm²
- ऊर्जा टैरिफ
- 0.3 $/kWh
- उत्सर्जन गुणांक
- 0.1 kg/kWh
- बड़े आकार का अतिरिक्त खर्च
- 800 $
प्रति वर्ष बचाई गई लागत
$375.84
- प्रति वर्ष बचाई गई ऊर्जा
- 1,252.8kWh
- प्रति वर्ष बचाया गया CO2
- 125.3kg
- अतिरिक्त लागत की वापसी अवधि
- 2.1years
- एक साल में खोई ऊर्जा, 35 mm²
- 4,809.6kWh
- एक साल में खोई ऊर्जा, 50 mm²
- 3,556.8kWh
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- 90 °C पर 35 mm² a.c. प्रतिरोध0.67Ω/km
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- 35 mm² हानि: 3 × 100² × R × 60 m1,202.4W
- 35 mm² में प्रति वर्ष ऊर्जा हानि, 4000 h पर4,809.6kWh
- 35 mm² की लागत प्रति वर्ष, $0.30 प्रति kWh पर$1,442.88
- 90 °C पर 50 mm² a.c. प्रतिरोध0.49Ω/km
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- 50 mm² हानि: 3 × 100² × R × 60 m889.2W
- 50 mm² में प्रति वर्ष ऊर्जा हानि, 4000 h पर3,556.8kWh
- 50 mm² की लागत प्रति वर्ष, $0.30 प्रति kWh पर$1,067.04
- प्रति वर्ष बचाई गई ऊर्जा1,252.8kWh
- प्रति वर्ष बचाई गई लागतपरिणाम$375.84
- प्रति वर्ष बचाया गया CO2125.3 kg
- अतिरिक्त लागत की वापसी अवधि2.1 वर्ष
इस कैलकुलेटर के बारे में
How this is calculated
Every cable turns some of the energy it carries into heat. The loss is the current squared times the resistance of the conductors that carry it. A larger cable has less resistance, so it wastes less. This tool puts a yearly figure on that waste for two sizes, so you can see what the size up saves.
The tool reads the a.c. resistance of each size from AS/NZS 3008.1, in ohms per kilometre, for the conductor metal and insulation you pick. It reads the table at the conductor's full-load temperature. On a single‑phase circuit the current flows out and back, so two conductors carry the loss. On a balanced three‑phase circuit the neutral carries no current, so three do.
The loss in watts is the number of loaded conductors times the current squared times the resistance times the length. The tool multiplies it by the running hours a year to get kWh. The tariff turns kWh into dollars, and the emission factor turns kWh into kilograms of CO2. Both are figures you set from your own contract and grid.
The difference between the two sizes is the saving a year. If you enter what the size up costs over the smaller cable, installed, the tool divides that by the saving to give the payback in years.
Enter the rms current over the running hours, not the mean or the peak. Loss grows with the square of the current, so a cable that runs near full load for long hours gains the most from a size up.
| Step | Table or clause | What it decides |
|---|---|---|
| Resistance of each size | Tables 34 and 35 | The ohms per kilometre at the full-load temperature |
| Loss | n × I² × R × L | The watts each size wastes |
| Energy a year | Loss × running hours | The kWh each size wastes |
| Cost and CO2 | Tariff and emission factor | Dollars and kilograms a year, from your figures |
| Payback | Extra cost ÷ saving a year | The years for the size up to pay for itself |
Worked examples
- A 100 A feeder of 60 m in 35 or 50 mm² XLPE saves $375.84 a year with the size up. That is 1,252.8 kWh a year, and the extra $800 pays back in 2.1 years.
- A 200 A feeder of 120 m that never stops, 95 or 120 mm² saves $1,892.16 a year. That is 6,307.2 kWh a year, and the extra cost pays back in 1.3 years.
- A 25 A heat pump circuit of 40 m in 6 or 10 mm² PVC saves $68.40 a year. That is 228 kWh a year, and the extra cost pays back in 2.2 years.
- A 150 A aluminium feeder of 100 m, 95 or 120 mm² saves $870.75 a year. That is 2,902.5 kWh a year, and the extra cost pays back in 1.7 years.
Limits
The resistance is the table figure at the full-load temperature. A cable at part load runs cooler, so the real loss is a little lower than the tool shows.
The tool does not size the cable. Size it first for current, voltage drop and fault with the cable size tool, then compare the size that passes with the next size up. It does not count the time value of money, a tariff that changes through the day, or harmonic currents, which add loss.
See also: Cable size, Voltage drop and Three phase power.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
केबल में नष्ट हुई ऊर्जा की गणना कैसे करें?
लोड वाले कंडक्टरों की संख्या को करंट के वर्ग, प्रति मीटर रेज़िस्टेंस और लंबाई से गुणा करें। यह वाट में लॉस है। इसे चलने के घंटों से गुणा करें और 1000 से भाग दें, तो सालाना kWh आता है। टूल AS/NZS 3008.1 से रेज़िस्टेंस पढ़ता है।
क्या बड़ी केबल से पैसे बचते हैं?
बड़ी केबल का रेज़िस्टेंस कम होता है, इसलिए उसमें कम एनर्जी नष्ट होती है। लंबे रन पर जो कई घंटों तक ज़्यादा करंट ले जाता है, वहाँ बचत कुछ सालों में अतिरिक्त केबल की कीमत वसूल सकती है। छोटे या कम इस्तेमाल वाले रन पर यह शायद ही होता है।
लॉस ऊपरी सीमा क्यों है?
टूल केबल के फ़ुल-लोड तापमान पर रेज़िस्टेंस पढ़ता है, PVC के लिए 75 °C और XLPE के लिए 90 °C। पार्ट लोड पर केबल ठंडा चलता है और उसका रेज़िस्टेंस कम होता है, इसलिए असली लॉस थोड़ा कम है। बचत भी कम है, और पेबैक एक निचली सीमा है।
मुझे कौन सा टैरिफ़ और एमिशन फ़ैक्टर इस्तेमाल करना चाहिए?
अपने सप्लाई कॉन्ट्रैक्ट की एनर्जी रेट इस्तेमाल करें, जिसमें घंटों से मेल खाने वाला कोई टाइम-ऑफ़-यूज़ विभाजन भी शामिल हो। CO2 के लिए अपने ग्रिड का प्रकाशित एमिशन फ़ैक्टर इस्तेमाल करें। ये दोनों आपके सेट किए अनुमान हैं। AmpSize इनमें से कोई नहीं रखता।
क्या यह केबल आकार जाँच की जगह लेता है?
नहीं। पहले केबल आकार टूल से करंट, वोल्टेज ड्रॉप और फ़ॉल्ट के लिए केबल का आकार तय करें। फिर जो आकार पास होता है, उसकी तुलना यहाँ के अगले बड़े आकार से करें।
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 24 Sept 2026 को जाँची गईं।
संबंधित टूल
- केबल आकार कैलकुलेटरFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- वोल्टेज ड्रॉप कैलकुलेटरCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- केबल फ़ॉल्ट रेटिंग कैलकुलेटरCheck that a conductor can withstand the fault current.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
क्या यह उपयोगी था?