How many 2.5 mm² cables fit in 20 mm conduit?

Conduit fill calculator

Worked to AS/NZS 3000:2018. Tables checked 19 Sept 2026.

Conduit fill

34.56%

Pinapayagang fill
40%
Lawak ng cable
61.07mm²
Internal area ng conduit
176.71mm²
Buksan ang calculator gamit ang mga input na ito

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

A drawn result card from the Conduit Fill tool: conduit fill 34.56 %; checked.

Six single‑core 2.5 mm² cables fit in a 20 mm conduit, at a fill of 34.56 %. AS/NZS 3000:2018 Appendix C Paragraph C6.2 sets the space factor the tool uses: 40 % for this number of cables.

The case

The conduit's internal area is 176.71 mm². The six cables take 61.07 mm² of it. A seventh cable takes the fill to 40.32 %, over the limit, and the tool then recommends 25 mm conduit.

Before you install

This count comes from the fill method. Appendix C Tables C10 to C12 also give a maximum-count guide, which can differ. Use the method your design states.

The fill method uses each cable's overall diameter. A multicore cable, or a cable with a thicker sheath, takes more room than its conductor size suggests. Enter the cables you will pull, and leave room for the draw-in.

See also: AS/NZS 3000 Appendix C conduit space factor and Conduit fill and installation methods.

Subukan gamit ang mga input na ito

Mga cable
[{"size":2.5,"cores":"single","count":6}]
Laki ng conduit
20 mm
Bansa
New Zealand
Buksan ang calculator gamit ang mga input na ito

Ano ang susunod

Ang mga ideyang nasa likod nito

Higit pang worked example

Design aid ang AmpSize. I-verify ang mga resulta laban sa kasalukuyang standard.

Nakatulong ba ito?

May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.