حاسبة إجمالي هبوط الجهد
أضف هبوط الجهد في التغذية الرئيسية والمغذّي الفرعي والدائرة الفرعية النهائية، وقارن المجموع بالحد 5 %.
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 1 Oct 2026.
جرّب مشروعاً 4
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Check the total voltage drop to a shedThe mains, the shed submain and a final subcircuit added against 5 %.
- Find the drop left for a new circuitWhat 25 m of mains and a 40 m submain leave for a final subcircuit.
- Add a three phase submain to a finalThree phase mains and submain with a single phase final, added by percent.
- Use the 7 % substation limitA factory fed from its own transformer, checked against 7 %.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- نقطة التغذية
- تغذية الشبكة (حد 5 %)
- المعيار
- NZ · AS/NZS 3008.1.2
- معامل القدرة
- 0.9
- أجزاء المسار، من نقطة التغذية
- 3 صفوف
إجمالي هبوط الجهد
4.25%
- حد هبوط الجهد
- 5%
- الخطوط الرئيسية والفرعية الرئيسية
- 1.98%
- المتبقي لدائرة فرعية نهائية
- 3.02%
- المتبقي عند نقطة الاستخدام
- 0.75%
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- الجزء 1التغذية الرئيسية للمستهلك
- الجزء 1 mV/A·m2.6mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- هبوط جهد الجزء 12.6V
- هبوط جهد الجزء 1، نسبة مئوية من 230 V1.13%
AS/NZS 3000:2018 App C Para C4.1
- المجموع الجاري بعد الجزء 11.13%
AS/NZS 3000:2018 App C Para C4.1
- الجزء 2الخط الفرعي الرئيسي
- الجزء 2 mV/A·m4.09mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- هبوط جهد الجزء 21.96V
- هبوط جهد الجزء 2، نسبة مئوية من 230 V0.85%
AS/NZS 3000:2018 App C Para C4.1
- المجموع الجاري بعد الجزء 21.98%
AS/NZS 3000:2018 App C Para C4.1
- الجزء 3الدائرة الفرعية الأخيرة
- الجزء 3 mV/A·m16.31mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- هبوط جهد الجزء 35.22V
- هبوط جهد الجزء 3، نسبة مئوية من 230 V2.27%
AS/NZS 3000:2018 App C Para C4.1
- المجموع الجاري بعد الجزء 34.25%
AS/NZS 3000:2018 App C Para C4.1
- حد هبوط الجهد5%
AS/NZS 3000:2018 Cl 3.6.2
- إجمالي هبوط الجهدالنتيجة4.25%
AS/NZS 3000:2018 Cl 3.6.2
- الخطوط الرئيسية والفرعية الرئيسية1.98%
- المتبقي لدائرة فرعية نهائية3.02%
AS/NZS 3000:2018 Cl 3.6.2
- المتبقي عند نقطة الاستخدام0.75%
حول هذه الحاسبة
How this is calculated
AS/NZS 3000 limits the voltage drop from the point of supply to any point in the installation. It is one limit for the whole run, not one per circuit. So the drop in the consumer mains, every submain and the final subcircuit must add up to no more than the limit. This tool adds them.
You enter each part of the run in order from the point of supply: the consumer mains, up to three submains and the final subcircuit. For each part you give the phases, the current, the route length and the cable. The tool works each part with the same calculation as the voltage drop tool. It reads the cable's resistance and reactance from AS/NZS 3008.1, finds the mV/A·m at the power factor, and gives the drop in volts.
Each drop is then taken as a percent of that part's own circuit voltage: 230 V for single phase and 400 V for three phase. Appendix C of AS/NZS 3000 adds the percents directly, so a three‑phase submain adds to a single‑phase final subcircuit with no conversion. The running total is the drop at the end of each part.
The limit is 5 % of the nominal voltage. Where the point of supply is the low voltage terminals of a substation on the premises, which supplies only this installation, it is 7 %. The clause sets no split between the parts. The tool shows what the mains and submains take, and what that leaves for a final subcircuit from the last board.
| Step | Table or clause | What it decides |
|---|---|---|
| Resistance and reactance of each part | AS/NZS 3008.1 Tables 34 and 35 | The impedance of the cable |
| Drop of each part | AS/NZS 3008.1 Cl 4.5 | The mV/A·m and the drop in volts |
| Percent of each part | AS/NZS 3000 App C Para C4.1 | The drop as a percent of its circuit voltage, added part by part |
| The limit | AS/NZS 3000 Cl 3.6.2 | The most the total may be from the point of supply |
| A substation on the premises | AS/NZS 3000 Cl 3.6.2 Exception 3 | The higher limit where it applies |
| A load spread along a final subcircuit | AS/NZS 3000 Cl 3.6.2 Exception 1 | The current you may use for that part |
Worked examples
- A house: mains, a garage submain and a socket‑outlet circuit. The total voltage drop is 4.25 %. The mains and submain take 1.98 %, which leaves 3.02 % for a final subcircuit.
- A shed 30 m from the house. The total voltage drop is 4.83 %, inside the 5 % limit but close to it. The upstream parts take 3.13 %, which leaves 1.87 % for a final subcircuit.
- A factory on its own substation. The total voltage drop is 6.27 % against the 7 % limit. The mains and submain take 4.38 %, which leaves 2.62 % for a final subcircuit.
- A farm workshop 60 m from the house. The total voltage drop is 10.82 %, so the run fails. The mains and submain take 8.55 % on their own, which leaves −3.55 % for a final subcircuit. A larger submain is the fix.
Limits
The tool works a.c. runs at 230 V and 400 V nominal. It does not check extra-low voltage circuits, which Cl 3.6.2 leaves out, or a stand-alone system, which Exception 4 judges on the utilisation voltage. Single‑core parts use the highest reactance the table gives for the formation. Use the voltage drop tool for one run with a known formation or an unbalanced neutral.
Motor starting and other short transient drops are not part of the limit. Check those against the equipment.
See also: Voltage drop, The 5 % voltage drop limit from supply to load and Total voltage drop: mains, submain and final.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
هل حد هبوط الجهد البالغ 5 % لكل دائرة أم للتركيب بأكمله؟
التركيب بأكمله. يحدّ AS/NZS 3000 Cl 3.6.2 الهبوط من نقطة التغذية إلى أي نقطة. تتشارك التغذية الرئيسية للمستهلك والمغذّيات الفرعية والدائرة الفرعية النهائية حداً واحداً قدره 5 %، لذلك تجمعها هذه الأداة.
هل يوجد تقسيم بنسبة 2 % و3 % بين التغذية الرئيسية والدوائر الفرعية النهائية؟
ليس في AS/NZS 3000. يضع Cl 3.6.2 حدًا واحدًا دون تقسيم. ويخطط المصممون غالبًا لتقسيم، لكن البند يشترط فقط بقاء الإجمالي ضمن الحد. تعرض الأداة ما تستهلكه التغذية الرئيسية والمغذّيات الفرعية وما يتبقى.
كيف أضيف مغذّيًا فرعيًا ثلاثي الأطوار إلى دائرة فرعية نهائية أحادية الطور؟
بالنسبة المئوية. يُحسب كل جزء كنسبة مئوية من جهد دائرته، أي 400 V للدائرة ثلاثية الأطوار و230 V للدائرة أحادية الطور. يجمع الملحق C في AS/NZS 3000 هذه النسب المئوية مباشرة.
متى يكون الحد 7 %؟
عندما تكون نقطة التغذية هي أطراف الجهد المنخفض لمحطة فرعية في الموقع نفسه، تغذي هذه التركيبة وحدها. اختر محطة فرعية خاصة وتستخدم الأداة 7 %.
أي تيار يجب أن أستخدمه لكل جزء؟
الطلب الأقصى لكل جزء، أو حمله المتصل، أو القيمة الاسمية لجهاز الحماية، أيّها تعرفه. ويجوز للدائرة الفرعية النهائية التي يتوزع حملها على امتدادها أن تستخدم نصف القيمة الاسمية للجهاز.
أمثلة محلولة
الخلفية
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 3000:2018 App C Para C4.1Adding voltage drop by percent
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit from the point of supply, and how the parts of an installation add
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2025 Table 4.1(A), 4.1(B), 4.5(A), 4.5(B)Reactance at 50 Hz and a.c. resistance at 50 Hz
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 1 Oct 2026.
أدوات ذات صلة
- حاسبة مقاس الكابلFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- حاسبة هبوط الجهدCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- حاسبة أقصى طول للدائرةLongest run that voltage drop and the fault loop allow.AS/NZS 3000AS/NZS 3008.1.2