جدول الاختبار للوحة التوزيع
اطبع ورقة اختبار اللوحة مع الحد لكل اختبار.
Reads Electricity (Safety) Regulations 2010, AS/NZS 3000:2018 and AS/NZS 3017:2022. Tables checked 1 Oct 2026.
جرّب مشروعاً 4
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Print the test sheet for a house boardSix circuits with their tests in order and the pass limits.
- Test a workshop board with three‑phase socketsAdds the phase sequence test to the three‑phase socket circuit.
- Make an Australian test sheetA house board where each RCD must operate, with no trip time.
- Mark a circuit for the reduced test voltageA data rack circuit tested at the lower insulation voltage.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- الدولة
- نيوزيلندا
- اسم اللوحة
- غير مذكور
- الدوائر الفرعية الأخيرة
- 6 صفوف
الدوائر في الورقة
6
- الاختبارات في التسلسل
- 7
- التأريض والربط الرئيسي، بحد أقصى
- 0.5Ω
- دوائر بلا صف في Table 8.1
- 0
- ترتيب الاختبارات
- De-energized, earth continuity, insulation, polarity, phase sequence, Zs, RCD
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- اختبار 1اختبار انعدام الطاقة
AS/NZS 3017:2022 Cl 4.3
- اختبار 2استمرارية التأريض
AS/NZS 3017:2022 Cl 4.4
- اختبار 3مقاومة العزل
AS/NZS 3017:2022 Cl 4.5
- اختبار 4القطبية وتوصيلات الدائرة الصحيحة
AS/NZS 3017:2022 Cl 4.6
- اختبار 4تسلسل الأطوار للمقابس متعددة الأطوار
AS/NZS 3017:2022 Cl 4.7
- اختبار 5معاوقة حلقة عطل التأريض
AS/NZS 3017:2022 Cl 4.8
- اختبار 6تشغيل RCD
AS/NZS 3017:2022 Cl 4.9
- اختبار 7أعد الاختبار الفاشل والاختبارات السابقة له التي قد يكون أثّر فيها
AS/NZS 3017:2022 Cl 4.2.2
- مقاومة العزل للدائرة 1، بحد أدنى1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- استمرارية التأريض Re للدائرة 1، بحد أقصى1Ω
AS/NZS 3000:2018 Table 8.2
- معاوقة حلقة عطل التأريض للدائرة 1، بحد أقصى3.1Ω
AS/NZS 3000:2018 Table 8.1
- Rphe للدائرة 1، بحد أقصى2Ω
AS/NZS 3000:2018 Table 8.2
- زمن فصل RCD للدائرة 1 عند 30 mA، بحد أقصى300ms
Electricity (Safety) Regulations 2010 reg 24
- مقاومة العزل للدائرة 2، بحد أدنى1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- استمرارية التأريض Re للدائرة 2، بحد أقصى0.5Ω
AS/NZS 3000:2018 Table 8.2
- معاوقة حلقة عطل التأريض للدائرة 2، بحد أقصى1.5Ω
AS/NZS 3000:2018 Table 8.1
- Rphe للدائرة 2، بحد أقصى1Ω
AS/NZS 3000:2018 Table 8.2
- زمن فصل RCD للدائرة 2 عند 30 mA، بحد أقصى300ms
Electricity (Safety) Regulations 2010 reg 24
- مقاومة العزل للدائرة 3، بحد أدنى1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- استمرارية التأريض Re للدائرة 3، بحد أقصى0.5Ω
AS/NZS 3000:2018 Table 8.2
- معاوقة حلقة عطل التأريض للدائرة 3، بحد أقصى1.5Ω
AS/NZS 3000:2018 Table 8.1
- Rphe للدائرة 3، بحد أقصى1Ω
AS/NZS 3000:2018 Table 8.2
- زمن فصل RCD للدائرة 3 عند 30 mA، بحد أقصى300ms
Electricity (Safety) Regulations 2010 reg 24
- مقاومة العزل للدائرة 4، بحد أدنى1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- استمرارية التأريض Re للدائرة 4، بحد أقصى0.5Ω
AS/NZS 3000:2018 Table 8.2
- معاوقة حلقة عطل التأريض للدائرة 4، بحد أقصى1.5Ω
AS/NZS 3000:2018 Table 8.1
- Rphe للدائرة 4، بحد أقصى1Ω
AS/NZS 3000:2018 Table 8.2
- زمن فصل RCD للدائرة 4 عند 30 mA، بحد أقصى300ms
Electricity (Safety) Regulations 2010 reg 24
- مقاومة العزل للدائرة 5، بحد أدنى1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- استمرارية التأريض Re للدائرة 5، بحد أقصى0.5Ω
AS/NZS 3000:2018 Cl 8.3.5
- معاوقة حلقة عطل التأريض للدائرة 5، بحد أقصى1Ω
AS/NZS 3000:2018 Table 8.1
- مقاومة العزل للدائرة 6، بحد أدنى1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- استمرارية التأريض Re للدائرة 6، بحد أقصى0.5Ω
AS/NZS 3000:2018 Table 8.2
- معاوقة حلقة عطل التأريض للدائرة 6، بحد أقصى1.5Ω
AS/NZS 3000:2018 Table 8.1
- Rphe للدائرة 6، بحد أقصى1Ω
AS/NZS 3000:2018 Table 8.2
- التأريض والربط الرئيسي، بحد أقصى0.5Ω
AS/NZS 3000:2018 Cl 8.3.5
حول هذه الحاسبة
How this is calculated
You list the final subcircuits of one board: what each supplies, its protective device and rating, its active conductor, single or three phase, and its RCD. The tool turns the list into the sheet you test from.
The tests follow the preferred order of the verification standard's sequence figure. First prove the circuit de-energized. Then test earth continuity, insulation resistance, and polarity with the correct connection of each circuit. A circuit with three‑phase socket‑outlets also takes the phase sequence test, so every outlet of a type turns a motor the same way. Then the earth fault-loop impedance, and last the operation of each RCD. If a test fails, fix the fault and repeat that test and any earlier one it may have upset.
Each circuit carries the limits its readings are judged against. They come from the wiring rules, through the same code the test results tool uses: the insulation resistance and its test voltage, the earth continuity Re and the Rphe from the subcircuit resistance table, and the earth fault-loop impedance from the loop impedance table, at a 0.4 s disconnection time. Where the resistance table has no row, Re falls back to the main earth figure, and the tool says so.
An RCD must operate at about its rated residual current and disconnect the circuit. In New Zealand the sheet also holds it to the regulations' trip time at that current. In Australia the sheet states no time, since the verification standard prints none.
| Step | Table or clause | What it decides |
|---|---|---|
| Order of tests | AS/NZS 3017 Figure 4.1 | The sequence on the sheet |
| Repeat after a fix | AS/NZS 3017 Cl 4.2.2 | Which tests to run again |
| Insulation resistance | Cl 8.3.6 | The least resistance and the test voltage |
| Earth continuity and Rphe | Table 8.2 | The most each conductor may read |
| Earth fault-loop impedance | Table 8.1 | The most Zs may read |
| Phase sequence | AS/NZS 3017 Cl 4.7 | Which circuits take it |
| RCD | AS/NZS 3017 Cl 4.9.4 and reg 24 | What the RCD must do, and the NZ trip time |
Worked examples
- A New Zealand house board. The sheet holds 6 circuits. The 10 A lighting circuit reads Zs at most 3.1 Ω, and each 30 mA RCD trips within 300 ms.
- An Australian house board. The same 6 circuits, and each RCD must operate at about 30 mA; the sheet states no trip time.
- A workshop board. The sheet holds 4 circuits. The three‑phase socket circuit takes the phase sequence test, and the D20 compressor reads Zs at most 0.9 Ω.
Limits
The sheet sets out the tests and the limits; it does not judge a reading. Put a reading into the test results tool to check it, or use it for a fuse circuit at a 5 s disconnection time. The sheet covers final subcircuits: test the main earthing conductor and the bonding against their own limit, shown on the sheet. It does not replace the visual inspection the standard asks for first.
See also: The order of verification tests, A test sheet for a house board and Test Results.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
بأي ترتيب أختبر التركيب الجديد؟
يحدد AS/NZS 3017 Figure 4.1 ترتيباً مفضلاً: تحقّق من أنه غير مُغذّى، ثم استمرارية التأريض، ومقاومة العزل، والقطبية والتوصيلات، ومعاوقة حلقة عطل التأريض، وأخيراً أجهزة RCD. قد يُفسد عطلٌ يُكتشف لاحقاً اختباراً سابقاً، لذلك كرّر تلك الاختبارات بعد الإصلاح.
من أين تأتي حدود المطابقة؟
من AS/NZS 3000: مقاومة العزل وفق Cl 8.3.6، واستمرارية التأريض Re وRphe وفق Table 8.2، ومعاوقة حلقة عطل التأريض وفق Table 8.1. هي الحدود نفسها التي تتحقق منها أداة نتائج الاختبار عند كل قراءة.
ما زمن الفصل الذي يحتاجه RCD؟
في نيوزيلندا، تُخضع ورقة الاختبار جهاز RCD بقيمة 30 mA لحد Electricity (Safety) Regulations عند تيار التسريب الاسمي له. يشترط AS/NZS 3017 أن يعمل كل RCD عند نحو تياره الاسمي ويفصل الدائرة، ولا يطبع زمناً، لذلك لا تذكر ورقة أسترالية أي زمن.
أي الدوائر تحتاج إلى اختبار تسلسل الأطوار؟
دائرة بمقابس متعددة الأطوار، بحيث يكون لكل مقبس من النوع نفسه ترتيب الطور نفسه (AS/NZS 3017 Cl 4.7). ضع علامة في مربع المقابس ثلاثية الأطوار على تلك الدائرة.
هل يمكنني طباعة الورقة؟
نعم. يطبع الملف PDF كل دائرة مع حدودها ومربعات فارغة لقراءات العزل وRe وZs والقطبية وRCD، لتعبئتها في الموقع.
أمثلة محلولة
- A circuit chart for a house board with solarThe circuit chart and labels for a six-circuit house board with a solar inverter: ways, devices, RCDs, MAIN SWITCH, MAIN SWITCH SOLAR and a shared neutral.
- A test sheet for a house boardA test sheet for a six-circuit New Zealand house board, with the tests in the AS/NZS 3017 order and the limit for each reading, then the Australian sheet.
الخلفية
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 3000:2018 Cl 8.3.5Earth continuity test
- AS/NZS 3000:2018 Cl 8.3.6Insulation resistance test
- AS/NZS 3017:2022 Cl 4.2.2Order of tests
- AS/NZS 3017:2022 Cl 4.3Test for de-energized
- AS/NZS 3017:2022 Cl 4.4Earth continuity test method
- AS/NZS 3017:2022 Cl 4.5Insulation resistance test method
- AS/NZS 3017:2022 Cl 4.6Polarity and circuit connections test method
- AS/NZS 3017:2022 Cl 4.7Phase sequence test method
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 1 Oct 2026.
أدوات ذات صلة
- المسار التنظيمي للشهادات الكهربائيةFind the paperwork for a job in NZ or Australia.Electricity (Safety) Regulations 2010
- مدقق نتائج الاختبارCheck measured test results against Section 8 limits.AS/NZS 3000AS/NZS 3017Electricity (Safety) Regulations 2010
- جدول دوائر لوحة التوزيعMake a board circuit chart and the labels it needs.AS/NZS 3000