مدقق الضوء المزعج
تحقّق من الإضاءة الخارجية عند نافذة على حد الملكية وفق AS/NZS 4282.
Reads AS/NZS 4282:2023. Tables checked 1 Oct 2026.
جرّب مشروعاً 7
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Check a car-park floodlight at a boundaryWhether a 20 000 lm floodlight 15 m from an upstairs window passes after the curfew.
- Check a bollard path at a boundaryWhether a 500 lm bollard 5 m from a neighbour’s window passes in zone A3.
- Check a tennis court floodlightWhether a 40 000 lm floodlight 20 m from a window passes.
- Check a security light on a houseWhether a 2000 lm wall light 8 m from a neighbour passes.
- Check a light in a rural zoneThe limits for a 5000 lm floodlight 30 m from the boundary in dark zone A1.
- Check a loading dock before the curfewA dock floodlight against the pre-curfew limit.
- Check the upward light of an uplightThe upward light ratio of a façade uplight.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- المنطقة البيئية
- A2، Low district brightness
- أثناء حظر التجول
- لا
- المسافة إلى الحد
- 10 m
- ارتفاع مركز النافذة
- 1.5 m
- تركيبات الإضاءة
- صف واحد
الإضاءة الرأسية عند النافذة
47.67lx
- حد الإضاءة الرأسية
- 5lx
- أعلى شدة باتجاه النافذة
- 3,143cd
- حد الشدة لكل وحدة إضاءة
- 7,500cd
- نسبة الضوء العلوي
- 0.020
- حد نسبة الضوء العلوي
- 0.01
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- المنطقة البيئيةA2, Low district brightness
AS/NZS 4282:2023 Table 3.1
- الفترةخارج ساعة الإغلاق
AS/NZS 4282:2023 Cl 3.2.4
- معامل الصيانة1
AS/NZS 4282:2023 Cl 3.2.2
- مركز النافذة10 m out, 1.5 m up
AS/NZS 4282:2023 Cl 3.3.1.3
- شدة الذروة I04,775cd
- الزاوية عن محور الشعاع35.8°
- الشدة باتجاه النافذة3,143cd
AS/NZS 4282:2023 Cl 3.3.1.3
- Ev عند النافذة، 2 × 23.836 lx47.67lx
AS/NZS 4282:2023 Cl 3.3.1.3
- الإضاءة الرأسية عند النافذةالنتيجة47.67lx
AS/NZS 4282:2023 Cl 3.3.1.3
- حد الإضاءة الرأسية5lx
AS/NZS 4282:2023 Table 3.2
- أعلى شدة باتجاه النافذة3,143cd
AS/NZS 4282:2023 Cl 3.3.1.3
- حد الشدة لكل وحدة إضاءة، المستوى 17,500cd
AS/NZS 4282:2023 Table 3.3
- لومن فوق الأفق400lm
AS/NZS 4282:2023 Cl 3.3.1.8.2
- إجمالي اللومن20,000lm
AS/NZS 4282:2023 Cl 3.3.1.8.2
- نسبة الضوء العلوي0.02
AS/NZS 4282:2023 Cl 3.3.1.8.2
- حد نسبة الضوء العلوي0.01
AS/NZS 4282:2023 Table 3.2
حول هذه الحاسبة
How this is calculated
The tool estimates the light a floodlight or bollard puts on a neighbour window. It checks the result against AS/NZS 4282:2023.
- Zone and period. You pick the environmental zone, A0 to A4, and whether the curfew applies. Table 3.1 defines the zones. Cl 3.2.4 sets the curfew period.
- Intensity toward the window. The tool takes the beam angle and the tilt of each luminaire. It finds the angle off the beam axis. It then reads the intensity at that angle from a simple lobe (Cl 3.3.1.3).
- Vertical illuminance. For each luminaire, it divides the intensity by the squared distance to the window. It applies the maintenance factor of Cl 3.2.2 and adds the luminaires.
- Illuminance limit. Table 3.2 gives the vertical illuminance limit for the zone and period.
- Intensity limit. Table 3.3 gives the intensity limit for one luminaire. The tool uses the Level 1 value.
- Upward light ratio. Cl 3.3.1.8.2 gives the share of lumens above the horizontal. Table 3.2 gives the limit.
| Step | Table or clause | What it decides |
|---|---|---|
| Zone | AS/NZS 4282:2023 Table 3.1 | The environment class of the site |
| Illuminance at the window | Cl 3.3.1.3 | The vertical light on the window |
| Illuminance limit | Table 3.2 | The most light allowed at the window |
| Intensity limit | Table 3.3 | The most intensity from one luminaire |
| Upward light ratio | Cl 3.3.1.8.2 | The share of light sent above the horizontal |
Worked example
- Two floodlights at a window 10 m away. Each unit gives 10,000 lm, mounted at 6 m and tilted 30°. Zone A2 applies outside the curfew. The tool gives 47.67 lx at the window against a limit of 5 lx, so it fails. The intensity of 3,143 cd is under the limit of 7,500 cd. The upward light ratio is 0.020 against 0.01, so that check also fails.
Limits
The result is a point-source estimate. A site measurement rules. The tool uses a lobe in place of the photometric file from the maker. Use the maker intensity table when you have it. Only direct light counts. Reflected light and obstructions are not modelled.
Level 1 intensity applies. Level 2 needs a precedent from existing lighting (Cl 3.2.5). Tilting a luminaire can raise the upward fraction, so type the value at the aiming angle.
See also: Obtrusive light and the 4282 zones, Car park floodlight obtrusive light at a boundary and the lighting lumen tool.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
أي منطقة بيئية تنطبق على موقعي؟
تتبع المنطقة التقسيم التخطيطي للمنطقة، بما في ذلك التقسيم المستقبلي. معظم الضواحي من نوع A3، والمناطق الريفية المتفرقة وشبه الريفية من نوع A2، ومراكز المدن والمناطق الصناعية من نوع A4. اسأل المجلس المحلي حيث يكون ذلك غير واضح.
ما هو وقت الإطفاء؟
فترة الحظر الليلي هي الفترة المتأخرة من الليل التي تنطبق فيها الحدود الأدنى. ما لم تحدد البلدية أو التصريح ساعات أخرى، اعتبرها من 11 مساءً إلى 6 صباحًا. فعّل فترة الحظر للتحقق من الإضاءة التي تبقى مضاءة خلالها.
لماذا تسمّي الأداة إجابتها تقديرًا؟
تعامل الأداة كل صف من وحدات الإضاءة كنقطة واحدة بشعاع منتظم. للكشاف الحقيقي جدول شدة خاص به، والموقع فيه جدران وأشجار وانعكاسات. استخدم حساباً فوتومترياً أو قياساً في الموقع للحصول على الإجابة النهائية.
ما النسبة الصاعدة لوحدة الإضاءة؟
نسبة لومنه التي تخرج فوق الأفق عند زاوية التوجيه. وحدة الإضاءة القاطعة كلياً والمركّبة أفقياً قيمتها 0. وإمالة الكشاف إلى الأعلى قد ترفعها، لذلك خذ الرقم من بيانات الصانع عند ميلها المركّب.
ما حدّا شدة الإضاءة للمستوى 1 والمستوى 2؟
خارج فترة الحظر، يعطي Table 3.3 حدّين للشدة. يُطبَّق المستوى 1 على الإضاءة الجديدة. المستوى 2 أعلى، ويحتاج إلى سابقة من إضاءة قائمة قريبة. تتحقق الأداة من المستوى 1.
أمثلة محلولة
الخلفية
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 4282:2023 Cl 3.2.2Maintenance factor for obtrusive light
- AS/NZS 4282:2023 Cl 3.2.4Curfew and non‑curfew limits
- AS/NZS 4282:2023 Cl 3.2.5Level 1 and Level 2 intensity
- AS/NZS 4282:2023 Cl 3.3.1.3Illuminance and intensity at a window
- AS/NZS 4282:2023 Cl 3.3.1.8.2Upward light ratio of the system
- AS/NZS 4282:2023 Table 3.1Environmental zones
- AS/NZS 4282:2023 Table 3.2Light technical parameter limits
- AS/NZS 4282:2023 Table 3.3Maximum luminous intensities per luminaire
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 1 Oct 2026.
أدوات ذات صلة
- حاسبة مقاس الكابلFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- حاسبة تباعد كواشف الحريقDetector spacing and count for a room or corridor.NZS 4512
- حاسبة دائرة شاحن المركبات الكهربائيةCheck EV chargers for spare capacity, cable size and RCD.AS/NZS 3000AS/NZS 3008.1.2AS/NZS 3008.1.1