ऑब्ट्रूसिव लाइट चेकर
AS/NZS 4282 के अनुसार बाउंड्री खिड़की पर बाहरी रोशनी जाँचें।
Reads AS/NZS 4282:2023. Tables checked 1 Oct 2026.
कोई प्रोजेक्ट आज़माएँ 7
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Check a car-park floodlight at a boundaryWhether a 20 000 lm floodlight 15 m from an upstairs window passes after the curfew.
- Check a bollard path at a boundaryWhether a 500 lm bollard 5 m from a neighbour’s window passes in zone A3.
- Check a tennis court floodlightWhether a 40 000 lm floodlight 20 m from a window passes.
- Check a security light on a houseWhether a 2000 lm wall light 8 m from a neighbour passes.
- Check a light in a rural zoneThe limits for a 5000 lm floodlight 30 m from the boundary in dark zone A1.
- Check a loading dock before the curfewA dock floodlight against the pre-curfew limit.
- Check the upward light of an uplightThe upward light ratio of a façade uplight.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- पर्यावरणीय क्षेत्र
- A2, Low district brightness
- कर्फ्यू के दौरान
- नहीं
- सीमा तक की दूरी
- 10 m
- खिड़की के केंद्र की ऊँचाई
- 1.5 m
- ल्यूमिनेयर
- 1 पंक्ति
खिड़की पर ऊर्ध्वाधर प्रदीप्ति
47.67lx
- ऊर्ध्वाधर प्रदीप्ति सीमा
- 5lx
- खिड़की की ओर सबसे अधिक तीव्रता
- 3,143cd
- प्रति ल्युमिनेयर तीव्रता सीमा
- 7,500cd
- ऊपर की ओर प्रकाश अनुपात
- 0.020
- ऊपर की ओर प्रकाश अनुपात की सीमा
- 0.01
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- पर्यावरणीय क्षेत्रA2, Low district brightness
AS/NZS 4282:2023 Table 3.1
- अवधिकर्फ्यू के बाहर
AS/NZS 4282:2023 Cl 3.2.4
- रखरखाव गुणांक1
AS/NZS 4282:2023 Cl 3.2.2
- खिड़की का केंद्र10 m out, 1.5 m up
AS/NZS 4282:2023 Cl 3.3.1.3
- पीक तीव्रता I04,775cd
- बीम अक्ष से कोण35.8°
- खिड़की की ओर तीव्रता3,143cd
AS/NZS 4282:2023 Cl 3.3.1.3
- खिड़की पर Ev, 2 × 23.836 lx47.67lx
AS/NZS 4282:2023 Cl 3.3.1.3
- खिड़की पर ऊर्ध्वाधर प्रदीप्तिपरिणाम47.67lx
AS/NZS 4282:2023 Cl 3.3.1.3
- ऊर्ध्वाधर प्रदीप्ति सीमा5lx
AS/NZS 4282:2023 Table 3.2
- खिड़की की ओर सबसे अधिक तीव्रता3,143cd
AS/NZS 4282:2023 Cl 3.3.1.3
- प्रति ल्युमिनेयर तीव्रता सीमा, स्तर 17,500cd
AS/NZS 4282:2023 Table 3.3
- क्षैतिज से ऊपर ल्यूमेन400lm
AS/NZS 4282:2023 Cl 3.3.1.8.2
- कुल ल्यूमेन20,000lm
AS/NZS 4282:2023 Cl 3.3.1.8.2
- ऊपर की ओर प्रकाश अनुपात0.02
AS/NZS 4282:2023 Cl 3.3.1.8.2
- ऊपर की ओर प्रकाश अनुपात की सीमा0.01
AS/NZS 4282:2023 Table 3.2
इस कैलकुलेटर के बारे में
How this is calculated
The tool estimates the light a floodlight or bollard puts on a neighbour window. It checks the result against AS/NZS 4282:2023.
- Zone and period. You pick the environmental zone, A0 to A4, and whether the curfew applies. Table 3.1 defines the zones. Cl 3.2.4 sets the curfew period.
- Intensity toward the window. The tool takes the beam angle and the tilt of each luminaire. It finds the angle off the beam axis. It then reads the intensity at that angle from a simple lobe (Cl 3.3.1.3).
- Vertical illuminance. For each luminaire, it divides the intensity by the squared distance to the window. It applies the maintenance factor of Cl 3.2.2 and adds the luminaires.
- Illuminance limit. Table 3.2 gives the vertical illuminance limit for the zone and period.
- Intensity limit. Table 3.3 gives the intensity limit for one luminaire. The tool uses the Level 1 value.
- Upward light ratio. Cl 3.3.1.8.2 gives the share of lumens above the horizontal. Table 3.2 gives the limit.
| Step | Table or clause | What it decides |
|---|---|---|
| Zone | AS/NZS 4282:2023 Table 3.1 | The environment class of the site |
| Illuminance at the window | Cl 3.3.1.3 | The vertical light on the window |
| Illuminance limit | Table 3.2 | The most light allowed at the window |
| Intensity limit | Table 3.3 | The most intensity from one luminaire |
| Upward light ratio | Cl 3.3.1.8.2 | The share of light sent above the horizontal |
Worked example
- Two floodlights at a window 10 m away. Each unit gives 10,000 lm, mounted at 6 m and tilted 30°. Zone A2 applies outside the curfew. The tool gives 47.67 lx at the window against a limit of 5 lx, so it fails. The intensity of 3,143 cd is under the limit of 7,500 cd. The upward light ratio is 0.020 against 0.01, so that check also fails.
Limits
The result is a point-source estimate. A site measurement rules. The tool uses a lobe in place of the photometric file from the maker. Use the maker intensity table when you have it. Only direct light counts. Reflected light and obstructions are not modelled.
Level 1 intensity applies. Level 2 needs a precedent from existing lighting (Cl 3.2.5). Tilting a luminaire can raise the upward fraction, so type the value at the aiming angle.
See also: Obtrusive light and the 4282 zones, Car park floodlight obtrusive light at a boundary and the lighting lumen tool.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
मेरी साइट पर कौन सा एनवायरनमेंटल ज़ोन लागू होता है?
ज़ोन इलाके की प्लानिंग ज़ोनिंग का पालन करता है, भविष्य की ज़ोनिंग समेत। ज़्यादातर सबर्ब A3 हैं, विरल ग्रामीण और अर्ध-ग्रामीण इलाके A2, और टाउन सेंटर व इंडस्ट्रियल इलाके A4। जहाँ साफ़ न हो, काउंसिल से पूछें।
कर्फ़्यू क्या है?
कर्फ़्यू वह देर रात की अवधि है जब कम सीमाएँ लागू होती हैं। जब तक काउंसिल या कंसेंट कोई और घंटे तय न करे, इसे रात 11 बजे से सुबह 6 बजे तक मानें। उस दौरान जलती रहने वाली लाइटें जाँचने के लिए कर्फ़्यू चालू करें।
टूल अपने उत्तर को अनुमान क्यों कहता है?
यह ल्यूमिनेयर की हर पंक्ति को एक चिकनी बीम वाला एक बिंदु मानता है। असली फ़्लडलाइट की अपनी तीव्रता टेबल होती है, और साइट पर दीवारें, पेड़ और रिफ़्लेक्शन होते हैं। अंतिम उत्तर के लिए फ़ोटोमेट्रिक गणना या साइट मापन इस्तेमाल करें।
ल्यूमिनेयर का अपवर्ड फ़्रैक्शन क्या है?
उसके ल्यूमेन का वह हिस्सा जो एमिंग कोण पर क्षैतिज से ऊपर निकलता है। एक पूरी तरह कट-ऑफ़ ल्यूमिनेयर जो समतल लगा हो, उसका 0 है। फ़्लडलाइट को ऊपर झुकाने से यह बढ़ सकता है, इसलिए लगे हुए टिल्ट पर निर्माता के डेटा से आंकड़ा लें।
लेवल 1 और लेवल 2 इंटेंसिटी सीमाएँ क्या हैं?
कर्फ़्यू के बाद, Table 3.3 दो तीव्रता सीमाएँ देता है। लेवल 1 नई लाइटिंग पर लागू होता है। लेवल 2 ऊँचा है, और उसके लिए पास की मौजूदा लाइटिंग से पूर्व-उदाहरण चाहिए। टूल लेवल 1 जाँचता है।
हल किए गए उदाहरण
बैकग्राउंड
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 4282:2023 Cl 3.2.2Maintenance factor for obtrusive light
- AS/NZS 4282:2023 Cl 3.2.4Curfew and non‑curfew limits
- AS/NZS 4282:2023 Cl 3.2.5Level 1 and Level 2 intensity
- AS/NZS 4282:2023 Cl 3.3.1.3Illuminance and intensity at a window
- AS/NZS 4282:2023 Cl 3.3.1.8.2Upward light ratio of the system
- AS/NZS 4282:2023 Table 3.1Environmental zones
- AS/NZS 4282:2023 Table 3.2Light technical parameter limits
- AS/NZS 4282:2023 Table 3.3Maximum luminous intensities per luminaire
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 1 Oct 2026 को जाँची गईं।
संबंधित टूल
- केबल आकार कैलकुलेटरFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- फ़ायर डिटेक्टर स्पेसिंग कैलकुलेटरDetector spacing and count for a room or corridor.NZS 4512
- EV चार्जर सर्किट कैलकुलेटरCheck EV chargers for spare capacity, cable size and RCD.AS/NZS 3000AS/NZS 3008.1.2AS/NZS 3008.1.1
क्या यह उपयोगी था?
कोई सवाल, या कोई मान गलत लगता है? हमसे संपर्क करें।