备用容量计算器
判断新增负荷能否接入供电的总开关。
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
尝试一个工程 4
每项工作都会预填示例数值。请替换为您自己的数值。
- Check a heat pump fits the supplyA heat pump drawing 2.5 kW against a 63 A main that logged 41 A.
- Check a spa fits a three‑phase boardA 25 A spa on the lightest phase of an 80 A supply.
- Find submain demand by limitationA submain demand from the breakers it feeds, against its 100 A main.
- Check a 22 kW charger fits a factoryA 22 kW three‑phase load on a 200 A supply limited to 160 A.
输入
使用默认输入值的示例计算。
- 相
- 单相
- 相电压
- 230 V
- 总开关额定值
- 63 A
- 最大需量依据
- 测量,Cl 2.2.2(c)
- L1 记录需量
- 38 A
- 每相计算需量
- 0 A
- 新增负荷,输入
- 安培
- 新增负荷
- 20
新增负荷后的剩余
5A
- 最大需量
- 38A
- 备用容量
- 25A
- 每相新增负荷
- 20A
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 方法测量值,30 分钟内的最高需量
AS/NZS 3000:2018 Cl 2.2.2(c)
- L1 记录需求量38A
AS/NZS 3000:2018 Cl 2.2.2(c)
- 每相总开关额定值63A
- L1 剩余容量25A
- L1 增加新负载后的剩余结果5A
关于此计算器
How this is calculated
The tool finds the maximum demand of an existing supply. It then finds the spare capacity against the main switch, per phase. It also checks whether a new load fits. It reads AS/NZS 3000:2018 Cl 2.2.2.
- Maximum demand by measurement. You enter the highest demand recorded over 30 minutes on each phase (Cl 2.2.2(c)).
- Calculated demand. You can also enter a calculated demand per phase. The tool uses the larger of the two, because a measured demand above the calculated one is the maximum demand (Cl 2.2.2).
- Maximum demand by limitation. The tool takes one fixed or adjustable circuit-breaker setting as the demand on every phase (Cl 2.2.2(d)). For mains and submains, you can enter the breakers they feed. The tool adds their settings per phase. A three‑pole breaker counts on each phase.
- Spare capacity. It subtracts the maximum demand from the main switch rating, per phase.
- New load. A load in kW becomes amps at its power factor and the phase voltage. A three‑phase load splits equally across the phases. A single‑phase load goes on the phase you choose.
- Fit. It adds the new load to the maximum demand on each phase. The load fits when every phase stays at or below the main switch rating.
| Step | Table or clause | What it decides |
|---|---|---|
| Measurement | Cl 2.2.2(c) | The highest demand over the recording period |
| Measured above calculated | Cl 2.2.2 | Which of the two figures is the maximum demand |
| Limitation | Cl 2.2.2(d) | The demand from breaker settings |
| Spare capacity | Cl 2.2.2 | The room left on each phase |
Worked example
- 63 A single‑phase house, 41 A recorded, 36 A calculated, a 3.5 kW heat pump at 0.9 power factor. The recorded demand is above the calculated demand, so the maximum demand is 41 A. The spare capacity is 22 A. The heat pump draws 16.91 A. That leaves 5.09 A, so it fits.
Limits
- The tool takes the main switch rating as the capacity. The supply fuse or the network agreement can be lower. Check both.
- A recording is only as good as the day you take it. Record when the demand is at its highest.
- The sum of breaker settings takes no diversity. It is the largest of the methods and is often above the main switch.
- The tool does not size the cable or the protection for the new load. Use the cable size calculator and the RCD selection tool.
See also: Maximum demand by measurement and limitation, Will a heat pump fit a 63 A supply?, EV charger spare capacity on a 63 A main switch, EV charging load and spare capacity and the EV charger calculator.
问题
结果仅供设计参考。请依据现行标准核对。
如何求出现有住宅的最大需量?
AS/NZS 3000 Cl 2.2.2 允许采用计算、评估、测量或限定方式。对于现有供电,应记录需量,并取住宅用电最繁忙时段内 30 分钟的最大值。智能电表的间隔数据也可提供该值。
若计算需量高于记录需量,该怎么办?
两项均需输入。本工具按各相取较大值。依据 Cl 2.2.2,记录的需量高于计算值时即作为最大需量,因此较低的读数不会掩盖计算负荷。
按限值确定的最大需量是什么?
断路器可决定需量:固定型取其额定值,可调型取其负荷整定值。对于进线和分支干线,其所供断路器整定值之和也计入。该和值未计及同时系数,因此偏高。
单相负荷应接在哪一相?
将其接在备用容量最大的相上。工具显示每相的剩余容量,并使超过总开关额定值的相判定为不合格。
总开关是否为真正的限值?
工具以总开关额定值作为容量。供电熔断器、进户电缆及网络接入协议所限容量可能更低。在增加负荷前,请先核对这些项目。
本工具读取的条款和表格
- AS/NZS 3000:2018 Cl 2.2.2(c)Maximum demand by measurement
- AS/NZS 3000:2018 Cl 2.2.2(d)Maximum demand by limitation
- AS/NZS 3000:2018 Cl 2.2.2Maximum demand by measurement and by limitation
表格最后核对于 1 Oct 2026。
相关工具
这是否有用?
有问题,或数值看起来有误?联系我们。