跳至内容
AmpSize

展览与游乐场布线检查器

展览布线的 RCD 检查,以及现场布线深度和高度。

Reads Electricity (Safety) Regulations 2010 and AS/NZS 3002:2021. Tables checked 1 Oct 2026.

输入

使用默认输入值的示例计算。

国家
新西兰
布线
展览或嘉年华的临时布线
供电方式
电气装置接入设施
末端分路额定值
20 A
RCD 额定剩余电流
30 mA

最大额定剩余电流

30mA

本条款适用的终端分支回路额定值
No cap in the clause
定期评估间隔
1 年 最长

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 供电方式Event wiring fed from a connection facility (Cl 3.2.1)

    AS/NZS 3002:2021 Cl 3.2.1

  2. 最大额定剩余电流结果30mA

    AS/NZS 3002:2021 Cl 3.2.1.2

  3. 本条款适用的末端分路额定值该条款未设额定值上限

    AS/NZS 3002:2021 Cl 3.2.1.2

  4. 条款要求的装置Type A minimum, to AS/NZS 61008.1, AS/NZS 61009.1 or IEC 62423

    AS/NZS 3002:2021 Cl 3.2.1.2

  5. 装置须适用的导体每根带电导体,即所有相线及中性线

    AS/NZS 3002:2021 Cl 3.2.1.2

  6. HRC 熔断器底座,最低 IP 等级IP2X, rated with the fuse carrier taken out

    AS/NZS 3002:2021 Cl 2.4.2.1

  7. 接线设施外壳,最低 IP 等级IP23 to AS 60529, with as many cables terminated as the enclosure allows, or under an equally protective cover

    AS/NZS 3002:2021 Cl 2.7.6.2

  8. 嘉年华或游乐场的定期评估间隔最长 1 年

    Electricity (Safety) Regulations 2010 reg 75(1)

关于此计算器

How this is calculated

The tool checks the RCD protection of show, carnival and fair ground wiring. It reads AS/NZS 3002:2021 and the Electricity (Safety) Regulations 2010.

  1. Method of supply. You pick how the event wiring is supplied. The tool reads Cl 3.2.1 for that method.
  2. Rated residual current. It reads the maximum from Cl 3.2.1.2 and compares your device with it.
  3. Final subcircuit rating. It says whether the clause caps the rating of the subcircuit it applies to.
  4. Device and conductors. It names the device the clause calls for, and the conductors it must operate in.
  5. Enclosures. It gives the lowest IP rating for an HRC fuse base (Cl 2.4.2.1) and a connection facility (Cl 2.7.6.2).
  6. Interval. It gives the reg 75(1) assessment interval for a carnival or fair ground.

Worked example

Limits

The tool compares the rated residual current only. It does not check the device type or the number of poles. It does not decide whether an exception applies. The depth and height checks cover installation wiring only. AmpSize holds pages 1 to 21 of the standard. It does not hold Section 4, or Appendices C and D.

The tool suits a check of event wiring before it connects. It compares the rating you enter with the clause. It does not replace the check by a competent person that Cl 3.2.1.1 describes. Record where the overcurrent and RCD devices sit, so supply can return fast after a trip.

See also: RCD selection, RCD types and where required and Assessment intervals.

问题

结果仅供设计参考。请依据现行标准核对。

展览与游乐场布线工具有什么作用?

工具报告 AS/NZS 3002:2021 对安装布线和展览与游乐场布线规定的 RCD 数据。对于安装布线,工具还会在预计使用长桩的情况下检查沟槽深度,并检查架空高度。它列出 HRC 熔断器底座和连接设施外壳的 IP 防护等级。在新西兰,它报告 reg 75 的周期。

游乐场或活动场所需要什么 RCD?

Clause 2.5.1 涵盖装置布线。它要求额定电流不超过 32 A 的终端分支回路设置 30 mA 保护,包括通往插座、照明或直接连接的、具有较高电击风险设备的回路。Clause 3.2.1.2 要求所有 活动布线 无论额定值如何均设 30 mA 保护。该装置为 A 型或更高类型,并断开所有相线和中性线。

展会场地的电缆覆土深度须达到多少?

对于装置布线,Clause 2.7.4 在可合理预见存在长钉时要求 1.0 m 或以上。此处“长”指超过 400 mm 的钉子或锚桩。较浅的沟槽需额外机械防护,本工具将这四项条件一并列出。活动布线有其自身的条文,AmpSize 未收录。

为何工具不给出架空导线档距?

在 AmpSize 的版本中,Clause 2.7.5.4.3 中 Table 3.1 的各列排版错位。因此 AmpSize 无法将导体类型和截面与跨距对应。该表涉及生命安全,因此 AmpSize 未予收录。请从标准中查取跨距。

游乐场装置多久评估一次?

在新西兰,reg 75(1)(d) 规定依据 AS/NZS 3002 的评估间隔不得超过 1 年。AmpSize 仅收录该标准第 1 至 21 页,因此不涵盖 Section 4 的程序或 Appendix C 和 Appendix D。澳大利亚的检验周期规定在 AmpSize 未收录的条款中。

计算示例

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 1 Oct 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。