RCD 选型计算器

检查是否需要 RCD,并测试动作时间。

Reads Electricity (Safety) Regulations 2010 and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

输入

使用默认输入值的示例计算。

国家
新西兰
安装
住宅
终端分支回路
插座
回路额定值
20 A
插座额定值
10 A
防护职责
电击防护
额定剩余电流
30 mA
检查实测跳闸时间
否

附加RCD保护

要求值,30 mA

条款要求的额定剩余电流
30mA
该工况下的最大额定剩余电流
30mA
额定剩余电流时的限值
300ms
5 倍额定值时的限值
40ms
最长切断时间
0.4s

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 需要附加保护是

    AS/NZS 3000:2018 Cl 2.6.3.3.1

  2. 条款要求的额定剩余电流30mA

    AS/NZS 3000:2018 Cl 2.6.3.3.1

  3. 该工况的最大额定剩余电流30mA

    Electricity (Safety) Regulations 2010 reg 24

  4. 额定剩余电流时的动作限值300ms

    Electricity (Safety) Regulations 2010 reg 24

  5. 额定剩余电流五倍时的动作限值40ms

    Electricity (Safety) Regulations 2010 reg 24

  6. 最长断开时间0.4s

    AS/NZS 3000:2018 Cl 5.7.2

  7. 在此电流或更低电流下不得跳闸15mA

    Electricity (Safety) Regulations 2010 reg 24

关于此计算器

How this is calculated

The tool says whether a circuit needs additional RCD protection. It picks the rated residual current. It can also test a measured trip time against the limits.

  1. Need. The tool reads the installation and the circuit type. It decides whether Clause 2.6.3.3.1 of AS/NZS 3000:2018 asks for additional protection.
  2. Rated current. It gives the rated residual current that the clause requires for that circuit.
  3. Maximum for the duty. In New Zealand you pick the duty: shock, property, patient or children. The tool gives the highest rated residual current for that duty (Electricity (Safety) Regulations 2010 reg 24).
  4. Trip limits. It gives the trip limit at the rated residual current. It also gives the limit at five times that current (reg 24).
  5. Disconnection time. It gives the maximum disconnection time (Cl 5.7.2).
  6. Measured result. If you enter two trip times, the tool compares them with the limits. It also gives the current below which the device must not trip.
StepTable or clauseWhat it decides
Need for protectionCl 2.6.3.3.1Whether the circuit needs an RCD
Rated current and trip limitsReg 24The rating and the trip times by duty
Disconnection timeCl 5.7.2The longest time to clear

Worked example

Limits

  • The tool does not choose a make or model. It does not check discrimination between RCDs.
  • It does not test nuisance tripping from earth leakage. A circuit with high leakage needs a site test.
  • The type of RCD (A, F or B) comes from the equipment on the circuit. See the learn page on RCD types.
  • The tool reads AS/NZS 3000:2018. Check the regulations for later changes.
  • Australia caps the circuit and New Zealand caps the socket‑outlet in some cases. Check the hint on the form.

See also: RCD types and where they are required, Testing to Section 8 and Wet area zones.

问题

结果仅供设计参考。请依据现行标准核对。

RCD 选型工具有什么作用?

工具报告所检查的条款是否要求在终端分支回路上使用 RCD 作附加保护。它给出该用途的最大额定剩余电流和最大动作时间。它还将额定电流下及其五倍电流下实测的动作时间与上述限值进行比较。

它采用哪些条款和法规?

新西兰的回路依据 AS/NZS 3000:2018 Clause 2.6.3.3,澳大利亚的回路依据 Clause 2.6.3.2.2 或 Clause 2.6.3.2.3.3。新西兰电动汽车回路若为住宅用途,依据 Clause 7.9.3,否则依据 Clause 7.9.4。住宅 Mode 2 回路还需满足 Clause 2.6.3.3.1 规定的 30 mA。跳闸限值依据《Electricity (Safety) Regulations 2010》reg 24,切断时间依据 Clause 5.7.2。

新西兰 RCD 动作时间的限值是多少?

额定剩余动作电流不超过 30 mA 的人身防护 RCD,在其额定剩余电流下的限值为 300 ms。在该电流的五倍时,限值为 40 ms。财产保护采用额定值不超过 300 mA 的 RCD,其限值为 0.5 s 和 0.15 s。

为何 40 A 回路不显示任何要求?

在澳大利亚,非住宅装置时本工具读取 Clause 2.6.3.2.3.3。该条款适用于额定值为 32 A 或以下的终端分支回路,因此超过该值时本工具不给出结果。Clause 2.6.3.2.2 适用于澳大利亚住宅装置的所有终端分支回路,不论额定值。新西兰住宅条款同样没有额定值上限。

本工具是否涵盖医疗及患者区域?

仅部分适用。工具报告法规第 24 条规定的 10 mA 患者限值。它不适用 AS/NZS 3003 患者区域标准。在医疗场所请阅读该标准。工具依据 Amendment 1 读取 AS/NZS 3000。EV 及澳大利亚住宅各行读取修订 1 至 3 的汇编版本。修订 2 修改了 Clause 2.6.3 的部分内容;请核对其现行文本。

计算示例

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 27 Sept 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。