最小导体截面查询

查阅回路允许的最小导体截面。

Reads AS/NZS 3000:2018. Tables checked 26 Sept 2026.

输入

使用默认输入值的示例计算。

回路用途
插座
导体材料
铜
并联导体
否

最小导体规格

2.5mm²

Table 3.3 数值
2.5mm²
受以下规定约束
AS/NZS 3000:2018 Table 3.3

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. Table 3.3 最小截面2.5mm²

    AS/NZS 3000:2018 Table 3.3

  2. 适用的最小规格结果2.5mm²

    AS/NZS 3000:2018 Table 3.3

关于此计算器

How this is calculated

The tool looks up the smallest conductor that AS/NZS 3000:2018 Table 3.3 allows for a use. It is a table lookup. It does not size a cable for current or voltage drop.

  1. Use. You pick the use: socket‑outlets, other circuits, signal and relay control, bare conductors, insulated flexible conductors or aerial wiring.
  2. Material. You pick copper or aluminium. Table 3.3 has no aluminium row for some uses. The tool then refuses and says so.
  3. Table value. The tool reads the minimum cross-sectional area from Table 3.3 for that use and material.
  4. Parallel conductors. You can mark the conductors as run in parallel. The tool then compares the table value with the parallel floor and keeps the larger.
  5. Size that applies. The tool gives the minimum size that applies, and names Table 3.3 as the source.
StepTable or clauseWhat it decides
Table valueAS/NZS 3000 Table 3.3The smallest area for the use and material
Parallel floorCl 3.4.3The floor for a parallel group
Size that appliesTable 3.3The larger of the two

Worked example

Aerial wiring in copper. The tool gives 6 mm². The Table 3.3 value is also 6 mm², and the source is AS/NZS 3000:2018 Table 3.3.

Limits

  • Table 3.3 carries two exceptions. Read them before you use the size.
  • Exception 1 can allow a smaller socket‑outlet conductor. It sets conditions that you must meet first.
  • The minimum is a floor. The cable must also pass current capacity, voltage drop and fault checks.
  • Use the cable size calculator for those checks.
  • Clause 3.4.3 sets more conditions on a parallel group than a minimum size.
  • The tool does not read AS/NZS 3008.1.

See also: Cable size calculator, Voltage drop calculator and What size breaker for 4 mm² cable.

问题

结果仅供设计参考。请依据现行标准核对。

插座回路需要的最小电缆截面是多少?

AS/NZS 3000:2018 Table 3.3 规定插座回路应采用 2.5 平方毫米 的导体。Exception 1 允许采用较小截面的导体,但仅限于其规定的条件。在采用低于表中数值的导体之前,请完整阅读 Exception 1。本工具会报告表中数值,并指向 Exception 1。

控制或信号回路的最小截面是多少?

Table 3.3 规定其他回路为 1 mm²,继电器控制及信号回路为 0.5 mm²。裸导体为 6 mm²。绝缘软导线为 0.75 mm²。

架空布线需要多大的截面?

Table 3.3 规定铜质架空布线为 6 mm²,铝质架空布线为 16 mm²。请在表单中选择材料,以查看适用数值。

并联连接电缆是否会改变最小值?

是的。AS/NZS 3000:2018 Clause 3.4.3 规定并联组中每根电缆的最小截面为 4 mm²。该条款还设定了其他条件。设计并联线路前,请完整阅读该条款。