跳至内容
AmpSize

最大需量计算器

估算家用或非家用负荷的最大需量。

Reads AS/NZS 3000:2018 and Electricity (Safety) Regulations 2010. Tables checked 19 Sept 2026.

输入

使用默认输入值的示例计算。

负荷表
Table C1 · 住宅
安装
单户住宅或单个居住单元
相
单相
相电压
230 V
负荷组
4 行

最大需量

50.43A

每相
50.43A
A(i) · Lighting
5A
B(i) · Socket-outlets and permanently connected equipment up to 10 A
15A
C · Ranges, cooking appliances and laundry equipment
17.39A
F · Storage water heaters
13.04A

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 负荷表C1 · single domestic

    AS/NZS 3000:2018 Table C1

  2. A(i) · Lighting5A

    AS/NZS 3000:2018 Table C1

  3. B(i) · Socket‑outlets and permanently connected equipment up to 10 A15A

    AS/NZS 3000:2018 Table C1

  4. C · Ranges, cooking appliances and laundry equipment17.39A

    AS/NZS 3000:2018 Table C1

  5. F · Storage water heaters13.04A

    AS/NZS 3000:2018 Table C1

  6. 最大需量50.43A

    AS/NZS 3000:2018 Table C1

  7. 每相最大需量结果50.43A

    AS/NZS 3000:2018 Table C1

关于此计算器

How this is calculated

The tool works out the maximum demand of an installation from its loads. It follows the load group method of AS/NZS 3000 Appendix C.

  1. Table. Table C1 covers domestic installations: one house or living unit, or a block of living units. Table C2 covers other installations. For Table C2 you pick the occupancy.
  2. Load groups. You enter each load in its group, such as lighting points, socket‑outlet points or kW of cooking. The tool lists only the groups the table assesses for your choice.
  3. Group demand. Each group has its own rule for its load. The tool applies that rule and gives the group demand in amperes. It converts each kW load at the phase voltage you enter.
  4. Living units per phase. A block of living units can take more than one phase. The tool then divides the units by the number of phases and rounds up. It reads the column for that number of units per phase.
  5. Total. The maximum demand is the sum of the group demands.
  6. Per phase. On three phases, the tool divides the total by three. That assumes you spread the load evenly over the phases. Where you cannot, allocate the loads per phase and check the heaviest phase.
StepTable or clauseWhat it decides
Domestic loadsAS/NZS 3000 Table C1The rule for each load group in a house or a block of living units
Other loadsAS/NZS 3000 Table C2The rule for each load group, by occupancy
Living units per phaseTable C1 Note 2The column a block of living units reads on more than one phase
Total and per phaseTable C1 or Table C2The sum of the groups and the share on each phase

Phase voltage

Enter the phase voltage, line to neutral, such as 230 V. The tool converts every kW load at that voltage. The 400 V between lines would read every kW group 42 % low. On a three‑phase supply the tool refuses a line voltage and asks for the phase voltage.

Common installations, worked with the tool

Each line states its loads. Every line uses a phase voltage of 230 V.

  • House on one phase. It uses Table C1 for one house. The loads are 30 lighting points, 25 socket‑outlet points, 8 kW of cooking and a 3 kW storage water heater. The maximum demand is 50.43 A.
  • The same house on three phases. The maximum demand is 16.81 A per phase and 50.43 A over all phases.
  • Block of 12 living units on three phases. Table C1 for blocks of living units, with the same load rows. The tool reads 4 units per phase. The maximum demand is 75 A per phase and 225 A over all phases.
  • Office on three phases. It uses Table C2 for factories, shops and offices. The loads are 10 kW of lighting, 20 socket‑outlets and motors of 15 A, 10 A and 5 A. The maximum demand is 44.93 A per phase and 134.78 A over all phases.

New Zealand and Australia

AS/NZS 3000 Appendix C applies in both countries, so the tool has no country select.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

See also: Commercial maximum demand with Table C2, Domestic maximum demand with Table C1 and Maximum demand and diversity.

问题

结果仅供设计参考。请依据现行标准核对。

最大需量计算器有什么作用?

工具对您添加的每个负荷组应用需量规则。它列出每组的需量(安培),然后报告总需量和每相需量。每一行都显示产生该结果的表及列。

最大需量计算器使用哪些 AS/NZS 3000 表格?

单户住宅或居住单元组采用 AS/NZS 3000:2018 Table C1。其他装置采用 Table C2,并按居住或商业列选择。请先选择表格和模式,因为它们会改变每个负荷组所遵循的规则。

每个负荷组的需量规则由什么决定?

表格和模式决定每个负荷组适用的规则。供电电压将以千瓦给出的负荷组换算为安培。相数用于除以总量。在居住单元模式下,每相的单元数决定结果。请输入单元总数和相数。

三相时如何计算居住单元?

工具按 Table C1 Note b 的要求,将单元数除以三。部分负荷组需要逐项列出,而非单一数量。部分负荷组按评估计,不另行累加。法规 59 的阈值上方会显示一条注释。

可以分享或保存需量计算吗?

是的。表格、模式、电压、相数以及每一行负荷都保存在页面地址中。复制链接,即可将同一需量评估发送给他人。以项目名称保存需要账户。默认采用新西兰条件。

计算示例

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 19 Sept 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。