英制电缆截面换算器
求出旧式英制电缆的保护装置额定值。
Reads AS/NZS 3000:2018. Tables checked 26 Sept 2026.
输入
使用默认输入值的示例计算。
- 英制电缆规格
- 7/.029
- 敷设方式
- 未封闭
- 绝缘
- V75
断路器最大额定值
32A
- 现有熔断器或插入式断路器
- 20A
- 计算截面积
- 2.98mm²
- 最接近的公制规格
- 2.5mm²
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 导体中的导线数7
- 导线直径,英寸0.03
- 计算导体截面积2.98mm²
- 最接近的公制规格2.5mm²
- 最大断路器额定值结果32A
AS/NZS 3000:2018 Table I1
- 现有可重接熔断器或插入式断路器的最大额定值20A
AS/NZS 3000:2018 Table I1
关于此计算器
How this is calculated
The tool finds the largest fuse or circuit-breaker for an old imperial-size cable. You use it when you alter or repair existing wiring. It reads AS/NZS 3000:2018 Appendix I, Table I1.
- Wires. You pick the size as the wire count and the wire diameter in inches, such as 7/.029.
- Calculated area. The tool works out the conductor area from the wire count and the diameter. This is a calculation. It is not a table value.
- Nearest metric size. It gives the nearest metric size for that area.
- Method and insulation. You pick how the cable is installed, unenclosed or partially surrounded, and the insulation, V75 or V60.
- Circuit-breaker rating. The tool reads the maximum circuit-breaker rating from Table I1.
- Existing device. It also reads the maximum rating for an existing rewireable fuse or plug-in circuit-breaker.
| Step | Table or clause | What it decides |
|---|---|---|
| Maximum rating | AS/NZS 3000 Table I1 | The largest breaker for the size, method and insulation |
| Existing device | Table I1 and Cl 2.5.2 | The largest fuse or plug-in breaker already in place |
Worked example
A 7/.029 conductor, unenclosed, with V75 insulation. The calculated area is 2.98 mm². The nearest metric size is 2.5 mm². The maximum circuit-breaker rating is 32 A. The maximum existing fuse or plug-in breaker is 20 A.
Limits
- Check the scope of Appendix I. It is written for existing imperial conductors.
- The second rating is for a device already in place. Read Clause 2.5.2 before you plan a new device.
- The two notes under Table I1 set conditions. Read them on the page.
- Do not use the area for conductors in parallel. Read Paragraph I3 and Table I2.
- The tool does not check voltage drop or the condition of the old insulation.
See also: Cable size calculator, What size breaker for 4 mm² cable and Checking an existing circuit.
问题
结果仅供设计参考。请依据现行标准核对。
英制电缆工具有什么作用?
工具读取 AS/NZS 3000:2018 Table I1。选择英制截面、绝缘和敷设方式。AmpSize 随后报告该表对该导体所列的最大断路器。它还会报告既有熔断器或既有插入式断路器的最大额定值。Appendix I 给出适用范围。
旧回路可以装插入式熔断器吗?
否。AmpSize 仅将Table I1 的第二列视为既有装置。该点由 Clause 2.5.2 规定,该表下的 Note 2 指向该条款。仅在改造或维修中已安装可重绕熔断器或插入式断路器时,才采用该额定值。
公制等效值如何求出?
AmpSize 根据导线根数和直径计算导体截面,然后给出最接近的标准公制规格。该截面为算术结果,而非从标准中查得的数值。AmpSize 未录入 Table I2(并联电缆表格)。对于该情况,请在标准中查阅。
Table I1 的额定值是否适用于所有装置?
否。Table I1 下的 Note 1 规定了额定值成立的条件。请在页面上阅读该注。然后在依赖任何数值之前,检查路径、成组敷设和电压降。
计算示例
本工具读取的条款和表格
- AS/NZS 3000:2018 Cl 2.5.2Protective devices already installed
- AS/NZS 3000:2018 Paragraph I3Imperial conductors in parallel
- I1Protective device ratings for imperial cables in alterations and repairs
表格最后核对于 26 Sept 2026。