英制电缆截面换算器

求出旧式英制电缆的保护装置额定值。

Reads AS/NZS 3000:2018. Tables checked 26 Sept 2026.

输入

使用默认输入值的示例计算。

英制电缆规格
7/.029
敷设方式
未封闭
绝缘
V75

断路器最大额定值

32A

现有熔断器或插入式断路器
20A
计算截面积
2.98mm²
最接近的公制规格
2.5mm²

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 导体中的导线数7
  2. 导线直径,英寸0.03
  3. 计算导体截面积2.98mm²
  4. 最接近的公制规格2.5mm²
  5. 最大断路器额定值结果32A

    AS/NZS 3000:2018 Table I1

  6. 现有可重接熔断器或插入式断路器的最大额定值20A

    AS/NZS 3000:2018 Table I1

关于此计算器

How this is calculated

The tool finds the largest fuse or circuit-breaker for an old imperial-size cable. You use it when you alter or repair existing wiring. It reads AS/NZS 3000:2018 Appendix I, Table I1.

  1. Wires. You pick the size as the wire count and the wire diameter in inches, such as 7/.029.
  2. Calculated area. The tool works out the conductor area from the wire count and the diameter. This is a calculation. It is not a table value.
  3. Nearest metric size. It gives the nearest metric size for that area.
  4. Method and insulation. You pick how the cable is installed, unenclosed or partially surrounded, and the insulation, V75 or V60.
  5. Circuit-breaker rating. The tool reads the maximum circuit-breaker rating from Table I1.
  6. Existing device. It also reads the maximum rating for an existing rewireable fuse or plug-in circuit-breaker.
StepTable or clauseWhat it decides
Maximum ratingAS/NZS 3000 Table I1The largest breaker for the size, method and insulation
Existing deviceTable I1 and Cl 2.5.2The largest fuse or plug-in breaker already in place

Worked example

A 7/.029 conductor, unenclosed, with V75 insulation. The calculated area is 2.98 mm². The nearest metric size is 2.5 mm². The maximum circuit-breaker rating is 32 A. The maximum existing fuse or plug-in breaker is 20 A.

Limits

  • Check the scope of Appendix I. It is written for existing imperial conductors.
  • The second rating is for a device already in place. Read Clause 2.5.2 before you plan a new device.
  • The two notes under Table I1 set conditions. Read them on the page.
  • Do not use the area for conductors in parallel. Read Paragraph I3 and Table I2.
  • The tool does not check voltage drop or the condition of the old insulation.

See also: Cable size calculator, What size breaker for 4 mm² cable and Checking an existing circuit.

问题

结果仅供设计参考。请依据现行标准核对。

英制电缆工具有什么作用?

工具读取 AS/NZS 3000:2018 Table I1。选择英制截面、绝缘和敷设方式。AmpSize 随后报告该表对该导体所列的最大断路器。它还会报告既有熔断器或既有插入式断路器的最大额定值。Appendix I 给出适用范围。

旧回路可以装插入式熔断器吗?

否。AmpSize 仅将Table I1 的第二列视为既有装置。该点由 Clause 2.5.2 规定,该表下的 Note 2 指向该条款。仅在改造或维修中已安装可重绕熔断器或插入式断路器时,才采用该额定值。

公制等效值如何求出?

AmpSize 根据导线根数和直径计算导体截面,然后给出最接近的标准公制规格。该截面为算术结果,而非从标准中查得的数值。AmpSize 未录入 Table I2(并联电缆表格)。对于该情况,请在标准中查阅。

Table I1 的额定值是否适用于所有装置?

否。Table I1 下的 Note 1 规定了额定值成立的条件。请在页面上阅读该注。然后在依赖任何数值之前,检查路径、成组敷设和电压降。

计算示例

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 26 Sept 2026。

这是否有用?