火灾报警布线查询

查阅火灾报警系统的电缆和回路规定。

Reads NZS 4512:2010. Tables checked 26 Sept 2026.

输入

使用默认输入值的示例计算。

回路类型
探测器或手动报警点回路
电缆内的线芯
2

最小导体规格

0.75mm²

需要绞合导体
是
绝缘电阻高于
5MΩ
防火等级
本条款未规定
Clause
402.1

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 适用条款402.1

    NZS 4512:2010 Cl 402.2

  2. 电缆中的芯线2

    NZS 4512:2010 Cl 402.1

  3. 最小导体规格结果0.75mm²

    NZS 4512:2010 Cl 402.1

  4. 需要绞合导体是

    NZS 4512:2010 Cl 402.1

  5. 绞合适用于以下规格1mm²

    NZS 4512:2010 Cl 402.1

  6. 绝缘电阻高于5MΩ

    NZS 4512:2010 Cl 402.2

  7. 耐火等级本条款未规定

    NZS 4512:2010 Cl 402.2

关于此计算器

How this is calculated

The tool looks up what a fire alarm circuit needs from NZS 4512:2010 Clauses 402.1 and 402.2. It gives the conductor size, the stranding, the insulation resistance and the fire rating.

  1. Circuit. You pick the circuit: detector, alerting device, transmission, staged evacuation, data link or mains supply.
  2. Clause. The tool picks the clause. Cl 402.1 covers detector and alerting device circuits. Cl 402.2 covers the rest.
  3. Cores. You enter the number of cores in the cable. The size rule in Cl 402.1 reads it.
  4. Conductor size. The tool gives the minimum conductor size and says whether it must be stranded.
  5. Insulation resistance. From Cl 402.2 it gives the minimum insulation resistance.
  6. Fire rating. It gives the fire rating, or says that this clause does not set one.
StepTable or clauseWhat it decides
Conductor size and strandingNZS 4512 Cl 402.1The smallest conductor and its construction
Insulation resistanceCl 402.2The minimum test result
Fire ratingCl 402.2The rating, where the clause sets one

Worked example

A detector circuit in 2‑core cable. The minimum conductor size is 0.75 mm². The conductor must be stranded. The insulation resistance must be above 5 MΩ. This clause sets no fire rating.

Limits

  • The tool reads Cl 402.1 and 402.2 only. Check the cable specification and the mechanical protection in Cl 402.1.
  • Clause 402.2(g) is the other size driver. Read it in full.
  • Check the earthing rules for zone circuit wiring in Cl 402.2(i).
  • Check the separation and identification rules in Cl 402.2(k).
  • The tool does not check voltage drop on the circuit.
  • NZS 4512:2021 supersedes the 2010 edition this tool reads.

See also: Fire alarm battery, Detector spacing and the segregation checker.

问题

结果仅供设计参考。请依据现行标准核对。

火灾报警回路需要多大的电缆?

NZS 4512:2010 Clause 402.1 规定:两芯电缆每根导体 0.75 mm²;多于两芯的电缆每根导体 0.5 mm²。AmpSize 还报告同一条款中的 1 mm² 绞合阈值。电缆类型及其可接受的防护方式请阅读 Clause 402.1。

哪些火灾报警回路需要耐火电缆?

AmpSize 报告两种情况。Clause 402.2(m) 对于传输回路,依据 AS/NZS 3013 分类 WS11,规定 15 分钟完整性。Clause 402.2(r) 对于分级疏散布线,规定 WS51W。请完整阅读这两条款,因为每条均包含本工具未作检查的条件。

火灾报警系统是否需要独立的供电回路?

是的。Clause 402.2(f) 要求设置独立的分支回路并配置永久性标签。AmpSize 打印该条款规定的标签文字 FIRE ALARM。请阅读 Clause 402.2(f),了解分支回路的起点及标签应设置的位置。

预期的绝缘电阻是多少?

Clause 402.2(j) 规定判定标准为 5 MΩ 以上,AmpSize 会报告该数值。Clause 402.2(i) 和 Clause 402.2(k) 分别规定同一布线的接地和分隔要求。记录测试结果前,请阅读这三条。

本工具能否确认某装置合规?

否。AmpSize 针对所选回路,报告 NZS 4512:2010 Clauses 402.1 和 402.2 的相关数值。它仅供参考,不构成裁定。火灾报警装置须依照整套标准及布线规则进行检查。