跳至内容
AmpSize

线管填充率计算器

检查电缆束能否放入线管。

Reads AS/NZS 3000:2018. Tables checked 19 Sept 2026.

输入

使用默认输入值的示例计算。

国家
新西兰
线管规格
32 mm
电缆
2 行

线管填充率

97.66%

允许填充率
40%
推荐导管
50mm
导管内部面积
539.13mm²
电缆截面积
526.52mm²

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 线管内截面积539.13mm²

    AS/NZS 2053 / AS/NZS 5000 manufacturer data (derived)

  2. 电缆截面积526.52mm²

    AS/NZS 2053 / AS/NZS 5000 manufacturer data (derived)

  3. 填充率(百分比)结果97.66%

    AS/NZS 3000:2018 App C Para C6.2; Tables C10–C12 give a maximum-count guide

  4. 推荐线管50mm

关于此计算器

How this is calculated

The tool checks that a bundle of cables fits in a conduit. It uses the fill percentage method of Paragraph C6.2 in Appendix C of AS/NZS 3000:2018. Appendix C also holds Tables C10 to C12, which list a maximum count of cables instead.

  1. Conduit area. The tool reads the internal area of the conduit size you pick. The data comes from the maker and AS/NZS 2053 sizes. The AmpSize hub marks this value as derived.
  2. Cable area. It reads the overall area of each cable by size and cores. It multiplies by the count and adds the rows.
  3. Fill percent. It divides the cable area by the conduit area.
  4. Permitted fill. It applies the space factor of Paragraph C6.2. The factor is 50 % for one cable and 33 % for two. It is 40 % for three or more.
  5. Result. The tool passes the bundle when the fill is at or below the permitted figure. It gives the smallest conduit that passes.
StepTable or clauseWhat it decides
Fill percentAS/NZS 3000 App C Para C6.2The space factor for the bundle
Maximum countAS/NZS 3000 Tables C10 to C12A guide by cable count

Worked example

Limits

  • The tool does not model bends, pull length or the pulling tension. A long or bent run needs a bigger conduit.
  • It does not apply a derating for cables in conduit. Use the correction factors calculator for that.
  • It reads one conduit. It does not check a trunking or a cable tray.
  • The conduit areas are maker data, not a Standard value. Check them against the conduit you buy.

See also: Conduit fill and installation methods, Conduit fill for 4 x 6 mm² in 25 mm and Appendix C conduit space factor.

问题

结果仅供设计参考。请依据现行标准核对。

线管填充率计算器有什么作用?

工具逐根累加整束电缆的截面积。将该总和除以线管的内部面积,得出线管填充率百分比。它将填充率与允许限值进行比较,并建议能容纳该束电缆的最小公称线管。

工具采用什么填充率限值?

工具对一根电缆采用 50%,两根电缆采用 33%,三根或以上采用 40%。这些是 AS/NZS 3000:2018 Appendix C、段落 C6.2 中的空间系数。同一附录的 Tables C10 至 C12 则给出最大根数的方法。

哪些输入最重要?

线管的公称尺寸决定其内部面积。导体截面、芯数和电缆根数决定电缆所占面积。在相同导体截面下,单芯电缆与多芯电缆的外径不同。因此,所选芯数会改变结果。

常见的注意事项有哪些?

工具采用填充率方法,而非根数方法。外径取自制造商数据,因品牌而异。未考虑弯头和穿线拉力。线管尺寸及电缆条目保存在页面地址中,因此链接可重现该束电缆。

计算示例

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 19 Sept 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。