AmpSize

Voltage drop calculator

Voltage drop calculator for New Zealand and Australia. Conductor impedance comes from AS/NZS 3008.1.2 or 3008.1.1, and the limit from AS/NZS 3000 Clause 3.6.2.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Phases
Three phase
Voltage
400 V
Design current
50 A
Run length
60 m
Power factor
0.9
Standard
NZ · AS/NZS 3008.1.2
Cable
16 mm² Copper PVC 75 °C
Cores
Multicore
Voltage drop limit
5 %
System
Low voltage (limit you set)
Neutral current
0 A

Voltage drop

1.69%

Voltage drop
6.74V
Drop per amp metre
2.25mV/A·m
Maximum length at limit
177.98m
Voltage drop limit
5%

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Resistance1.4Ω/kmAS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
  2. Reactance0.09Ω/kmAS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
  3. mV/A·m2.25mV/A·mAS/NZS 3008.1.2:2017 Cl 4.5
  4. Voltage drop6.74V
  5. Voltage drop percent1.69%
  6. Voltage drop limit5%AS/NZS 3000:2018 Cl 3.6.2
  7. Maximum length177.98m

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

What does the voltage drop calculator do?

The tool reads the resistance and reactance of the conductor. It combines them at the power factor to get the drop in millivolts per amp metre. It then reports the drop in volts and the longest run that still meets the limit. It also gives the drop as a percent of the supply voltage.

What voltage drop limit does AS/NZS 3000 set?

The default limit is 5 percent and you can change it. Choosing extra-low voltage sets the limit to 10 percent from AS/NZS 3000:2018 Clause 7.5.7. A result above the limit is marked as a fail and a warning appears above 80 percent of the limit. Impedance comes from AS/NZS 3008.1.2:2017 Table 30 and Tables 34 to 35.

Which inputs change the voltage drop most?

Design current and run length scale the drop directly. Conductor size, material and insulation set the resistance and reactance. Power factor sets how much reactance adds to the drop. Cables in parallel divide both resistance and reactance by the number of cables.

Why does a three phase result differ from a single phase result?

The tool multiplies by the square root of three for a three phase result. It multiplies by two for a single phase result, because the current flows out and back. The same cable and current therefore give a different drop on each supply type.

Can I share or save a voltage drop result?

Yes. The phases, voltage, current, length, power factor, cable and limit all sit in the page address. Copy the link to send the same calculation to somebody else. Saving under a project name needs an account. In the Standard select, pick AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia, both 2017 editions.

Worked examples

Background

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 24 Sept 2026.