AmpSize

Cable size calculator

Free cable size calculator for New Zealand and Australia. It reads AS/NZS 3008.1.2 or AS/NZS 3008.1.1, both 2017 editions, and checks each size against AS/NZS 3000.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Phases
Three phase
Voltage
400 V
Design current
50 A
Power factor
0.9
Standard
NZ · AS/NZS 3008.1.2
Run length
60 m
Installation method
Enclosed in air
Ambient temperature
30 °C
Grouped circuits
1
Third harmonic content
0 %
Material
Copper
Insulation
PVC 75 °C
Cores
Multicore
Cables in parallel
1
Voltage drop limit
5 %
Check protective device
No
Prospective fault current
0 kA

Conductor size

10mm²

Derated capacity
50A
Voltage drop
2.66%
Earth conductor
4mm²
Total derating factor
1x

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Ambient derating factor1xAS/NZS 3008.1.2:2017 Tables 27(1), 27(2) p.88
  2. Grouping derating factor1xOne circuit, no grouping factor
  3. Soil derating factor1xAS/NZS 3008.1.2:2017 Table 29 p.90
  4. Burial depth derating factor1xAS/NZS 3008.1.2:2017 Tables 28(1), 28(2) p.89
  5. Total derating factor1x
  6. Required tabulated current50AAS/NZS 3000:2018 Cl 3.4
  7. Selected conductor size10mm²AS/NZS 3008.1.2:2017 Table 13 p.62–64
  8. Derated current capacity50AAS/NZS 3000:2018 Cl 3.4
  9. Voltage drop2.66%

About this calculator

How the calculator picks a size

The tool tests every standard conductor size in turn. It reports the smallest size that passes each check you ask for.

  1. Tabulated current. It reads the current each size can carry for your material, insulation, core count and installation method. The Standard select decides which part it reads. It reads AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia. Both are 2017 editions.
  2. Derating. It multiplies the ambient, grouping, soil, burial depth and harmonic reduction factors into one factor. It divides the design current by that factor. Above 33 % third harmonic, it uses the neutral current instead. The result is the current the cable must carry in the table.
  3. Voltage drop. It works out the drop for the run length, the power factor and the conductor. It compares the drop with the limit you set. The default limit is 5 %.
  4. Protective device. If you name a device, its rating must sit at or below the derated capacity. The circuit's earth fault loop impedance must stay under the maximum for that device.
  5. Fault withstand. If you enter a prospective fault current, the conductor must withstand it for the clearing time. The k factor sets that limit. It depends on the material, the insulation and the conductor size.
  6. Result. The tool lists each size that fails and the check it failed. Each step names its table or clause where one applies.

Common circuits, worked with the tool

Each line states its route. Change one input and the size can change, so run your own circuit before you buy cable. Every line uses multicore copper with PVC insulation and one circuit on the route. The power factor is 0.9, except where a line names a different value. Ze is 0.35 Ω and every size uses the New Zealand tables.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 the tool reads. Part 1.2 holds the New Zealand tables. They assume 30 °C air and 15 °C soil. Part 1.1 holds the Australian tables. They assume 40 °C air and 25 °C soil. Both are the 2017 editions. The checks from AS/NZS 3000 are the same in both countries.

A single-phase circuit at 32 A runs 25 m on the Australian tables. It sits enclosed in air at 40 °C, grouped with one other circuit. It needs 10 mm² with a derated capacity of 35.2 A. Open the Australian example.

AmpSize does not hold AS/NZS 3008.1.1:2025. No figure from that edition appears on this site.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

What size cable do I need for a 32 A circuit?

The circuit is single-phase, 32 A, over 25 m. It runs enclosed in air at 35 °C, grouped with one other circuit. The tool selects 10 mm² copper for that route. Its derated capacity is 37.6 A and the voltage drop is 1.42 %. A different route gives a different answer, so enter your own inputs.

Can a 6 mm² cable take 40 A?

Not on a typical route. The route runs 20 m at 40 A single-phase, enclosed in air at 30 °C. On that route, 6 mm² copper fails the current capacity check. The tool selects 10 mm², with 50 A of derated capacity. A shorter run does not change that, because capacity depends on the route, not the length.

What size cable for a 63 A three-phase submain?

The route runs 35 m at 63 A, 400 V, XLPE copper, enclosed in air at 35 °C. The device is a 63 A C curve, and Ze is 0.3 Ω. The tool selects 25 mm² with 95 A derated capacity. 16 mm² meets the current and drop checks but its loop impedance of 0.49 Ω fails Table 8.1.

Does the cable size calculator work for Australia?

Yes. Set Standard to AU · AS/NZS 3008.1.1. The tool then reads the 2017 Australian tables, which use 40 °C air and 25 °C soil. NZ · AS/NZS 3008.1.2 is the default. The AS/NZS 3000 checks, often written AS3000, are the same in both countries. AmpSize does not include the 2025 edition.

Which standard and tables does the result come from?

Single-core ratings come from Tables 4, 5, 7 and 8 of AS/NZS 3008.1.2:2017 or 3008.1.1:2017. Tables 13 and 14 give multicore ratings. Derating comes from Tables 22 and 25 to 29, impedance from Tables 30 to 35. Table 52 gives the k factor. AS/NZS 3000:2018 Tables 5.1 and 8.1 give earth size and maximum Zs.

Worked examples

Background

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 24 Sept 2026.