Cable size calculator
Free cable size calculator for New Zealand and Australia. It reads AS/NZS 3008.1.2 or AS/NZS 3008.1.1, both 2017 editions, and checks each size against AS/NZS 3000.
Inputs
Worked example with the default inputs. The live calculator replaces it when the page loads.
- Phases
- Three phase
- Voltage
- 400 V
- Design current
- 50 A
- Power factor
- 0.9
- Standard
- NZ · AS/NZS 3008.1.2
- Run length
- 60 m
- Installation method
- Enclosed in air
- Ambient temperature
- 30 °C
- Grouped circuits
- 1
- Third harmonic content
- 0 %
- Material
- Copper
- Insulation
- PVC 75 °C
- Cores
- Multicore
- Cables in parallel
- 1
- Voltage drop limit
- 5 %
- Check protective device
- No
- Prospective fault current
- 0 kA
Conductor size
10mm²
- Derated capacity
- 50A
- Voltage drop
- 2.66%
- Earth conductor
- 4mm²
- Total derating factor
- 1x
This result is a design aid. Verify it against the current standard.
Calculation steps
- Ambient derating factor1xAS/NZS 3008.1.2:2017 Tables 27(1), 27(2) p.88
- Grouping derating factor1xOne circuit, no grouping factor
- Soil derating factor1xAS/NZS 3008.1.2:2017 Table 29 p.90
- Burial depth derating factor1xAS/NZS 3008.1.2:2017 Tables 28(1), 28(2) p.89
- Total derating factor1x
- Required tabulated current50AAS/NZS 3000:2018 Cl 3.4
- Selected conductor size10mm²AS/NZS 3008.1.2:2017 Table 13 p.62–64
- Derated current capacity50AAS/NZS 3000:2018 Cl 3.4
- Voltage drop2.66%
About this calculator
How the calculator picks a size
The tool tests every standard conductor size in turn. It reports the smallest size that passes each check you ask for.
- Tabulated current. It reads the current each size can carry for your material, insulation, core count and installation method. The Standard select decides which part it reads. It reads AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia. Both are 2017 editions.
- Derating. It multiplies the ambient, grouping, soil, burial depth and harmonic reduction factors into one factor. It divides the design current by that factor. Above 33 % third harmonic, it uses the neutral current instead. The result is the current the cable must carry in the table.
- Voltage drop. It works out the drop for the run length, the power factor and the conductor. It compares the drop with the limit you set. The default limit is 5 %.
- Protective device. If you name a device, its rating must sit at or below the derated capacity. The circuit's earth fault loop impedance must stay under the maximum for that device.
- Fault withstand. If you enter a prospective fault current, the conductor must withstand it for the clearing time. The k factor sets that limit. It depends on the material, the insulation and the conductor size.
- Result. The tool lists each size that fails and the check it failed. Each step names its table or clause where one applies.
Common circuits, worked with the tool
Each line states its route. Change one input and the size can change, so run your own circuit before you buy cable. Every line uses multicore copper with PVC insulation and one circuit on the route. The power factor is 0.9, except where a line names a different value. Ze is 0.35 Ω and every size uses the New Zealand tables.
- Lighting, 10 A single-phase over 40 m. Enclosed in air at 30 °C with a 10 A C curve device. It needs 2.5 mm² with a 2.84 % drop.
- Socket-outlets, 20 A single-phase over 30 m. Enclosed in air at 30 °C with a 20 A C curve device. It needs 2.5 mm² with a 4.25 % drop, close to the 5 % limit.
- Cooker, 32 A single-phase over 15 m. Enclosed in air at 30 °C with a 32 A C curve device. It needs 6 mm² with a 1.43 % drop.
- Shed supply, 32 A single-phase over 40 m. Enclosed in air at 30 °C with a 32 A C curve device. It needs 6 mm² with a 3.8 % drop.
- EV charger, 32 A single-phase over 25 m. Partly in insulation at 35 °C, with no wiring enclosure. It has a power factor of 1 and a 32 A C curve device. It needs 10 mm² with a 1.55 % drop.
- Single-phase mains, 63 A over 20 m. Enclosed in air at 30 °C with a 63 A C curve device. It needs 16 mm² with a 1.42 % drop.
- Three-phase submain, 100 A at 400 V over 60 m. Enclosed in air at 30 °C. The tool checks no device on this route. It needs 35 mm² with a 1.59 % drop.
New Zealand and Australia
The Standard select picks the part of AS/NZS 3008.1 the tool reads. Part 1.2 holds the New Zealand tables. They assume 30 °C air and 15 °C soil. Part 1.1 holds the Australian tables. They assume 40 °C air and 25 °C soil. Both are the 2017 editions. The checks from AS/NZS 3000 are the same in both countries.
A single-phase circuit at 32 A runs 25 m on the Australian tables. It sits enclosed in air at 40 °C, grouped with one other circuit. It needs 10 mm² with a derated capacity of 35.2 A. Open the Australian example.
AmpSize does not hold AS/NZS 3008.1.1:2025. No figure from that edition appears on this site.
Keep the result
Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.
Questions
Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.
What size cable do I need for a 32 A circuit?
The circuit is single-phase, 32 A, over 25 m. It runs enclosed in air at 35 °C, grouped with one other circuit. The tool selects 10 mm² copper for that route. Its derated capacity is 37.6 A and the voltage drop is 1.42 %. A different route gives a different answer, so enter your own inputs.
Can a 6 mm² cable take 40 A?
Not on a typical route. The route runs 20 m at 40 A single-phase, enclosed in air at 30 °C. On that route, 6 mm² copper fails the current capacity check. The tool selects 10 mm², with 50 A of derated capacity. A shorter run does not change that, because capacity depends on the route, not the length.
What size cable for a 63 A three-phase submain?
The route runs 35 m at 63 A, 400 V, XLPE copper, enclosed in air at 35 °C. The device is a 63 A C curve, and Ze is 0.3 Ω. The tool selects 25 mm² with 95 A derated capacity. 16 mm² meets the current and drop checks but its loop impedance of 0.49 Ω fails Table 8.1.
Does the cable size calculator work for Australia?
Yes. Set Standard to AU · AS/NZS 3008.1.1. The tool then reads the 2017 Australian tables, which use 40 °C air and 25 °C soil. NZ · AS/NZS 3008.1.2 is the default. The AS/NZS 3000 checks, often written AS3000, are the same in both countries. AmpSize does not include the 2025 edition.
Which standard and tables does the result come from?
Single-core ratings come from Tables 4, 5, 7 and 8 of AS/NZS 3008.1.2:2017 or 3008.1.1:2017. Tables 13 and 14 give multicore ratings. Derating comes from Tables 22 and 25 to 29, impedance from Tables 30 to 35. Table 52 gives the k factor. AS/NZS 3000:2018 Tables 5.1 and 8.1 give earth size and maximum Zs.
Worked examples
- AS/NZS 3008 2025 edition: what AmpSize citesThe 2025 edition of AS/NZS 3008.1.1 is not held here. This page shows the 2017 tables the tool reads today, with a worked 100 A three-phase submain.
- Cable size for a 32 A single-phase 25 m runWork through a 32 A single-phase circuit over 25 metres in New Zealand. See every derating factor, the check that sets the size, and the result the tool gives.
Background
- Current-carrying capacity and deratingWhy one cable size has many ratings. Install method, ambient, grouping, soil and depth, with a 25 A circuit that needs 10 mm² once the factors apply.
- The MEN system: earth and neutral at the boardWhy the neutral and the earth are joined at the main switchboard in New Zealand, what the MEN link, the main earthing conductor and the electrode each do.
- Voltage drop basicsOhm's law on a cable, the mV/A·m shortcut, the percent limit and the maximum length, worked on a 25 A run over 35 m of 4 mm² copper.
- IB, IN and IZ: matching a breaker to a cableThe three currents that decide whether a circuit breaker protects its cable, why the order matters, and a worked 32 A circuit that shows the rule being applied.
- Loop impedance and disconnection timeZe, R1+R2, Zs and Ia, and the two disconnection times, worked on a 32 A curve C circuit over 30 m that returns 0.79 Ω against a 0.96 Ω limit.
- Short-circuit withstand and the k factorThe adiabatic check in plain terms: prospective fault current, clearing time and k, worked on 25 mm² copper XLPE at 10 kA for 0.1 s.
Clauses and tables this tool reads
- AS/NZS 3000:2018 Cl 2.5.3.1Protective device coordination
- AS/NZS 3000:2018 Cl 3.4Current-carrying capacity
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit
- AS/NZS 3000:2018 Cl 5.7.4Earth fault loop impedance
- AS/NZS 3008.1.2:2017 Cl 3.5.2.6(a)Groups of circuits in underground wiring enclosures
- AS/NZS 3008.1.2:2017 Cl 3.5.9Third harmonic current in the neutral
- AS/NZS 3008.1.2:2017 Cl 5.3Short-circuit performance
- AS/NZS 3000:2018 Table 5.1Minimum earthing conductor size by active conductor size
Every clause and table, with how each was verified
Tables last checked on 24 Sept 2026.